ML18047A252

From kanterella
Jump to navigation Jump to search
Forwards High Water Level Study Palisades Plant,Lake Mi,Mi, for CPC, Concluding That Plant Design Will Be Adequate to Withstand Probable Max Surge Height of 11 Ft,Per SER Topics II-3.B,II-3.B.1 & II-3.C
ML18047A252
Person / Time
Site: Palisades Entergy icon.png
Issue date: 03/23/1982
From: Vincent R
CONSUMERS ENERGY CO. (FORMERLY CONSUMERS POWER CO.)
To: Crutchfield D
Office of Nuclear Reactor Regulation
Shared Package
ML18047A253 List:
References
TASK-02-03.B, TASK-02-03.B1, TASK-02-03.C, TASK-2-3.B, TASK-2-3.B1, TASK-2-3.C, TASK-RR NUDOCS 8203290267
Download: ML18047A252 (1)


Text

(J

.. J ~-"'

General Offices:

consumers Power company 1945 West Parnell Road, Jackson, Ml 49201 * (517) 788-0550 March 23, 1982 Dennis M Crutchfield, Chief Operation Reactor Branch No 5 Nuclear Reactor Regulation US Nuclear Regulatory Commission Washington, DC 20555 DOCKET 50-255 - LICENSE DPR PALISADES PLANT - SEP TOPICS II-3.B, II-3.B.l, II-3.C, HYDROLOGICAL CONSIDERATIONS On February 3, 1982, a meeting was held between the NRC, Consumers Power Company and our respective consultants to discuss site flooding at Palisades due to a surge from Lake Michigan.

During that meeting a draft report of a new study on site flooding was discussed as well as specific criticisms of previous work in this area.

Subsequently in a letter dated February 24, 1982, Consumers Power Company formally submitted comments on that previous work and discussed why we felt that a sufficient technical basis already existed to resolve this issue.

This letter concluded by stating that the final report of the new study would be submitted when published.

Attached is the final report of that study, entitled "High Water Level Study, Palisades Plant, Lake Michigan, Michigan" by R M Noble & Associates dated March 12, 1982.

This study concludes that the probable maximum surge from Lake Michigan at the Palisades site should be 4.8 feet.

When this is superimposed on the maximum mean monthly lake level of 583.6 feet (msl), a maximum stillwater elevation of 588.4'msl results.

Since the Palisades Plant design can currently withstand a surge height of over 11 feet above the maximum mean monthly lake level before flooding of the limiting component occurs (service water pump motors at 594.7 feet (msl)), it is concluded that the design is adequate, and, indeed, has a substantial margin of safety.

We trust that this new study now fully resolves this issue for Palisades.

We will be happy to discuss this report with you in detail, at your convenience.

Robert A Vincent Staff Licensing Engineer CC Administrator, Region III, USNRC NRC Resident Inspectqr_.--Palisades 82032A9D00-2C*~70~~g~~~5 PDR PDR p