ACCELERATED DISTRIBUTION DEMONSTPWTION SYSTEM REGULATORY INFORMATION DISTRIBUTION SYSTEM'RIDS)
ACCESSION NBR:9403220250 DOC.DATE: 94/03/14 NOTARIZED: NO DOCKET FACIL:50-260 Browns Ferry Nuclear Power Station, Unit 2, Tennessee 05000260'UTH.
NAME AUTHOR AFFILIATION SALAS,P.
Tennessee Valley Authority RECIP.NAME RECIPIENT. AFFILIATION Document Control Branch (Document Control Desk)
SUBJECT:
Notifies NRC'f rev to ERDS data point library,per 10CFR50',
App E.Licensee revised alarm/trip setpoints for suppression pool temp.
DISTRIBUTION CODE: A026D COPIES RECEIVED:LTR ENCL SIZE:
TITLE: Emergency
Response
Data System (ERDS)
NOTES:
D RECIPIENT ID CODE/NAME AEOD/IRB
'01
'TRIMBLE,D COPIES LTTR ENCL 2
2 1
1 RECIPIENT ID CODE/NAME NRR/PD3-2 COPIES LTTR ENCL 1
1 A
D D
INTERNAL: ACRS AEOD/DOA/IRB OC/LFDCB RGN2 ERC EXTERNAL: NRC PDR' 1
AEOD 1
1
~NRR~S~S PEPB 1
0
~RE~QLEQ 1
1 RGN2 FILE 1
1 1
1 1
1 1
1 D
NOTE TO ALL"RIDS" RECIPIENTS:
D D
PLEASE HELP US TO REDUCE WAFEE! CONTACT THE DOCUMENT CONTROL DESK, ROOM Pl-37 (EXT. 20079) TO ELIMINATEYOUR NAME FROM DISTRIBUTION LISTS FOR DOCUMENTS YOU DON'T NEED!
TOTAL NUMBER OF COPIES'EQUIRED:
LTTR 13 ENCL 12
II
'J
Tennessee Vatfey Authority. Post Office Box 2000, Decatur, Alabama 35609 BAR
< 4 U.S. Nuclear Regulatory Commission ATTN:
Document Control Desk Washington, D.C.
20555 Gentlemen:
In the Matter Of
~
)
Tennessee Valley Authority
)
Docket No. 50-260 BROWNS FERRY NUCLEAR PLANT (BFN) - UNIT' REVISION TO EMERGENCY RESPONSE DATA SYSTEM (ERDS)
DATA,POINT LIBRARY In accordance with the requirements of '10 CFR 50, Appendix E, Part VI, paragraph 3a, TVA is notifying NRC of a revision to the BFN ERDS Data Point Library.
Specifically, on February 14,
- 1994, TVA revised the alarm/trip setpoints for the, suppression pool temperature (ERDS. point number 24).
The specific revisions are provided below.
ERDS POINT NUMBER 24 REVISIONS 1.
The "LO" alarm setpoint of 75'F is deleted.
2.
The "LOLO" alarm setpoint of 70'F is revised to 50'F.
REASON FOR THE REVISIONS The process computer originally had both "LO" and "LOLO" alarms to indicate abnormally low suppression pool temperatures to the plant operators.
TVA determined that the "LOLO" alarm setpoint was too high to be indicative of abnormal temperatures.
TVA also determined that the "LO" alarm does not provide meaningful information to plant operators.
Accordingly, TVA has deleted the "LO" alarm and revised the "LOLO" alarm to 50'F to more accurately represent abnormally low suppression pool temperatures.
5q'~
'tf403220250 940314 PDR ADOCK 050002b0 PDR 0gk f
0 4l
U.S. Nuclear Regulatory Commission Page 2
TVA's revised ERDS Data Point Library listing and ERDS Point Number 24, Suppression Pool Temperature, are contained in the Enclosure.
No new commitments are contained in this.submittal.
If you have any questions, please telephone me at (205) 729-2636.
Sincerel Salas Manager of Site Licensing Enclosure cc:
See page 3
U.S. Nuclear Regulatory Commission
-Page 3
NAR $ 4 199"-
Enclosure cc (Enclosure):
'r.
John R. Jolicoeur ERDS Project Manager U.S. Nuclear Regulatory Commission Mail Stop NMBB 3206 Washington, D.C.
20555 Mr., R. V. Crlenjak, Project Chief U. S. Nuclear Regulatory Commission Region II 101 Marietta Street, NW,.Suite 2900 Atlanta, Georgia 30323 NRC Resident Inspector Browns Ferry Nuclear Plant Route 12, Box 637
- Athens, Alabama 35611 Mr. D.
C. Trimble,. Project Manager U.S. Nuclear Regulatory Commission One White Flint, North 11555 Rockville Pike Rockville, Maryland 20852 Mr. J.
