Documents Agreement W/Util Commitments Re More Stringent Limit on Allowed primary-to-secondary Leakage for Duration of Cycle V & Proposals for Increased Surveillance & Training Re primary-to-secondary Leakage
ML18047A319
Person / Time
Site: Palisades 
Issue date: 05/07/1982
From: Crutchfield D
Office of Nuclear Reactor Regulation
To: Vandewalle D
CONSUMERS ENERGY CO. (FORMERLY CONSUMERS POWER CO.)
References
LSO5-82-05-011, LSO5-82-5-11, NUDOCS 8205140316
Download: ML18047A319 (2)


Text

May 7, 1982 DISTRIBUTION Docket NRC PDR Docket NO. 50-255 LS05-82-05-0l l Mr. David VandeWalle Nuclear Licensing Administrator Consumers Power Company 1945 West Parna11 Road Jackson, Michigan 49201

Dear Mr. VandeWalle:

Loe a 1 PDR ORB Reading NSIC DCrutchfield HSmith TWambach CCheng OELD OI&E ACRS SEPB

SUBJECT:

PALISADES PLANT -

STEAM GENERATOR TUBE INSPECTION The purpose of this letter is to document our agreement with the commitments you made in discussions with the NRC staff, as well as. those made in your letter of April 23, 1982. These discussions were conducted as a result of leaks discovered in two tubes in the 11.t\\

11 steam generator.

We have reviewed your summary of the results of inspections performed on 612 tubes in the A steam generator using the 540 SFW and 4x4 eddy current test probes.

You reported that no cracking had been discovered other than in the two previously identified leaking tubes (2-82-20 and 2-22-127).

Furthermore, no additional degradation was noted in the inspected tubes beyond that identified during the last eddy current tests in 1981. Based on these results, we agree that this cracking phenorne ~.does not appear to be widespread.

However, due to the limitations of the eddy current testing equipment, the staff agrees with you that a more stringent limit on allowed primary-to-secondary leakage for the duration of Cycle V is appropriate.

We also agree with your proposals regarding increased surveillance and training regarding primary-to-secondary leakage.

We have discussed this matter with the Resident Inspector at Palisades, and he concurs that your Standing Order No. 41, Rev. 0, dated April 22, 1982 which limits leakage to 0.1 gpm and.increases* sampling frequency in the event of a leak~ is sufficient and no modifications to your Technical Specifi-cations are necessary. She,ul d you have any further questions, pl ease contact us.

OFFICE* *****cc:*****see**n xt**page*********

SURNAME> ************************

DATE.************************

NRG FORM 318 (10-80) NRCM 0240 Sincerely, Original signed by Dennis M. Crutchfield, Chief Operating Reactors Branch #5 ivision o Licensin OFFICIAL RECORD COPY USGP0:1981-335-960

'1

~.-----. --

--:------._~*-*-***--.-.*-*-.. ***

Mr.~David J. VandeW~lle cc M. i. Miller, *Esquire Isham, Lincoln & Beale

    • suite 4200 One First National Plaza Chicago, Illinois S0670
  • Mr. Paul A. Perry, Secretary*

Consumers Power Company*

212 West Michigan Avenue Jackson, Michigan 49201 Judd L. Bae on,.Es qui re Consumers Power Company 212 West Michigan Avenue Jackson, Michigan 49201 CHERRY & FLYNN Suite 3700 Three First National Plaza

_Chicago, Illinois 60602

. Ms. Mary P. Sinclair Great Lakes Energy A 1 li ance

  • 5711 Summerset Drive
  • Midland, Michigan 48640 William J. Scanlon, Esquire 2034 Pauline Boulevard Ann Arbor, Michigan 48103 Township Supervisor Covert Townshi

. Route 1, Box 10 Van Bu.relfCounty, Michigan 49043 Office of* the Governor (2)-

. Room 1 - Capitol Building Lansing, Michigan 48913 Palisades Plant ATTN:

Mr.

Rob~rt Montross Plant Manager Covert, Michigan 49043 ~**.*.

May 7, *1982 U. S. Environmental Protection Agency Federal Activities Branch Region V Office ATTN:

Regional Radiation Repr~sentative 230 South Dearborn Street Chicago, Illinois 60604 Charles Bechhoefer, Es~.,.CHairman Atomic*s~fety and Licensing Board Panel * *

  • U. S. Nuclear Regulatory Commission Washington, D. C.

20555 Dr. George c. Anderson Department of Oceanogra~hy University of Washington Seattle, Washington 98195.

Dr. M. Stanley Livingston 1005 Calle Largo Santa Fe, New Mexico 87501 Resident Inspector c/o U. S. NRC Palisades Plant Route 2, P. o. Box 155 Covert, Michigan 49043 James G. Keppler, Regional Administrator Nuclear Regulatory Commission, Region III*

799 Roosevelt Road Glen Ellyn, Illinois 60137