: r:: -,.

ATTACHMENT 2 r-:rnoRANDUM FOR:

W. V.

Johnston~ Chief, Core Performance Branch, OSI FROM:

T. P. Speis, Chief, Reactor Systems ~ranch, OSI

SUBJECT:

PALISADES RELOAD REVIEW

REFERENCES:

1.

Letter from David P. Hoffman, Nuclear Licensing Administrator, Consumers.Power Company to Director, NRR, Palisades Plant - Technical Specifications Change Request Higher FrT for H-Fuel Cycle-4, dated May 14, 1980

2.

Exxon Nuclear Company, ECCS and Thermal-Hydraulic Analysis for the Palisades Reload H Design, XN-NF-80-18, April 1980 Consumers Power Company (CPC) has requested changes in their nuclear peaking factor for Cycle 4 (Ref. 1).

The changes and discussions are all physics questions and should be reviewed by CPB.

Reference 1 considers an ENC topical report (Ref. 2), which has two sections~

The first section is a partial ECCS re-analysis to account for type H fuel *.

The re-analysis involved only the hot channel and hot pin calculations for the limiting break~ It was not necessary to repeat the hydraulic analyses since the changes to type H fuel would not have a substantive hydraulic effect.

An axial shape sensitivity study was also performed.

RSB finds the ECCS results and methodology acceptable subject to review of the following items by CPB:

1.

Radial vs. axial peaking factor trade-off.

2. *Type H fuel parameters
3.

Acceptability of swelling and rupture model The second section of reference 2 is a thermal:-hydraulic analysis and should be reviewed by CPB.

cc:

Se~ next page Qvr~~

ruo~r7o7r5

-z/vp~~ p~~

Themis P. Speis, Chief Reactor Systems Branch Division of Systems Integration *

~ cc:

P. Check L. Rubenstein T. Wambach L. Lois D. Crutchfield CONTACT:

N. Lauben, X-27589