ML18029A511
| ML18029A511 | |
| Person / Time | |
|---|---|
| Site: | Browns Ferry |
| Issue date: | 04/22/1985 |
| From: | Office of Nuclear Reactor Regulation |
| To: | |
| Shared Package | |
| ML18029A512 | List: |
| References | |
| DPR-33-A-116, DPR-52-A-111, DPR-68-A-086 NUDOCS 8505060129 | |
| Download: ML18029A511 (32) | |
Text
ATTACHMENT TO LICENSE AMENDMENT NO. 116 FACILITY OPEPATING LICENSE NO.
DPR-33 DOCKET NO. 50-259 Revise Appendix A as follows:
1.
Remove the following pages and replace with identically numbered pages.
57, 58, 59, 60, 61, 86, 88, 109 2.
The marginal lines on these pages denote the area being changed.
85050bol29 850422 PDR ADOCK 05000259 P
TABLE 3.2.A PRIMARY CONTAINMENT AND REACTOR BUILDING ISOLATION INSTRUMENTATION Minimum No.
of Instrument Channels Operable er Tri S stem
- 1) ll)
Function
'eactor Building Isolation Timer (refueling floor)
Tri Level Settin 0 6 t ~ 2 secs Action HorF Remarks 1.Below trip setting prevents spurious trips and system per-turbations from init-.
iating isolation Reactor Building Isolation Timer (reactor zone) 05 t~ 2 secs GorA or H 1.Below trip setting prevents spurious trips and system per-turbations from init-iating isolation 2 (10)
Group 1 (Initiating) Logic N/A 1.Refer to Table 3.7.A for list of valves.
Group 1 (Actuation)
Logic N/A 1 Refer to Table 3
7 A for list of valves
'Minimum Ão.
. Instrument Channels Operable TABX,E 3.2.A PRIHARY COHTAIHHENT AHD REACTOR BUILDING ISOLATION IHSTRUNENTATION ve Se ct on 1
2 Croup 2 (Initiatin ) Logic H/h h or (B and E) 1.
Refer to Table 3 T.h for list of valves.
Croup 2
(RHR Isolation-Actuation) Logic
- Croup 8 (Tip-Actuation)
Logic Group 2 (Dryvell Suap Drains-Actuation)
..otic H/A Group 2 (Reactor Building H/h 6 Refueling Floor; and Dry-vell Vent and Purge-hctuation) Itic t and G
1.
Part of Group 6 Logic.
Croup 3 (Initiating) Logic H/A Croup 3 (Actuation) Logic H/h C
Refer to Table 3 7.A for list of valves.
Group 6 Logic H/h t and G
'I.
Refer to Table 3 7.A for list of valves.
Group 8 (Initiating) Logic H/A Reactor Building Isolation H/A (refueling floor) Logic Reactor Building Isolation H/A (reactor zone)
Logic Nor F Nor G or A Refer to Table 3 7.A for list of valves.
2.
Saae as Group 2 initiating logic'.
Inst.rurent Channels Cperable 1L TABLE y 2 h PRINARY CONTAINNEÃF AN9 REACTOR aUILDING ISOLATION INSTRUNCHTATIOI4 v
1 t
Reaar ks
>(7) (8)
SOTS Train A Logic 1(7) (8)
SGTS Train 8 Logic 7(7) (8)
SGTS Train C Logic N/A N/A L or (I and 1)
L or (I and P)
L or (I and t)
Refer to Table 3.2.B for QCIC and RPCI functions including Groupt
~ ~ S, and 2 valves
NOTES FOR TABLE 3.2.A
- 1. Whenever the respective functions are required to be operable there shall be two operable or tr1pped trip systems for each function.
If the first column cannot be met for one of the trip systems, that trip system or logic for that function shall be tripped (or the ap-propriate action listed below shall be taken).
If the column cannot be met for all trip systems, the appropriate action listed below shall be taken.
A.
Initiate an orderly shutdown and have the reactor in Cold Shutdown in 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.
B.
Initiate an orderly load reduction and have Main Steam Lines isolated within eight hours.
C.
