consumers Power POW ERi Nii MICHlliAN"S PROliRESS Palisades Nuclear Plant:
27780 Blue Star Memorial Highway, Covert, Ml 49043 January 16, 1991 Nuclear Regulatory Commission Document Control Desk Washington, DC 20555 DOCKET 50-255 - LICENSE DPR PALISADES PLANT -
GB Slade General Manager REQUEST FOR RELIEF FROM SPECIFIC ASME B&PV CODE REQUIREMENT - CONTAINMENT AIR COOLER LEAKAGE Pursuant to 10 CFR 50.55a(g) a relief request from certain prov1s1ons of Section XI of ASME B&PV Code is being submitted for NRC review and approval.
10 CFR 50.55a(g)(4) states that components which are classified as ASME Code Class 1, Class 2 and Class 3 shall meet the requirements of Section XI of the Code, to the extent practical within the limitations of design, geometry and materials of construction of the components.
10 CFR 50.55a(g)(5 & 6) explain that if the licensee does determine that conformance with a certain code requirements is impractical the Commission may grant relief. The Palisades containment air cooler cooling coil header to tube connections are brazed and are in a nearly inaccessible configuration. Attempts at repair of some of the connections by rebrazing has resulted in adjacent tube to header connections becoming heat affected and creating new leak locations on previously non-leaking connections.
In this regard it has been determined that, due to the design, geometry and materials of construction of the Palisades containment air coolers cooling coils, the ability to maintain no through wall leakage as required by ASME B&PV code Table IWD-2500-1, is impractical.
A discussion of the requested relief and the basis for the request are presented in Attachment 1 to this letter. This request has been reviewed and approved by plant management and the Plant Review Committee and will be incorporated into the Palisades Nuclear Plant 40-year Master Inservice Inspection Plan upon approval by the NRC, pursuant to Palisades Technical Specification 4.3.e. A single copy of the references has been sent to the NRCs Project Manager for the Palisades Plant.
&A~
Gerald B Slade General Manager CC Administrator Region III, USNRC NRC Resident Inspector, Palisades Attachment 9101?900~A 910116
~b~*-~n6~~ 05000255 P
~oO(
/1,\\ I
ATTACHMENT Consumers Power Company Palisades Plant Docket 50-255 PROPOSED REQUEST FOR RELIEF FROM THE PROVISIONS OF ASME B&PV CODE SECTION XI -
CONTAINMENT AIR COOLER LEAKAGE Pursuant to 10 CFR 50.55a(g)
January 16, 1991 6 Pages
1 HISTORICAL PERSPECTIVE.
In June of 1986, containment air coolers VHX-1 & 2 were found to have minor leakage.
As a result of this discovery a special repair process was qualified (June through August 1986) to repair the cooler tubes. Qualification of this repair process proved very difficult since, due to joint configuration, the code required original joint strength could not be achieved.
An air pressure drop test was also developed (August 1986), with acceptance criteria designed to accept a minor amount of coil leakage due to the difficulties associated with assuring zero leakage due to coil design configuration and materials.
The leaks on these two coolers were then repaired in August and September of 1986.
New leaks were discovered on all containment air coolers in October of 1986.
These leaks were repaired in October and November of 1986. A section of one of the coils from VHX-4 was removed at this time for evaluation and destructive examination.
The results showed that the overall poor workmanship of the coils was the primary cause of the joint leakage and is reported in the referenced letter "Containment Air Cooler Repair Report" dated February 17, 1987.
In December of 1986 additi~nal leaks were repaired on VHX-4.
During the 1988 refueling outage a number of leaks on VHX-4 were repaired. It is estimated that this repair effort required approximately 625 man-hours due to the fact that when a braze repair of the tubes was attempted, the heat applied to the repair area would affect adjacent tube connections and create new leak locations.
During the 1990 refueling outage the coils on VHX-4 were replaced with a modified set of coils designed to alleviate, as much as possible, the cause of coil leakage.
