Forwards Revised Summary of Offsite Power Events,Correcting Info Provided to NRC at 860108 Meeting.Addl Events Occurred on 720517 & 741017
ML18052A381
Person / Time
Site: Palisades Entergy icon.png
Issue date: 04/10/1986
From: Kuemin J
CONSUMERS ENERGY CO. (FORMERLY CONSUMERS POWER CO.)
To:
Office of Nuclear Reactor Regulation
References
NUDOCS 8604140306
Download: ML18052A381 (3)


Text

consumers Power POW ERi Nii MICHlliAN'S l'RDliRESS General Offices: 1945 West Parnall Road, Jackson, Ml 49201 * (517) 788-0550 April 10, 1986

Director, Nuclear Reactor Regulation US Nuclear Regulatory Commission Washington, DC 20555 DOCKET 50-255 - LICENSE DPR PALISADES PLANT -

LOSS OF OFFSITE POWER EVENTS - CORRECTION OF PREVIOUSLY PROVIDED INFORMATION Consumers Power Company and the NRC met on January 8, 1986 to discuss the reliability of the Palisades Auxiliary Feedwater System.

The discussions included a summary of loss of offsite power events.

A January 31, 1980 Consumers Power Company letter was used as the basis for the summary of loss of offsite power events which stated that Palisades had a total of five such events.

Four events are noted in the January 31, 1980 letter and one event occurred on January 1, 1984.

A recent review of plant files has shown that there have been two additional loss of offsite power events to those provided in the summary given on January 8, 1986, and in the January 31, 1980 letter.

The two events occurred on May 17, 1972 and October 17, 1974 and each was initiated by overly sensitive differential relaying.

These events were reported to the NRC in letters dated May 26, 1972 and N6vember 15, 1974.

Our January 31, 1980 letter states that no loss of offsite power occurred on October 17, 1984, but that the unit was shutdown for AEC Operator's examinations.

This is incorrect.

The unit was shutdown as stated however the loss of offsite power did occur later that same day.

An additional error, in the previous information provided, is that the recovery time for the November 25, 1977 event was reported, in the January 31, 1980 letter, to be 3 hours3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> and 30 minutes.

Both the log books and the LER reoo4T4o3oo-aolJ4TO 1

I PDR. ADOCK 050002551 *1 S

PDR

..I OC0486-0067-NL04

Director, Nuclear Reactor Regulation Palisades Plant Loss of Offsite Power Events April 10, 1986 associated with this event, dated December 16, 1977 show the recovery time to be 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> and 16 minutes.

Attached is a revised summary of loss of offsite power events.

/~

e-:uemin.

Staff Licensing Engineer CC Administrator, Region HI, USNRC NRC Resident Inspector - Palisades Attachment OC0486-0067-NL04 2

    • .:. t..

PALISADES TOTAL LOSS OF OFFSITE POWER

SUMMARY

There have been seven total loss of offsite power events at Palisades.

One event was purposely initiated so that switchyard breaker maintenance could be performed.

The three events that occurred in late 1977 were suspected to be caused by seepage of water into a sudden pressure auxiliary relay or one of the startup transformers.

Since that time, the relay and conduit into the control cabinet were replaced.

Also, separate lockout relays for each transfer trip system were added so that a single mistrip would not result in the loss of the "R" bus.

There has been no reoccurrence of this type of event since the above modifications.

The two events which occurred in 1972 and in 1974 were also initiated by a single cause; in this case, differential relaying which was overly sensitive.

Even though the intentional event in early. 1984 resulted in a loss of onsite AC power, there was never an.increased threat to public health or safety because there was no fuel in the reactor.

If there had been any reason to suspect a safety hazard, the maintenance that resulted in the event would not have been started.

The average time that it took to regain offsite power was three hours and three minutes.

The maximum time the plant was without offsite power is eight hours and twenty-two minutes.

TABLE 3 Palisades Total Loss of Offsite Power Events Event No Date Time Power Was Off (hr:min) 1 09/02/71 0:56 2

05/26/72 8:22 3

11/17/74 0:30 4

09/24/77 4:45 5

11/25/77 2:16 6

12/11/77 1:30

7.

Oi/08/84 3:23 A description of the 1984 event is attached.

MI0386-0009A-NL01-NL04