Isolate Reactor Water Cleanup System.
D.
Isolate Shutdown Cooling.
E.
Initiate primary containment isolat1on within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.
F.
The handling of spent fuel will be prohibited and all operat1ons over spent fuels and open reactor wells shall be prohibited.
G.
Isolate the reactor building and start the standby gas treatment system.
H.
Immediately perform a logic system functional test on the loaic in the other trip systems and daily thereafter not to exceed 7 days.
I.
DELETE J.
Withdraw TIP.
K.
Manually isolate the affected lines.
Refer to section 4.2.E for the requirements of an inoperable system.
L. If one SGTS train is inoperable take actions H or A and F. If two SGTS trains are inoperable take actions A and F.
- 2. When it is determined that a channel is failed in the unsafe cond1tion, the other channels that monitor the same variable shall be functionally tested immediately before the trip system or logic for that function is tripped.
The trip system or the logic for that function may remain untripped for short periods of time to allow functional testing of the other trip system or logic for that function.
- 3. There are four sensors per steam line of which two must be operable.
- 4. Only required in Run Node (Interlocked with Mode Switch).
- 5. Not required in Run Mode (bypassed by mode switch).
Amendment No.
8$, 116 60
6.
Channel shared by RPS and Primary Containment 6 Reactor Vessel Isolation Control Systems.
A channel failure may be a channel failure in each system.
7.
A train is considered a trip system.
8 ~
Two out of three SGTS trains required.
A failure of more than one will require action A and F.
9.
DELETED 10.
Refer to Table 3.7.A and its notes for a listing of Isolation Valve Groups and their initiating signals.
ll.
A channel may be placed in an inoperable status for up to four hours for required surveillance without placing the trip system in the tripped condition provided at least one OPERABLE channel in the same trip system is monitoring that parameter.
12.
A channel contains four sensors, all of which must be operable for the channel to be operable.
Power operations permitted for up to 30 days with 15 of the 16 temperature switches operable.
In the event that normal ventilation is unavailable in the main steam line tunnel, the high temperature channels may be bypassed for a period of not to exceed four hours.
During periods when normal ventilation is not available, such as during the performance of secondary containment leak rate tests, the control room indicators of the affected space temperatures shall be monitored for indications of small steam leaks.
In the event of rapid increases in temper-ature (indicative of steam line break), the operator shall prompt-ly close the main steam line isolation valves.
13'he nominal setpoints for alarm and reactor trip (1.5 and 3.0 times background, respectively) are established based on the normal back-ground at full power.
The allowable setpoints for alarm and reactor trip are 1.2 - 1.8 and 2.4 3,6 times background, respectively.
14 'equires two independent channels from each physical location, there are two locations.
61 Amendment No.
gg N
78)y 7SHt KÃS> Kf4t 116 Corrected
O SURVEllLAllC!RIQOIROQKTSS yoR>>IKaRT CSRTAll44EKT AND RSACToR bulLbIKQ lboLATION IKSTROHaleRTXOR TRRLR ~*2 I lnetcusent Channel-Reactoc building Ventllatlm Righ Radiation - Retueling tcae lnetrusent Channel-SGTS Tcain I buatere laetrusent Channel-SCTS Tcain b Heatere lnetruscnt Channel-SGI'S Tcain C Beatece Reactor building leolation Tisec (cetuel ing tlour)
(1) (1 ~) (22)
( ~ }
(~ I a
on uen orle/3 sonthe once/operating cycle netrusent Check once/day (b)
K/A Reactor building leolation Tiser (reactor rona) once/opera ting cycle K/I
TABLE 4.2.A SURVEILLANCE REQUIREMENTS FOR PRIMARY CONTAINMENT AND REACTOR BUILDING ISOLATION INSTRUMENTATION Function Group 6 Logic Group 8 (Initiating Logic Reactor Building Iso-lation (refueling floor)
Logic Reactor Building Iso-lation (reactor zone)
Logic SGTS Train A Logic SGTS Train B Logic SGTS Train C Logic Functional Test once/operating cycle (18)
Checked during channel functional test.
