("*..*,_.

~tJ '

consumers Power company General Offices: 212 West Michigan Avenue,.Jackson, Michigan 49201

  • Area Code 517 788-0550 May 31, 1979 Mr James G Keppler Office of Inspection and Enforcement Region III IB Nuclear Regulatoey Commission 799 Roosevelt Road Glen Ellyn, IL* 60137 I'X)CKET 50-255 - LICENSE DPR PALISADES PL.ANT - SPECIAL NON-RADIOACTIVE ENVIRONMENTAL MONITOR-ING REPORT Attached is an NPDES Noncompliance Notification concerning Total Suspended Solids issued by Consumers Power Company on May 11, 1979. It is being sub-mitted to you in accordance with Technical Specification 6.9.3.1.D.

David P Hoffman (Signed)

David P Hoffinan Assistant Nuclear Licensing Administrator CC:

Director, Office of Nuclear Reactor Regulation Director, Office of Inspection and Enforcement C,oo~

s

,/,

7 906 os o'3b<6.

t

Flla Mo Pi6.2.l

___. e

"'ncident. No PAL 79-05-NC27 NPDES Noncornplience Notification Possibie Noncomplia.ace with ~aily Average/Ma.~imum Limitation May 11, 1979 Date Plant Palisades Permit No MI 0001457 Outfa.ll No 800213.

Outfall Description ireutrn.li zer Tank Wastes ( OOF)

Parameter Solids-Suspended Parameter No 00530

1. Date of Incident 5-7-79

_________.._ _____ ~

2. Identification of specific effluent limitation exceeded:

Exceeded daily maximum limitation of less than 100 mg/l for TSS.

3. Description of Incident:
4.
  • On 5-7-79 the neutralizer tank discharge measured 175 mg/l TSS.

Apparent Cause:

The higher TSS discharged resulted from an operating_ error whereby the concentration of TSS within the n.:utralizer tank was not checked prior to discharge*.

If not i:::mi.ediately corrected, the a.aticipated time the condition is ex:?ected to continue:

NA

6.

Corrective Action - the following corrective action was taken or will be taken to reduce, eliminate and prevent recurrence:

"Neutralizer tank effluent limitations and proper procedures for authorizing releases from the tank were discussed with the individuals involved.

7. Additional Co:n.'1lents:

~!A

8.

Siened:

R L Fobes

-/J ~ Ft,~/-v...d.,/

/),/.-

7 9 o a o s o.JI 01