We will be monitoring this new coil configuration to see if it alleviates the problems experienced with coil leakage and repairs, and given satisfactory experience we intend to proceed with coil replacement for the other coolers during future outages.
Also, during the 1990 refueling outage, leaks on VHX-1 were identified and repairs attempted. After several repair attempts, the leaks on the cooler piping greater than one inch were successfully repaired.
The leaks identified on the 5/8 inch tube to header connections could not be totally repaired.
The 5/8 inch tube to header connections are brazed connections in a nearly inaccessible location. Attempts at brazing repair have frequently led to adjacent non-leaking connections being affected by the heat applied in brazing resulting in additional leaks. All leaks were repaired until the air pressure drop test could be successfully passed per the pre-established acceptance criteria.
BASIS STATEMENT The Palisades plant containment air coolers (VHX 1-4) are air handling and cooling units located entirely in the containment building. Plant service water from the critical service water header is circulated through the units cooling coils. The units are designed to control containment temperature during normal operations and condense steam during certain accident scenarios to help limit peak containment pressure. The coolers are classified as safety class III per Regulatory Guide 1.26. The ASME Boiler and Pressure Vessel Code (B&PV),Section XI, Table IWD-2500-1 Examination Category D-B, Item No. D2.10, and IWA-5250 requires a Class III system to be examined and to exhibit zero
ieakage during post-repair hydrostatic testing.
Presently, containment air cooler VHX-1 does not meet this requirement and due to the coil design, configuration and materials, this requirement is considered impractical for the Palisades containment air coolers.
2 Each cooler consists of eight sets of coils piped to manifolds for supply and return connections to the critical service water system.
Some of the coils' header to tube connections have exhibited leakage and attempts have been made to repair these leaks.
While some of the attempts have been successful, limitations of the cooler design, geometry, and materials of the construction of the tube to header, connection make achievement of a complete zero leakage repair of the coils impractical.
10 CFR 50.55a(g}(4) states that components which are classified as ASME Code Class 1, Class 2 and Class 3 shall meet the requirements of Section XI of the Code, to the extent practical within the limitations of design, geometry and materials of construction of the components.
10 CFR 50.55a(g)(5 & 6) goes on to explain what the Licensee does once it has determined that conformance with a certain code requirement is impractical and how the commission may grant relief. The 5/8 inch cooler tube to header connections are the brazed connections in a nearly inaccessible location where attempts at a brazing repair have frequently lead to adjacent non-leaking connections being affected by the heat applied in brazing and subsequently developing leaks.
Any connection greater than one inch is more external to the coil itself and experience has shown that repairs can be successfully completed on these pipes without heat affecting any adjacent parts.
In addition to the design limitations, adequate lead time does not exist to redesign, fabricate and procure new cooler coils and install them during the present refueling outage.
We have completed an analysis, and safety review which show how much leakage can be tolerated from each coil and cooler, and have established a program to periodically inspect the coolers in order to assure compliance with these leakage limits.
As described in FSAR Section 6.3.2.1, each cooler has a sump with a drain, a liquid level switch and an overflow valve.
Normally, very little water will be condensed from the air and the small amount of condensation will easily flow out through the drain.
If a cooling coil leak or steam leak occurs to cause a flow through the drain greater than 20 gpm, the level in the sump will rise to the liquid level switch and initiate an alarm in the control room.
RELIEF REQUESTED It is requested that relief be granted from the zero leakage requirement during pressure test as specified in ASME Boiler and Pressure Vessel (B&PV)
Code,Section XI, Table IWD-2500-1 Examination Category D-B, Item No. 02.10, and IWA-5250 as clarified by Inquiry Number (IN)89-017, for the 5/8 inch tubing sections of the containment air coolers.
As an alternative to maintaining zero leakage, Palisades will or has performed the following actions:
All cooler leaks on piping greater than one inch shall be repaired and tested during refueling shutdowns, in accordance with Section XI, 1983S83 requirements.
All leaks on cooler piping one inch or less shall be reduced to the lowest possible level within the requirements of the safety evaluation.