No further test required once/6 months (18) once/6 months (18) once/6 months (19) once/6 months (19) once/6 months (19)
Calibration Fre uenc N/A N/A (6)
(6)
N/A N/A N/A Instrument Check N/A N/A N/A N/A N/A N/A N/A Instrument Channel-Reactor Cleanup System Floor Dr. Hi. Temp Instrument Channel-Reactor, Cleanup System Space 'High Temp once/operating cycle once/operating cycle N/A N/A
NOTES FOR TABLES 4.2.A THROUGH 4.2.H 1.
Functional tests shall be performed once per month.
2.
Functional tests shall be performed before each startup with a required frequency not to exceed once per week.
3.
This instrumentation is excepted from the functional test definition.
The functional test will consist of injecting a simulated electrical signal into the measurement channel.
4.
Tested during logic system functional tests.
5.
Refer to Table 4.1.B.
6.
The logic system functional tests shall include a calibration once per operating cycle of time delay relays and timers necessary for proper functioning of the trip systems.
7.
The functional test will consist of verifying continunity across the inhibit with a volt-ohmmeter.
8.
Instrument checks shall be performed in accordance with the definition
'f Instrument Check (see Section 1.0, Definitions).
An instrument check is not applicable to a particular setpoint, such as Upscale, but is a qualitative check that the instrument is behaving and/or indicating in an acceptable manner for the particular plant condition.
Instrument check is included in this table for convenience and to indicate that an Instrument Check will be performed on the instrument.
Instrument checks are not required when these instruments are not required to be operable or are tripped.
9.
Calibration frequency shall be once/year.
10.
DELETE ll.
Portion of the logic is functionally tested during outage only.
12.
The detector will be inserted during each operating cycle and the proper amount of travel into the core verified.
13.
Functional test will consist of applying simulated inputs (see note 3).
Local alarm lights representing upscale and downscale trips will be verified, but no rod block will be produced at this time.
The inop-erative trip will be initiated to produce a rod block (SRM and IRM inoperative also bypassed with the mode switch in RUN).
The functions that cannot be verified to produce a rod block directly will be ver-ified during the operating cycle.
Amendment No. 116 109
ATTACHt".FNT TO LICENSE ARENOHEN~ NO.
111 FACILITY OPERATING LICENSE NO.
DPR-52 DOCKET NO. 50-260 Revise Appendix A as follows:
1.
Remove the following pages and replace with identically numbered pages.
57, 58, 59, 60, 61, 86, 88, 109 2.
The marginal lines on these pages denote the area being chanoed.
TABLE 3.2.A PRIMARY CONTAINMENT AND REACTOR BUILDING ISOLATION INSTRUMENTATION Minimum No.
of Instrument Channels Operable er Tri S stem (1) 11)
Function Tri Level Settin Action Remarks Reactor Building Isolation Timer (refueling floor) 05 t ~ 2 secs H or F 1 Below trip setting prevents spurious trips and system per-turbations from init-iating isolation Reactor Building Isola'tion Timer (reactor zone) 0$ t~2 secs GorA or H 1.Below trip setting prevents spurious trips and system per-turbations from init-iating isolation 2 (10)
Group 1 (Initiating) Logic N/A 1.Refer to Table 3.7.A for list of valves.
Group 1 (Actuation)
Logic N/A 1.Refer to Table 3.7.A for list of valves
Hinimum No.
Instrument Channels Operable TABLE 3 ~ 2 h PRIHARY CONTAINHENT AND REACTOR BUILDIHG ISOLATION IHSTRUNEHTATION ri Leve tt n Remarks 2
Group 2 (Initiatin') Logic N/A A or (8 and E) 1.
Refer to Table 3.7.h for list of valves.'roup 2
(RHR Isolation-hctuation)
Logic Croup 8 (Tip-Actuation)
Logic Group 2 (Dryvell Suap Drains-Actuation)
Logic N/A N/h Group 2 (Reactor Building N/A 4 Refueling Floor, and Dry-vell Vent and Purqe-Actuation)
Logic Croup 3 (Initiating) Logic N/A F and C 1.
