ML18057A894

From kanterella
Jump to navigation Jump to search
Monthly Operating Rept for Apr 1991 for Palisades Nuclear Plant
ML18057A894
Person / Time
Site: Palisades 
Issue date: 04/30/1991
From: Handlovits S, Mlynarek S
CONSUMERS ENERGY CO. (FORMERLY CONSUMERS POWER CO.)
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
NUDOCS 9105140233
Download: ML18057A894 (4)


Text

"

(

I consumers Power POW ERIN&

MICHl&AN'S PRD&RESS Palisades Nuclear Plant: 27780 Blue Star Memorial Highway, Covert, Ml 49043 May 7, 1991 US Nuclear Regulatory Commission Document Control Desk Washington, DC 20555 LICENSEE REPORT OF MONTHLY OPERATING DATA DPR-20, DOCKET NO 50-255 Enclosed is a copy of the Monthly Operating Data and Summary of Operating Experience for the Palisades Nuclear Plant for the month of April, _1991.

If you have any questions or concerns, please feel free to contact me at (616) 764-8913, extension 0113.

Sincerely, MG Mlynarek _

  • Reactor Engineer CC:

DPHoffman, P26~117B RMRice, Palisades ABDavis, USNRC JLKuemin, Palisades Resident Irispector, Palisades DRHahn, 'Div of Rad Health S~rvites, Lansing, Ml BWJorgensen, Michigan Dept of Labor, Lansing, MI RCallen, Michigan Public Service Commission Records Center, INPO, Atlanta, GA RWTaylor, CE, Palisades AAAlatalo, Palisades HRSnider, P21-129 Administrator, USNRC Document Control, 950*22*35*10/L

-SMH91*012

' 910514<)233. 91043(1

'*" j'\\ "\\

'p[1R: ADOCK 05000255 \\

R PDR

\\ __,

.. l_._

A CMS' ENER5YCOMPANY

OPERATING DATA REPORT OPERATING STATUS:

l.

UNIT NAME

2.

REPORTING PERIOD:

Palisades 910401-910430

3.

LICENSED THERMAL POWER (MWt) 2530.0

4.

NAMEPLATE RATING (GROSS MWe) 811.7

5.

DESIGN ELECTRICAL RATING (NET MWe) 8D5.0 6.. MAXIMUM DEPENDABLE CAPACITY (GROSS MWe)

    • 770
7.

MAXIMUM DEPENDABLE CAPACITY (NET MWe)

    • 730
8.

IF CHANGES OCCUR IN CAPACITY RATINGS (ITEM NUMBERS 3-7) SINCE LAST REPORT, GIVE REASONS:

9.

POWER LEVEL TO WHICH RESTRICTED, IF ANY (NET MWe):

10. REASONS FOR RESTRICTIONS, IF ANY:
11. HOURS IN REPORTING PERIOD
12. NUMBER OF HOURS REACTOR WAS CRITICAL
13. REACTOR RESERVE SHUTDOWN HOURS
14. HOURS GENERATOR ON-LINE
15. UNIT RESERVE SHUTDOWN HOURS
16. GROSS THERMAL ENERGY GENERATED (MWH)
17. GROSS ELECTRICAL ENERGY GENERATED (MWH)
18. NET ELECTRICAL ENERGY GENERATED (MWH)
19. UNIT SERVICE FACTOR
20. UNIT AVAILABILITY FACTOR
21. UNIT CAPACITY FACTOR (USING MOC NET)
22. UNIT CAPACITY FACTOR (USING DER NET)
23. UNIT FORCED OUTAGE RATE This Month 719.0 719.0 719.0 1809167.0 591090.0 562380.0 100.0%

100.0%

107.1%

97.2%

0.0%

24.. SHUTDOWNS SCHEDULED OVER THE NEXT 6 MONTHS (TYPE, DATE AND DURATION OF EACH):

25. IF SHUTDOWN AT END OF REPORT PERIOD, ESTIMATED DATE OF STARTUP:
26. UNITS IN TEST STATUS (PRIOR TO COMMERCIAL OPERATION):

INITIAL CRITICALITY INITIAL ELECTRICITY COMMERCIAL OPERATION

    • Based on condenser backpressure
  • Weighted Average (635 MWe used as MOC Net prior to October 1985)

DOCKET NO 50-255 DATE 04-30-91 COMPLETED BY SMHandlovits TELEPHONE (616)764-8913 NOTES:

Yr-to-Date Cumulative 2879.0 169742.0 1207.9 91409.0 1086.4 87304.0 2289623.0 183042068.0 736780.0 57373315.0 692948.0 53991071. 0 37.7%

51.4%

37.7%

51.4%

33.0%

48.2%*

29.9%

39.5%

3.8%

32.6%

Forecast Achieved

AVERAGE DAILY UNIT POWER LEVEL DOC KET NO __

____;;5~0-'-2=-=5:..=5 UNIT Palisades DATE 05/01/91 COMPLETED BY

_S_M_H_a~nd_._l_o~v,~.t~s MONTH APRIL 1991 TELEPHONE (616)764-8913 DAY AVERAGE DAILY POWER LEVEL DAY AVERAGE DAILY POWER LEVEL (MWe Net)

(MWe Net)

1.

743

17.

791

2.

752

18.

791

3.

754

.19.

791

4.

760

20.

793

5.

767

21.

791 6..

772

22.

791

7.

778

23.

790

8.

780

24.

792

9.

788

25.

792

10.

791

26.

779

11.

792

27.

785

12.

790

28.

785

13.

790

29.

777

14.

787

30.

793

15.

790

16.

791 INSTRUCTIONS:

On this format, list the average daiiy unit power level in MWe-NET for each day in the reporting month.

Compute to the nearest whole megawatt.

SUMMARY

OF OPERATING EXPERIENCE FOR APRIL 1991 The plant began the month at 953 power and achieved 1003 power on the 8th.

The plant maintained full power through the end of the month.