ML18051B264

From kanterella
Jump to navigation Jump to search
Proposed Tech Specs Providing Clarification & Additions to Existing Tech Specs 3.22 & 4.17 Due to Fire Protection Mod Projects
ML18051B264
Person / Time
Site: Palisades Entergy icon.png
Issue date: 02/05/1985
From:
CONSUMERS ENERGY CO. (FORMERLY CONSUMERS POWER CO.)
To:
Shared Package
ML18051B262 List:
References
NUDOCS 8502120202
Download: ML18051B264 (8)


Text

PROPOSED PAGES PROPOSED TECHNICAL SPECIFICATION CHANGE REQUEST INSPECTION AND TESTING OF FIRE PROTECTION DEVICES AND ASSEMBLIES CONSUMERS POWER COMPANY Palisades Plant 255 0502120202 050205 I

PDR ADOCK 05000255 I

--_ e c_

-- ___ --.- _ F!P~L _;.

I TSC-FIREPROTECTION-85-01 7 Pages

3.22 FIRE PROTECTION SYSTEM 3.22.1 FIRE DETECTION INSTRUMENTATION LIMITING CONDITIONS FOR OPERATION 3.22.1.1 The minimum fire detection instrumentation for each fire detection zone shown in Table 3.22.1 shall be OPERABLE.

APPLICABILITY:

ACTION:

At all times when equipment in that fire detection zone is required to be OPERABLE.

With the number of instruments OPERABLE less than required by Table 3.22.1.

1.

Except the detectors located inside containment, within one hour, establish a fire watch patrol to inspect the zone with the inoperable instrument(s) at least once per hour.

2.

Restore the inoperable instrument(s) to OPERABLE status within 14 days, or

3.

In lieu of any.other report required by Specification 6.9.2, prepare and submit a Special Report to the Commission with 30 days outlining the action taken, the cause of the inoperability and the plans for restoring the instrument(s) to OPERABLE status, and

4.

In*the event this Limiting Condition for Operation and/or associated Action requirements cannot be satisfied, provisions relating to operating restrictions on the plant are not applicable.

BASIS OPERABILITY of the fire detection instrumentation ensure that adequate warning capability is available for the prompt detection of fires.

This capability is required tin order to detect and locate fires in their early stages Prompt detection of fires will reduce the potential for damage to safety-related equipment and is an integral element in the overall facility fire protection program.

In the event that a portion of the fire detection instrumentation is inoperable, the establishment of frequent fire patrols in the affected areas is required to provide detection capability until the inoperable instrumentation is returned to service.

3-96 TS-SECTION 3.22-FIREPROTECTION

TABLE 3.22.1 fr NUMBER OF

'IYPE OF MINlMl.lM FIRE DETECTICN ZONE DETECTORS DEI'ECIURS INS'IRUMENIS OPERABLE

1.

Cable Spreading Roan and 1-C Switchgear Roan, Col M-28 1

Water Flow Sw 1

2.

Switchgear Roan ID, Col G-28 1

Water Flow Sw 1

3.

North Penetration Roan, Col G-22 1

Water Flow Sw 1

4.

Cableway Roan 328, Col G-22 1

Water Flow Sw 1

5.

Electrical F.quipment Roan, Col G-28 1

Water Flow Sw 1

6.

Cllarging funp Roan, Col E-28 1

Water Flow Sw 1

7.

Diesel Generator Roan 1-1, Col J-28 1

Water Flow Sw 1

8.

Diesel Generator Roan 1-2, Col M-28 1

Water Flow Sw 1

9.

Southwest Cable Penetration, Col H-10 1

Water Flow Sw 1

10.

Intake Structure 590', Col Y. 5-7 1

Water Flow Sw 1

11.

Control Roan and.RoWI 325 7

&ooke 5

LU I

12.

Control Room Adjacent Offices, Rocms 324 & 320 2

Stroke 1

\\0

---.:i

13.

Cable Spreading Roan (224) Area 8

Smoke 6

14.

Refueling and Spent F\\.tel Area, Rm 220 4

Snnke 2

15.

Switchgear Roan 1-D, Roan 223.

4

&ooke 3

16.

North Penetration, Roan 332 2

Snnke 1

17.

Switchgear Roan 1-C, Roan 116A 2

Smoke 1

18.

Southwest Cable Penetration, Rm 250 2

Sroke 1

19.

Engineered Safeguards Panel Area 3

&ooke 2

20.

Stairwell CAltside Engineered Safeguards Panel Area 1

Stroke 1

21.

Canponent Cooling funp Roan 123 2

Smoke 1

22.

Safeguard Area Roan 4 3

Snnke 2

23.

Safeguard Area Roan 5 2

&oolr..e 1

24.

Corridor 106 on 590' Elevation 6*

Stroke 4

25.

Charging funp Roan 104 2

Smoke 1

1S0584-0012.A-IM)l

TS0584-0012A-Il101

3.22 FIRE PROTECTION SYSTEM 3.22.3 FIRE SPRINKLER SYSTEM LIMITING CONDITIONS FOR OPERATION 3.22.3.1 The sprinkler system located in the following areas shall be OPERABLE:

a.

Cable Spreading Room/Switchgear Room lC

b.

Switchgear Room ID

c.

Diesel Generator Room 1-1

d.