Part of Group 6 Logic
'1. 'efer to Table 3.7.A for list of valves.
v 1
Group 3 (Actuation) Logic N/A Group 6 Logic N/h Reactor Building Isolation N/A (refueling floor) 1.ogle Reactor Building Isolation N/A (reactor zone)
Logic Group 8 (Initiating) Logic N/h F and G
Nor F B or G or A 1.
Refer to Table 3.7.A for list of valves.
1.
Refer to Table 3.7.h for list of valves.
2.
Sane as Group 2 initiating logic.
.ink..ural.;p, lnstrurent Channels operable
"'l TABLE 3. 2.h PJlINARZ COJJTAINNENl'le REACTOR cViJILDIJJG ISOLATION INSTRUNEHTATIpl'l s
e Resar ks 7(7l tel SGTS Train h Ingle 7)7) {B)
SGTS Train B Laic 1(7) (8)
SGTS Train C Logic Jl/h JJ/h L or fh and P)
I or (h and P)
I or P, and F)
Refer to Table 3.2.B for RCIC and IpCI functions includiny Groupe 1, 5$ and 7 va1vei.
o
NOTES FOR TABLE 3.2.A
- 1. Whenever the respective functions are required to be operable there shall be two operable or tripped trip systems for each function.
If the first column cannot be met for one of the trip systems, that trip system or logic for that function shall be tripped (or the ap-propriate action listed below shall be taken).
If the column cannot be met for all trip systems, the appropriate action listed below shall be taken.
A.
Initiate an orderly shutdown and have the reactor in Cold Shutdown in 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.
B.
Initiate an orderly load reduction and have Main Steam Lines isolated within eight hours.
C.
Isolate Reactor Water Cleanup System.
D.
Isolate Shutdown Cooling.
E.
Initiate, primary containment isolation within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.
F.
The handling of spent fuel will be prohibited and all operations over spent fuels and open reactor wells shall be prohibited.
G.
Isolate the reactor building and start the standby gas treatment system.
H.
Immediately perform a logic system functional test on the logic in the other trip systems and daily thereafter not to exceed 7 days.
I.
DELETE J.
Withdraw TIP.
K.
Manually isolate the affected lines.
Refer to section 4.2.E for the requirements of an inoperable system.
L. If one SGTS train is inoperable take actions H or A and F. If two SGTS trains are inoperable take actions A and F.
- 2. When it is determined that a channel is failed in the unsafe condition, the other channels that monitor the same variable shall be functionally tested immediately before the tripsystem or logic for that function is tripped.,
The trip system or the logic for that function may remain untripped for short periods of time to allow functional testing of the other trip system or logic for that function.
- 3. There are foug sensors per steam line of which two must be operable.
- 4. Only required in Run Mode (Interlocked with Mode Switch)..
- 5. Not required in Run Mode (bypassed by mode switch).
Amendment No. gg, 111 60
6.
Channel shared by RPS and Primary Containment 6 Reactor Vessel Isolation Control Systems.
A channel failure may be a'hannel failure in each system.
7.
A train is considered a trip system.
8.
Two out of three SGTS trains required.
A failure of more than one will require action A and F.
9.
DELETED 10.
Refer to Table 3.7.A and its notes for a listing of Isolation Valve Groups and their initiating signals.
ll.
A channel may be placed in an inoperable status for up to four hours for required surveillance without placing the trip system in the tripped condition provided at least one OPERABLE channel in the same trip system is monitoring that parameter.
12.
A channel contains four sensors, all of which must be operable for the channel to be operable.
Power operations permitted for up to 30 days with 15 of the 16 temperature switches operable.
In the event that normal ventilation is unavailable in the main steam line tunne1, the high temperature channels may be bypassed for a period of not to exceed four hours.
During periods when normal ventilation is not available, such as during the performance of secondary containment leak rate tests, the control room indicators of the affected space temperatures shall be monitored for indications of small steam leaks.
In the event of rapid increases in temper-ature (indicative of steam line break),
the operator shall prompt-ly close the main steam line isolation valves.
13.
The nominal setpoints for alarm and reactor trip (1.5 and 3.0 times background, respectively) are established based on the normal back-ground at full power.
