ML18043A366
| ML18043A366 | |
| Person / Time | |
|---|---|
| Site: | Palisades |
| Issue date: | 12/28/1978 |
| From: | Hoffman D CONSUMERS ENERGY CO. (FORMERLY CONSUMERS POWER CO.) |
| To: | Ziemann D Office of Nuclear Reactor Regulation |
| Shared Package | |
| ML18043A367 | List: |
| References | |
| NUDOCS 7901020106 | |
| Download: ML18043A366 (3) | |
Text
..
consumers Power company General Offices: 212 West Michigan Avenue, Jacks~n. Michigan 49201
- Area Code 517 788-0550 December 28, 1978 Director, Nuclear Reactor Regulation Att:
Mr Dennis L Ziemann, Chief Operating Reactors Branch No 2 US Nuclear Regulatory Commission Washington, DC 20555
. DOCKET 50-255 - LICENSE DPR-20 PALISADES PLANT - SPECIAL NONRADIOACTIVE ENVIRONMENTAL MONITORING REPORT Attached is an NPDES Noncompliance Notification of a possible noncompliance with daily average effluent limitations for the Palisades Plant.
In accordance with Technical Specification 6~9.3.l.D, ten copies of this letter are enclosed.
~d P IJN.JmOJn David P Hoffman. * -f)O" 1..
Assistant Nuclear Licensing Administrator CC:
JGKeppler, USNRC REGULP,TORY OOC!-\\ET FILE. COPY
j *~.
. 1
. ~
}j *.
"j -
j 1
- l i
'I
- l 1
1 1
~
j I
1 1
General Offices: 212 West Michigan Avenue, Jackson, Michigan 49201
- Area Code 517 788-0550 December 11, 1978 Mr Robert J Courchaine Executive Secretary Michigan Water Resources Commission Stevens T Mason Bldg Lansing, MI 48926 INCIDENT NO:
PAL-78-ll-NC25 DEC 1 :2 1978.
NUCLEAR LICENSlt--1r*.
- This is in regard to NPDES Permit No MI 0001457 for the Company's Palisades Nuclear Plant.
In accordance with Part II, A4, "Noncompliance Notification,"
the attached "NPDES Noncompliance :Notifie;atiou," Incident No PAL-78-ll-NC25, is submitted as a report of a recent possible noncompliance*with the.daily average effluent limitations for this facility.
. If you have any questions regarding the attach~d report, please contact this office.
P C Hittle Director of Environmental Activities By 7~/J4(/7. /?,:l-'4ef-RLF /mlp CC MCLaracey, CP Co JGLewis,CP Co AJKempke, CP Co RBDeWitt, CP Co
~Cashell, CP Co CHurvey, MWRC
\\.1 7901020(0i
- -"\\*."*('*-*.. **.-:.. **.:-:...*,;*,,.....,.,
,*"*f*M*:'*****~......,_... _______.
)..:
File No Pl0.2.1
- I I-dent No PAL-78-11-Nc25*
NPDES Noncompliance. Notification Possible* Noncompliance with Daily Average/Ha..°'<im~ Limitation December 11, 197S Date Plant Palisades Permit No MI 0001457 OUtfall Description Neutralizer Tank Wastes (OOF)
Parameter Solids-Susnended outfall No 800213
_;;..~=:;:;.__ __
Parameter No 00530
- 1.
Date of Incident 11/30/78 2..
Iden.tification of specific effluent limitation exceeded:
Exceeded daily average limitation of less tha;n 30 mg/l for TSS during November 1978.
- 3.
Description of Incident:
- 4.
- 5.
Neutralizer tank releases for November 1978 (11 days) resulted in a daily average
.of 39.2 mg/l TSS.
Apparent Cause:
Apparent source of TSS is from internal corrosion of carbon-steel piping used in the air sparging system within the neutralizer tank.
The air sparging system is
- used to mix tank contents.
Seventy percent of the TSS present is in the form of metallic iron placed in solution by the acidic conditions periodically found in the tank.
If not immediately corrected, the anticipa~ed ti~e the condition is expected to
.continue:
NA
- 6.
Corrective Action - the following corrective action **ras taken or will be tal~en to reduce, eliminate and prevent recurrence:
The air sparging system will not be used until the carbon-steel piping can be
- replaced with PVC or some such corrosion resistant material.
- 7.
Additional Comments:
NA
.* *s.
7901020H3.