Diesel Generator Room 1-2

e.

Southwest Cable Penetrating Room

f.

Cable Way Room 328

g.

Intake Structure Room 136 and 136A

h.

North Cable Penetration Room

i. Electrical Equipment Room
j.

Charging Pump Rooms 104, 104A, and 104B APPLICABILITY:

Whenever equipment in the sprinkler protected area is required to be operable.

ACTION:

1.

With one or more of the above required sprinkler systems inoperable, establish a continuous fire watch with backup fire suppression equipment in the unprotected area(s) within one hour.

Restore the system(s) to operable status within 14 days, or, in lieu of any other report required by Specification 6.9.2, prepare and submit a Special Report to the Commission within the next 30 days outlining the action taken, the cause of the inoperability and the plans and schedule for restoring the system to operable status.

2.

In the event this Limiting Condition for Operation and/or associated Action requirements cannot be satisfied, any provisions relating to the operating restrictions on the plant are not applicable.

Basis Refer to Basis Section 3.22.2.

3-98 TS-SECTION 3.22-FIREPROTECTION

3.22 FIRE PROTECTION SYSTEM 3.22.5 FIRE RATED AND FIRE PROTECTION ASSEMBLIES LIMITING CONDITIONS FOR OPERATION 3.22.5.1 All fire rated assemblies (walls, floors, ceilings, cable tray enclosed, cable wraps), fire protection assemblies (radiant heat shields) and sealing devices in fire rated assembly penetrations (fire doors, fire dampers, cable, piping, and ventilation duct penetration seals) which protect safety related fire areas or separate portions of redundant system important to safe shutdown within a fire area, shall be OPERABLE.

APPLICABILITY:

At all Times.

ACTION:

1.

With one or more of the above required fire rated assemblies or penetration sealing devices inoperable, a continuous fire watch shall be established on at least one side of the affected assembly within one hour, or verify the OPERABILITY of fire detectors on at least one side of the inoperable assembly and establish an hourly fire inspection.

2 With a fire protection assembly rendered inoperable, within on~ hour establish an hourly fire inspection in that area.

Basis The functional integrity of the fire rated assemblies, penetration sealing devices and fire protection assemblies ensures that fires will be confined or adequately retarded from spreading to adjacent portions of the facility.

These design features minimize the possibility of a single fire rapidly involving several areas of the facility prior to detection and extinguishment.

The fire rated assemblies, fire protectin assemblies and penetration sealing devices are passive elements in the facility fire protection program and are subject to periodic inspections.

Fire rated assemblies, fire protection assemblies and penetration sealing devices which are not in as-designed condition, an evaluation shall be performed to show that the fire rating of the fire rated assembly, fire protection assembly or penetration sealing device has not been degraded.

3-102 TS-SECTION 3.22-FIREPROTECTION

4.17.

FIRE PROTECTION SYSTEM 4.17.4 FIRE HOSE STATIONS SURVEILLANCE REQUIREMENTS 4.17.4.1 4.17.4.2 Each fire hose station defined in Section 3.22.4.1 a through j shall be verified to be OPERABLE:

a. At least once per month by visual inspection of the station to assure all equipment is available.
b. At least once per 18 months by removing the hose for inspection and reracking and replacing all gaskets in the couplings as required.
c. At least once per 3 years by:
1)

Partially opening each hose station valve to verify valve operability and now flow blockage, and

2)

Conducting a hose hydrostatic test at a pressure of at least 50 psig greater than the maximum pressure availabe at that hose station.

Each fire hose station defined in Section 3.22.4.1 k & 1 shall verified to be operable:

a. At least once per month during normal refueling outage by visual inspection of the station to assure all equipment is available.
b. At least once per refueling outage by removing the hose for inspection and replacing all gaskets in the couplings as required.
c. At least once per 3 years by:
1)

Partially opening each hose station valve to verify valve operability and no flow blockage, and

2)

Conducting a hose hydrostatic test at a pressure at least 50 psig greater than the maximum pressure available at that hose station.

4-79 TS-SECTION 3.22-FIREPROTECTION

4.17.5 FIRE PROTECTION SYSTEM 4.17.5 FIRE RATED AND FIRE PROTECTION ASSEMBLIES LIMITING CONDITIONS FOR OPERATION 4.17.5.1 Fire rated assemblies, fire protection assemblies and penetration sealing devices (except fire doors per 4.17.5.2), shall be verified OPERABLE at least once per refueling outage by performing an inspection of:

a.

The exposed surfaces of each fire rated assembly (visual),

b.

the structural integrity of fire protection assemblies (visual),

c.

all penetration sealing devices (visual, and

d.

fire dampers and associated hardware (functional where practicable).

4.17.5.2 All fire doors shall be verified OPERABLE by visually inspecting the structural integrity, automatic hold-open, release, closing mechanism and latches at least once per six months, and by verifying:

a.

The OPERABILITY of the fire door supervision system for each electrically supervised fire door at least once per 31 days,

b.

that each locked closed fire door is closed at least once per seven days,

c.

that doors with automatic hold-open and release mechanisms are free of obstructions at least once per 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />,

d.

that each unlocked fire door without electrical supervision is closed at least once per 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />, and 4-80 TS-SECTION 3.22-FIREPROTECTION