Further minimization of 5/8 inch coil leakage will be pursued by investigating other cold type repair techniques (epoxy, liquid steel).
3 A periodic inspection for leakage by visual observation shall be performed on a refueling outage basis in accordance with the Palisades Preventative Maintenance Program. Additionally, the ASME Section XI required pressure tests at each period and interval shall be completed per the Palisades Inservice Inspection Pressure Test Program.
For coolers discovered to be leaking, an air pressure drop test shall be performed during refueling shutdowns to quantify leakage.
The maximum Leakage allowed by the air pressure drop test shall be less 1/2 gpm per coil (4 gpm per cooler).
An actuation of the air coolers sump float switch requires Operations to check the cooler for coil leakage.
Should any cooler become inoperable due to leakage the Limiting Conditions for Operation (LCO) and action statements of Technical Specification 3.4, "Containment Cooling",
would apply. This LCO allows one cooler to be out of service for up to 7 days before placing the reactor in hot shutdown.
The replacement of existing cooler coils utilizing a modified tube to header joint configuration appears to be the best long term solution.
Failure studies were performed on containment air cooler coils in 1986 and 1987.
Recommendations from these studies led to design engineering and modification of available spare cooling coils. These modified coils were installed in containment atr cooler VHX-4 during the present 1990 refueling outage.
Palisades will monitor the operation of these coils, and given satisfactory experience with the modified coils, we intend to continue modifying and replacing coils in future outages for the remaining containment air coolers (VHX-1,2&3).
Until replacement coils are available, the current repair and testing methods (brazing, hydro test, air pressure test), provide appropriate leakage control.
The coolers have been verified as being capable of performing their safety function with a minimal amount of leakage (1/2 gpm per coil - 4 gpm per cooler) without adversely affecting the outcome of any analyzed event or accident. This verification has been documented in the 10 CFR 50.59 safety evaluations for Palisades deviation report D-PAL-86-218 and permanent maintenance procedure SWS-M-6. This verification was repeated in the safety evaluation for this relief request.
This safety evaluation shows that the minimal amount of leakage from the containment air coolers has been determined to not be an unreviewed safety questions as follows:
- 1.
The leakage does not increase the probability of an accident previously evaluated in the FSAR.
. Loss of service water pressure boundary (ie leakage) is not the initiating event for any of the previously evaluated accidents discussed in FSAR Chapter 14.
Therefore, analyzed accident probabilities are not increased.
- 2.
The leakage does not increase the consequences of an accident previously evaluated in the FSAR.
Permanent Maintenance Procedure SWS-M-6 sets the maximum allowable leakage from any one coil to be 1/2 gpm.
This equates to a total maximum allowable leakage from all coils of 16 gpm.
This maximum
allowed leak rate is significantly less than the existing leakage alarm setpoints of 20 gpm per cooler and 300 gpm for the containment service water system.
Furthermore, previous safety evaluations (D-PAL-86-218) have determined that an additional containment accident water volume of 50,000 gallons is required before flooding becomes a concern, and 100,000 gallons is required before dilution of Boron becomes a concern.
At the maximum allowable cooler leak rate (16 gpm total), 2.2 days and 4.4 days are required to reach the respective limits. This allows for ample time to deal with such a situation.
4 Permitting leakage from the Service Water pressure boundary in containment raises the question of accident leakage from the containment to service water and hence to the environment. This issue has been repeatedly evaluated in the past, most recently in.PRC meeting 88-081 on Nov 17, 1988.
In that meeting, PRC concluded that some leakage was acceptable and that leakage should not be included in ILRT/LLRT totals for the following reasons:
a)
The path from containment to service water and to the environment is torturous.
b) 10 CFR 50 Appendix J, III A.1.6 states that "Systems normally filled with water and operating under post-accident condition, such as the containment heat removal system, need not be vented,"
during ILRT testing.
c)
The Service Water System outlet piping is a monitored pathway.
- 3.
The leakage does not increase the probability of malfunctions of equipment important to safety.
