Forwards Amends 259 & 218 to Licenses DPR-52 & DPR-68, Respectively.Amends Change TS Completion Time for Required Action 3.8.1.B.4 from Existing 7 to 14 Days
ML18039A829
Person / Time
Site: Browns Ferry  
Issue date: 08/02/1999
From: Long W
NRC (Affiliation Not Assigned)
To: Scalise A
TENNESSEE VALLEY AUTHORITY
Shared Package
ML18039A830 List:
References
TAC-M98205, TAC-M98206, NUDOCS 9908060140
Download: ML18039A829 (6)


Text

Ivlr. A. J. Scalise g,"-hiIaf Nuclear Officer end Executive Vice President Tennessee Valley Authority

,6A Lookout Place

...r4101. Market Street August 2, 1999 Chattanooga, Tennessee 37402-2801

SUBJECT:

BROWN FERRY NUCLEAR PLANT, UNITS.2 AND3-ISSUANCE OF AMENDMENTSREGARDING AUTHORIZATIONOF 14-DAYALLOWABLE OUTAGE TIME FOR EMERGENCY'DIESEL GENERATORS (TAC NOS. M98205 AND M98206)

Dear Mr. Scalise:

The Commission has issued the enclosed Amendment Nos. 259 and 218 to Facility Operating License Nos. DPR-52, and DPR-68 for the Browns Ferry Nuclear Plant (BFN) Units 2, and 3, respectively.

These amendments are in response to your application dated March 12, 1997 as supplemented by letters dated March 30, 1999, April23, 1999, and June 18, 1999.

(Technical Specification Change TS-376.)

The amendments change the Technical Specification COMPLETION TIMEfor REQUIRED ACTION 3.8.1.B.4 for Units 2 and 3 from existing 7 days to 14 days. This permits an extension of the allowed outage time from 7 days to 14 days for an inoperable emergency diesel generator.

A copy of the related Safety Evaluation is also enclosed.

The Notice of Issuance willbe included in the Commission's biweekly Federal

~Re ister notice.

Docket Nos. 50-260 and 50-296 Sincerely, Original signed by:

William O. Long, Senior Project Manager, Section 2 Project Directorate II Division of Licensing Project Management Office of Nuclear Reactor Regulation

Enclosures:

1. Amendment No. 259 to License No. DPR-52
3. AmendmentNo.

218 to License No. DPR-68

4. Safety Evaluation

((

cc w/enclosures:

See next page DISTRIBUTION: See next page DOCUMENT NAME: 98205amd.wpd To receive e copy of this document, Indicate in the box:

C ss Copy without ettechment/enclosure "E

"N" ss No co Copy with ettachment/enclosure OFFICE NAME BCla on d~

WLon PM.'DLPM:P 2 C

LA:DLPM:PD2 E

BC:SPSB:DS RBarrett DE:EELB DThatch G

Rd~t q~~

DATE 7/4/99 7/(p /99 7/

/99 q"1'/

/99 07/r )99 OFFICE PDII-2tSC PDI -2i NAME DATE SPeterso 07 99 H erk 07//99'7/

/99 07/ /99 nc'A A%A

'ti'ti08060140 'ii90802 PDR ADQCK 05000260 P

PDR OFFICIALRECORD COPY Q/OL6~~~~~~i tnit~PF, tistt~4c eVO l~@O 0(

O ~gei0q

%/

o a

fi

~

~cP 4e>

re

~

nO le

+y r>

>~0,

+>>*+~

t UNITED STATES NUCLEAR REGULATORY COMMISSION WASHINGTON, D. C. 20555 August 2, 1999 Mr. A.,J. Scalice Chief Nuclear Officer and Executive Vice President Tennessee Valley Authority 6A Lookout Place 1101 Market Street Chattanooga, Tennessee 37402-2801 SUBJECT BROWN FERRY NUCLEAR PLANT, UNITS 2 AND3-ISSUANCE OF AMENDMENTSREGARDING AUTHORIZATIONOF 14-DAYALLOWABLE OUTAGE TIME FOR EMERGENCY DIESEL GENERATORS (TAC NOS. M98205 AND M98206)

Dear Mr. Scalice:

The Commission has issued the enclosed Amendment Nos.

259 and 218 to Facility Operating License Nos. DPR-52, and DPR-68 for the Browns Ferry Nuclear Plant (BFN) Units 2, and 3,.respectively.

These amendments are in response to your application dated March 12, 1997 as supplemented by letters dated March 30, 1999, April23, 1999, and June 18, 1999. (Technical Specification Change TS-376.)

The amendments change the Technical Specification COMPLETION TIMEfor REQUIRED ACTION 3.8.1.B.4 for Units 2 and 3 from existing 7 days to 14 days.

This permits an extension of the allowed outage time'from 7 days to 14 days for an inoperable emergency diesel generator.

A copy of the related Safety Evaluation is also enclosed.

The Notice. of Issuance willbe included in the Commission's biweekly Federal ~Re ister notice.

Sincerely, Docket Nos. 50-260 and 50-296 William O. Long, Senior Project Manager, Section 2 Project Directorate II Division of Licensing Project Management Office of Nuclear Reactor Regulation

Enclosures:

1. Amendment No.259 to License No. DPR-52
2. Amendment No. 218 to License No., DPR-68
3. Safety. Evaluation cc w/enclosures:

See next page

Il f,

P

~"

~i

~ Mr. J'. A. Scalice Tennessee Valley Authority BROWNS FERRY NUCLEAR PLANT Senior Vice President Nuclear Operations Tennessee Valley Authority 6A,Lookout Place 1101 Market Street Chattanooga, TN 37402-2801 Mr. Jack A. Bailey, Vice President Engineering &Technical Services Tennessee Valley Authority 6A Lookout Place 1101 Market Street Chattanooga, TN 37402-2801 Mr. Karl W. Singer, Site Vice President Browns Ferry Nuclear Plant Tennessee Valley Authority P.O. Box 2000 Decatur, AL 35609 General'Counsel Tennessee Valley Authority ET 10H 400 West Summit Hill Drive Knoxville, TN 37902 Mr. N. C. Kazanas, General Manager Nuclear Assurance Tennessee Valley Authority 5M Lookout Place 1101 Market Street Chattanooga, TN 37402-2801 Mr. Robert G. Jones, Plant Manager Browns Ferry Nuclear Plant Tennessee, Valley Authority P.O. Box 2000 Decatur, AL 35609 Mr. Mark J. Burzynski; Managar Nuclear Licensing Tennessee Valley Authority 4X Blue Ridge 1101 Market Street Chattanooga, TN 37402-2801 Mr. Timothy E. Abney, Manager Licensing and Industry Affairs Browns Ferry Nuclear Plant Tennessee Valley Authority P.O. Box 2000 Decatur, AL35609 Senior Resident Inspector U.S. Nuclear Regulatory Commission Browns Ferry Nuclear Plant I0833 Shaw Road Athens, AL35611 Mr. KirkE. Whatley Office of Radiation Control Alabama Dept. of Public Health 2001 Monroe Street, Suite 700 Montgomery, AL36104 Chairman Limestone County Commission 310 West Washington Street.