The allowable setpoints for alarm and reactor trip are 1.2 1.8 and 2.4 3.6 times background, respectively.
14.
Requires two independent channels from each physical location, there are two locations.
61 Amendment No.
5g, g2, fN, 194 fN, 1N, ill Corrected
O SDRVEILLARCE R()IRE)(n(TS yoR yRIWey CORTAIWENT TARLE a+i A REACTOR RUILDIHG lbOLATIOR INSTRQNENTATICh(
4 oil uen netrunent Check Inetcuaent Channel Reactoc building Ventliatim Rich Radiat(on - Retuelieg rue Inetaeent Channel scTS Tcain A suatece Inetruuent Channel-SCTS Train b Heaters Inetcusent Channel-SCTS Train C Heaters Reactoc bui ldinq Isolation Tlucc (ce(ueling (loot)
(>) (>4) (33)
(4)
(~ I (4)
(4) orle/3 aonthe once/operatlny cycle once/day (5)
RIA R/A R44ctoc building Isol4tion Tlucc (cc4ctoc c4ne) once/operat ivy cycle
TABLE 4.2.A SURVEILLANCE REQUIREMENTS FOR PRIMARY CONTAINMENT AND REACTOR BUILDING ISOLATION INSTRUMENTATION 0
Function Group 6 Logic Group 8 (Initiating Logic Reactor Building Iso-lation (refueling floor)
Logic Reactor Building Iso-lation (reactor zone)
Logic SGTS Train A Logic SGTS Train B Logic SGTS Train C Logic Functional Test once/operating cycle (18)
Checked during channel functional test.
No further test required once/6 months (18) once/6 months (18) once/6 months (19) once/6 months (19) once/6 months (19)
Calibration Fre uenc N/A N/A (6)
(6)
N/A N/A N/A Instrument Check N/A N/A N/A N/A N/A N/A N/A O
5 CDA C+
CD CL Instrument Channel-Reactor Cleanup System Floor Dr. Hi. Temp Instrument Channel-Reactor Cleanup System Space High Temp once/operating cycle once/operating cycle N/A N/A
'OTES FOR TABLES 4.2.A THROUGH 4.2.H 1.
Functional tests shall be performed once per month.
2.
Functional tests shall be performed before each startup with a required frequency not to exceed once per week.
3.
This instrumentation is excepted from the functional teat definition.
The functional test will consist of injecting a simulated electrical signal into the measurement channel.
4.
Tested during logic system functional tests.
5.
Refer to Table 4.1.B.
6.
The logic system functional tests shall include a calibration once per operating cycle of time delay re1ays and timers necessary for proper functioning of the trip systems.
7.
The functional test will consist of verifying continunity across the inhibit with a volt-ohmmeter.
8.
Instrument checks shall be performed in accordance with the definition.
of Instrument Check (see Section 1.0, Definitions).
An instrument check is not applicable to a particular setpoint, such as Upscale, but is a qualitative check that the instrument is behaving and/or indicating in an acceptable manner for the particular plant condition.
Instrument check is included in this table for convenience and to indicate that an Instrument Check will be performed on the instrument.
Instrument checks are not required when these instruments are not required to be operable or are tripped.
9.
Calibration frequency shall be once/year.
Zo.
nzr EXZ ll.
Portion of the logic is functionally tested during outage only.
12.
The detector will be inserted during each operating cycle and the proper amount of travel into the core verified.
13.
Functional test will consist of applying simulated inputs (see note 3).
Local alarm lights representing upscale and downscale trips will be verified, but no rod block will be produced at this time.
The inop-erative trip will be initiated to produce a rod block (SRN and IRM inoperative also bypassed with the mode switch in RUN).
The functions that cannot be verified to produce a rod block directly will be ver-ified during the operating cycle.
Amendment No.
111 109
ATTACHMENT TO LICENSE AMENDNFHT NO. 86 FACILITY OPERATING LICENSE NO.
DPR-68 DOCKET NO. 50-296 Revise Appendix A as follows:
1.
Remove the following pages and replace with identically nUmbered pages.