Operation with minor leakage at brazed joints may accelerate loss of braze material at the affected joints; however, due to the relatively stiff design of the coils the leaks would be self limiting and would not increase the probability of catastrophic cooler failure.
- 4.
The leakage does not increase the consequences of a malfunction of equipment important to safety.
Implementation of this relief request will have no effect on the consequences of air cooler malfunction. That is, failure of the cooler after operating with leakage will be the same as if the cooler operated leak-free.
The primary consequence would be loss of heat removal capability.
Loss of heat removal capability can be mitigated by use of containment spray system. Therefore the consequences of equipment malfunction are not altered.
- 5.
The leakage does not create an accident of different type than any previously evaluated in the FSAR.
Operation with the code relief requested will not introduce any new failure modes and hence no new accident types. therefore the possibility of a new accident is not created.
- 6.
The leakage does not create the possibility of a malfunction of a different type than any previously evaluated in the FSAR.
Operation with the Code relief requested will not introduce any new failure modes and hence no new malfunction types. Therefore the possibility of a new malfunction is not created.
- 7.
The leakage does not reduce the margin of safety as defined by the plant Licensing Basis.
REMARKS Cooler leakage of less than 20 gpm, the alarm setpoint (FSAR Section 6.3.2.1), essentially defines the margin of safety. Allowing operation with cooler leakage below this limit (4 gpm per cooler);
therefore, does not reduce the margin of safety (ie we operate within the margin of safety).
This request for relief applies to the containment air coolers VHX 1-4.
REFERENCES ASME B&PV Code Inquiry Number IN89-017, "Section XI, 1983 Edition; IWA-1400, IWX-3000, IWA-6000 and IWA-7000, through wall leakage - Repair and Replacement Requirements". This inquiry asked for code clarification on repair of through wall leakage.
The Code Committee indicated that it was the intent of the Code that through wall leakage be repaired.
ASME B&PV Code,Section XI, Table IWD-2500-1, "Test and Examination Categories" and IWA-5250.
This code table outlines the test and examination requirements for the different examination categories.
Palisades is requesting relief from the "No leakage" Acceptance Standard of Examination Category D-B, Item No. 02.10.
Palisades Periodic Activities Control Sheet X-SYENG046.
This is periodic activity that initiates the periodic inspection of the Containment Air Coolers for leakage.
5 Palisades FSAR 6.3, "Containment Air Coolers". This FSAR section describes the function of the containment air coolers and their sump level switch which actuates to an alarm in the control room if there is a cooling coil tube is leaking or steam is condensing at a rate greater than 20 gpm.
Technical Specification 3.4, "Containment Cooling". This section outlines the Limiting Conditions of Operation (LCO) and Actinn Statements for containmen~ cooling systems.
The containment air coolers are included within its scope.
Safety evaluation D-PAL-86-218F.
This evaluation documents that containment air cooler leakage has no significant affect on reactor safety when containment leakage and flooding are considered.
Safety evaluation for relief request, PS&L Log No 91-0096. This evaluation documents that containment air cooler leakage within the limits of the FSAR does not significantly affect plant or public safety.
Plant Review Committee Meeting No 88-081.
These meeting minutes document the review of containment air cooler leakage by the Plant Review Committee.
In that meeting, PRC concluded that some leakage was acceptable and that leakage should not be included in Integrated Leak Rate
~...
Testing (ILRT)/Local Leak Rate Testing (LLRT) totals for the following reasons: 1) The path from containment to service water and to the environment is torturous 2) 10 CFR 50 Appendix J, III A.1.6 states that "systems normally filled with water and operating under post-accident conditions such as the containment heat removal system, need not be vented", during ILRT Testing. 3) the service water outlet piping is a monitored pathway.
Letter PDFlenner to DDCrabtree, Containment Air Cooler Repair Report, February 17, 1987 (FLNR 34-87). This letter describes the results of the investigation by Consumers Power Company and its contractors on the condition of the containment air coolers and gives recommendations for future activities.
6