F. Williams, Project Manager U.S. Nuclear Regulatory Commission One White Flint, North 11555 Rockville Pike Rockville, Maryland 20852
4l
ENCLOSURE TENNESSEE'ALLEY'UTHORZTY BROWNS FERRY NUCLEAR PLANT (BFN)
UNIT 2 EMERGENCY RESPONSE DATA SYSTEM (ERDS)'ATA
'POINT LIBRARY ERDS POINT NUMBER 24 REVZSZON
'0
BROWNS FERRY UNIT 2 ERDS DATA POINT LIBRARY 1 ~
2 ~
3 ~
4 ~
5.
6.
7 ~
8 ~9.
10
'1.
12 ~
13.
14.
15.
16.
17.
18.
19.
20.
21 ~
22
'3.
24.
25.
26.
27
'8.
29.
30.
31.
32.
33.
34.
35.
36.
37.
38.
39.
NZ POWER RNG NZ INTER RNG NI SOURC RNG REAC VES LEV MAIN FD FLOW RCIC FLOW RCS PRESSURE HPCI FLOW LPCI FLOW LPCZ FLOW CR SPRAY FL CR SPRAY FL CND A/E RAD CND A/E RAD DW RAD DW RAD DW RAD MN STEAM RAD MN 'STEAM RAD MN STEAM RAD MN STEAM RAD DW PRESS DW TEMP SP TEMP SP LEVEL H2 CONC 02 CONC CST LEVEL
.WIND SPEED WIND SPEED WIND SPEED WIND DZR WIND DIR WIND DIR STAB CLASS STAB CLASS STAB CLASS EFF GAS RAD SPDS0001 CALC045 SPDS0041.
SPDS0007 CALC040 71-36 SPDS0008 73-33 74-50 74-64 75-21 75-49 SPDS0047 90-157 90-272C 90-273A 90-273C 90-136 90-137 90-138 90-139 SPDS0009 SPDS0010 SPDS0016 SPDS0013 SPDS0017 76-43 2-161 MET00191M MET00246M MET00310M MET00491M MET00546M MET00610M MET007 MET008 MET009 TYPEDATA SPDS0024 RX POWER APRM COMPOSED AVERAGE OF ZRM' RX POWER SRM - AVG RX WATER LEVEL - COMPOSED RFW FLOW TO REACTOR RCIC PUMP DISCHARGE FLOW RX PRESSURE - COMPOSED HPCZ Pump Discharge Flow RHR SYS I FLOW RHR SYS ZZ FLOW CORE SPRAY SYS I FLOW CORE SPRAY SYS ZZ FLOW OFFGAS POST TREATMENT AVG OFFGAS PRE TREATMENT AVG DW RAD-RX 582, 340 DEG AZIMUTH DW RAD-RX 560, 270 DEG AZIMUTH DW RAD-RX 582, 190 DEG AZIMUTH MAIN STM LINE A RAD LEVEL MAIN STM LINE C RAD LEVEL MAIN STM LINE B 'RAD LEVEL MAIN STM LINE D RAD LEVEL DRYWELL PRESSURE COMPOSED DRYWELL TEMPERATURE COMPOSED SUPPR PL WTR TEMP - COMPOSED SUPPR PL WTR LVL (ZN) COMPOSED DRYWELL H2 COMPOSED DRYWELL OXYGEN 'CONCENTRATION CST P3 (UNIT 2)
LEVEL VECTOR WIND SPEED (15 MZN AVG)
VECTOR WIND SPEED (15 MZN AVG)
VECTOR WIND SPEED (15 MIN AVG)
VECTOR WIND,DIR (15 MIN AVG)
VECTOR WIND DZR '(15 MIN AVG)
VECTOR WIND DIR (15 MIN AVG)
Stability Class Upper Stability Class Intermediate Stability Class Lower REAL/SIMULATED STACK RELEASE RATE - COMPOSED DENOTES'l.CHANGES'APE!'."CIRCE:<.:'T8EYXXST;-"SOBMIT~~
4l
ERDS point number 24.
SP TEMP SPDS0016 Suppression, Pool Temperature Date:
Reactor Unit:
Data feeder:
NRC ERDS Parameter:
Point ZDs Plant Spec Point Desc:
Generic/Cond Desc:
Analog/Digital:
Engr Units/Dig States:
Engr'nits Conversionc Minimum Instr Range:
Maximum Instr Range:
Zero Point
Reference:
Reference Point Notes:
PROC or SENS:
Number of Sensors:
How Processed:
Sensor Locations:
Alarm/Trip Set Points:
NID power cutoff level:
NID power cut-on level:
Instrument Failure Mode:
Temperature Compensation:
Level Reference Legs Unique 'System Desc:
03/16/94 BF2 1
SP TEMP SPDS0016 SUPPR PL WTR TEMP COMPOSED Suppression Pool Temperature A
DEGF.
N/A 30 230 N/A N/A P
16 Average (PSVA)
Around Circumference of Torus All modes:
HIHZ~95 HI=93 LOLO=50 N/A N/A N/A N
N/A There are 4
inputs actually scanned by the computer.
'Two of these 4
are made of 8
individual sensors that are hardware averaged.
The other 2 are selected individual sensors from
,the total 16. sensors.
Ol,