59, 60, 61, 62, 63, 89, 91, 106 2.
The marqinal lines on these pages denote the area being chanced.
TABLE 3.2.A PRIMARY CONTAINMENT AND REACTOR BUILDING ISOLATION INSTRUMENTATION Minimum No.
of Instrument Channels Operable er Tri S stem (1) 11)
Function Reactor Building Isolation Timer (refueling floor)
Tri Level Settin
- 05. tk2 secs Action HorF Remarks 1.Below trip setting prevents spurious trips and system per-turbations from init-iating isolation Reactor Building Isolation Timer (reactor zone) 05 t~ 2 secs GorA or H 1.Below trip setting prevents spurious trips and system per-turbations from init-iating isolation 2 (10)
Group 1 (Initiating) Logic N/A A
1.Refer to Table 3.7.A for list of valves.
Group 1 (Actuation)
Logic N/A 1.Refer to Table 3.7.A for list of valves
Minimum No.
Instrument Cliannels Operable
'p TABLE 3'+A PRINARY CONTAINNEHT AND REACTOR BUILDING ISOLATION IHSTRQNEHTATION Tri Leve Setti 2
Group 2 (Initiating) Logic N/A hct 1
h or (B and E)
Rcaa ks 1.
Refer to Table 3 7.A for list of valves.
Group 2
(RHR Isolation-Actuation) Logic Group 8 (Tip-Actuation)
Logic Group 2 (Dryvell Suap Drains-Actuation)
Logic Group 2 (Reactor Building 6 Refueling Floor, and Dry-vell Vent and Purge-Actuation) Logic N/h N/A N/h F and G
1.
Part of Group 6 Logic.
S.
1 Group 3 (Initiating) Logic N/h Group 3 (Actuation) Logic N/A Group 6 Logic N/A Group 8 (Initiating) Logic N/h Reactor Building Isolation N/h (refueling floor) Logic Reactor Building Isolation N/A (reactor xone) Logic F and G
HorF 8 or G or h 1
Refer to Table 3.7.h for list of valves.
1.Refer to Table 3.7.A for list of valves.
1.
Refer to Table 3.7.A for list of valves.
2.
Saae as Group 2 initiating logic
)linimum Vo.
Instrument
'hannels Operable TABLE 3 2 h PRIHARV OONTAINHENT AND REACTOR BOILDING ISOLATION INSTRUHEHIATION a)Sat Re aa Re 1(7) (8)
SOTS Train h logic 1(7) (8)
SGTS Train b Logic 1(1) (8)
SGTS Train C Logic H/A L or (h and F)
L or (A and F)
L or (h and F)
Refer to Table 3 l b for RCIC and SPCI functione including Groups e~ 5, and 7 valves.
Ol
NOTES FOR TRBLE 3
2 R
whenever the respective functions are required to be.
operable, there shall be two operable or tri d
i for each function.
r ppe tr p systems 3
If the f'rst column cannot be met cr one of the tri
- systems, that tri s
ystem or logic for that function shall be e
r p taken). If t tr pped (or the appropriate action listed below h 11 b he column cannot be met for all trip systems the appropriate action listed below shall. be taken.
h.
Initiate an orderly shutdown and have the reactor in Cold Shutdown Condition in 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> B.
C ~
E Initiate an orderly load reduction and have Hain Steam Lines isolated within eight hours.
Isolate Reactor Mater Cleanup System.
Isolate Shutdown Coolinq.
Initiate primary containment isolation within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.
o era The handling of spent fuel wi11 be prohibit d d al an 1
be prohibited.
p tions over spent fuels and open reacto ll h
rwe s s all G.
Isolate the reactor building and start the sta db treatment system.
e standby gas H.
Immediately perform a logic system functional test on the logic in the other trip systems and dail th not to exceed 7 days.
y t ereafter I ~
DELETE J.
Withdraw TIP.
L.
Manually isolate the affected li s
R f 4.2.E for th nes.
Re er to section or e requirements of an inoperable system.
h and F.
If one SGTS train is inoperable take actions H or action and F. If two SGTS trains are inoperable take actions 2.
