Forwards SALP Input & Safety Evaluation of Revised Offsite Dose Calculation Manual (Odcm), & Rev 1 to Process Control Program (Pcp).Odcm & PCP Acceptable Refs for Use W/ Tech Specs for Assuring Compliance w/10CFR20 & 50
ML18052A821
Person / Time
Site: Palisades 
Issue date: 12/30/1986
From: Thadani A
Office of Nuclear Reactor Regulation
To: Berry K
CONSUMERS ENERGY CO. (FORMERLY CONSUMERS POWER CO.)
Shared Package
ML18052A822 List:
References
NUDOCS 8701090322
Download: ML18052A821 (3)


Text

  • --

Docket No. 50-255 Mr. Kenneth W. Berry Director, Nuclear Licensing Consumers Power Company 1945 West.Parnall Road Jackson, Michigan 49201

Dear Mr. Berry:

December 30, 1986 *

SUBJECT:

PALISADES PLANT - ACCEPTANCE OF THE REVISED ODCM (DATED AUGUST 29, 1985) AND PCP (REV. 1) DOCUMENTS By submittal dated August 29, 1985 of the Palisades Semiannual Radioactive Effluent Release and Waste Disposal Report for January through June 1985, Consumers Power Company provided Revision 1 of the Process Control Program (PCP) and a revised Offsite Dose Calculation Manual (ODCM) (dated August 29, 1985) in accordance with Technical Specifications 6.18 and 6.19.. These are the latest reported revisions of these documents.

The original PCP and ODCM authorized for use were essentially draft documents.

We have reviewed this revised Palisades ODCM and find that lt generally uses documented and approved methods consistent with the guidelines of NUREG-0133.

However, you have not provided a methodology in the ODCM for estimating the release of specific radionuclides in gaseous effluents from the steam generator blowdown vent system which exhau~ts directly to the atmosphere and is not released through the plant stack.

Therefore, we find that the revised ODCM is an acceptable reference with the exception that you should revise the ODCM in the near future to correct this above deficiency.

We have also reviewed the revised PCP (Rev. 1) and find that it is generally consistent with current NRC criteria and, the~efore, is acceptable for use with the Technical Specifications.

However, several deficiencies were noted which should be corrected in a future revision of the PCP.

In addition, it should be noted that the acceptability of the revised PCP is based on currently available NRC guidance that does not fully incorporate consideration of the requirements of 10 CFR Part 61 which became effective in 1983.

A future revision of the PCP should provide fully detailed information on assuring compl1ance with the requirements of 10 CFR 20.311 regarding classification of waste according to 10 CFR 61.56 and waste characteristics requirements of 10 CFR 61.55.

NRC guidance on the above is scheduled for issuance by early 1988.

---rr-1*

l--~61230 '.

  • 1

(

970109030%~ 05000255 \\

pDR AD pDR

...i

.\\

p

Mr. Kenneth Our findings are documented in the enclosed Safety Evaluation (SE).

Included as part of the SE is our contractor's Technical Evaluation Report.

Please inform us of your intentions with regard to the noted deficiencies.

Enclosures:

1.

Safety Evaluation Report

2.

Technical Evaluation Report cc w/enclosures:

See next page Sincerely,

/s/

Ashok C. Thadani, Director PWR Project Directorate #8 Division of PWR Licensing-B DISTRIBUTION Docket File NRC PDR L PDR PBD-8 Rdg FMiraglia OGC-Bethesda EJordan ACRS-10 BGrimes JPartlow TWambach PKreutzer Gray File NThompson CNichols PBD#8 p~~r ir.4;?86*

PBD#8 ;f 11 If(

TWambach;cf 12~'[/86 M

PBD#8

  • AThadani 120f086

Mr. Kenneth W. Berry Consumers Power Company cc:

M. I. Miller, Esquire Isham, Lincoln & Beale 51st Floor

.Three First National Plaza Chicago, Illinois 60602 Mr. Thomas A. McNish, Secretary Consumers Power Company 212 West Michiaan Avenue Jackson, Michigan 49201 Judd L. Bacon, Esquire Consumers Power Company 212 West Michigan Avenue Jackson, Michigan 49201 Regional Administrator, Region III U.S. Nuclear Regulatory Commission 799 Roosevelt Road Glen Ellyn, Illinois 60137 Jerry Sarno Township Supervisor Covert Township 36197 M-140 Highway Covert, Michigan 49043 Office of the Governor Room 1 - Capitol* Building Lansing, Michigan 48913 Palisades Plant ATTN:

Mr. Joseph F. Firlit Plant General Manager 27780 Blue Star Memorial Hwy~

Covert, Michigan 49043 Resident Inspector c/o U.S. NRC Pa 1 i sades Pl ant

  • 27782 Blue Star Memorial Hwy.

Covert-, -Mkh-igan -49043 Palisades Plant Nuclear Facilities and Environmental Monitorino Section Office

~

Division of Radiological Health P.O. Box 30035 Lansing, Michigan 48909