Mhen it is determined that a channel is failed in the unsafe s
a e
unctxonally tested immediately before the trip for short periods of time to allow functional test n
other trip system or logic for th f
or t at function.
Amendment No. 86
- 3. There are four channelsper steam line of which two must be operable.
- 4. Only required in Run Mode (Interlocked with Mode Switch).
- 5. Not required in Run Mode (bypassed by mode switch).
6.
Channel shared by RPS and Primary Containment 6 Reactor Vessel Isolation Control Systems.
A channel failure may be a channel failure in each system.
7.
A train is considered a trip system.
8.
Two out of three SGTS trains required.
A failure of more than one will require action A and F.
9.
- DELETED 10.
Refer to Table 3.7.A and its notes for a listing of Isolation Valve Groups and their initiating signals.
A channel may be placed in an inoperable status for up to four hours for required surveillance without placing the trip system in the tripped condition provided at least one OPERABLE channel in the same trip system is monitoring that parameter.
12.
A channel contains four sensors, all of which must be operable for the channel to be operable.
Power operations permitted for up to 30 days with 15 of the 16 temperature switches operable.
In the event that normal ventilation is unavailable in the main steam line tunnel, the high temperature channels may be bypassed for a period of not to exceed four hours.
During periods when normal ventilation is not available, such as during the performance of secondary containment leak rate tests, the control room indicators of the affected space temperatures shall be monitored for indications of small steam leaks.
In the event of rapid increases in temper-ature (indicative of steam line break), the operator shall prompt-ly close the main steam line isolation valves.
13.
The nominal setpoints for alarm and reactor trip (1.5 and 3.0 times background, respectively) are established based on the normal back-ground at full power.
The allowable setpoints for alarm and reactor trip are 1.2 1.8 and 2.4 3.6 times background, respectively.
14.
Requires two independent channels from each physical location, there are two locations.
Amendment No. PP,
$5, lk, f5, )6, N 86 Corrected 63
TABLE 4 2 A SURVEILLANCE RBQUIRENENTS POR PRIMARY CONTAINNENT AND REACTOR BUILOING ISOLATION INSTRUMENTATION Punction Instrument Channel-Reactor Building Ventilation High Radiation - Refueling Zone Instrument Channel-SGTS Train A Heaters Instrument Channel-SGTS Train B Heaters Instrument Channel-SGTS Train C Heaters Reactor Building Isolation Timer (refueling floor) unct o al T st
(>) (>4) (22)
(4)
(4)
(4)
(4)
Cal bration Pr uen erne/3 months once/operating cycle Instrument Check once/day (8)
NIA Reactor Building Isolation Timer (reactor xone)
(4) once/operating cycle N/A
Function TABLE 4.2.A SURVEILLANCE REQUIREMENTS FOR PRIMARY CONTAINMENT Functional Test Calibration Fre uenc Instrument Check AND REACTOR BUILDING ISOLATION INSTRUMENTATION Group 6 Logic Group 8 (Initiating Logic Reactor Building Iso-lation (refueling floor)
Logic Reactor Building Iso-lation (reactor zone)
Logic SGTS Train A Logic SGTS Train B Logic SGTS Train C Logic once/operating cycle (18)
Checked during channel functional test.
No further test required once/6 months (18) once/6 months (18) once/6 months (19) once/6 months (19) once/6 months (19)
N/A N/A (6)
(6)
N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A Instrument Channel-Reactor Cleanup System Floor Dr. Hi. Temp Instrument Channel-Reactor Cleanup System Space High Temp once/operating cycle once/operating cycle N/A N/A
0 k
I
1 ~
2 ~
3>>
4>>
5 SPORSLS42
~ATHRH48 Functional tests shall be performed once per month.
toncticeal teats shall be performed before each atartup vith
~ required frequency not to exceed once per veek This instrumentation is excepted from the functional test definition.
The functional test vill consist of infecting a simulated electrical signal into the measurement channel.
Teated during logic system functional tests.
Refer to Table 4.1.B.
6 ~
The logic system functional tests shall include a calibration once per operating cycle of time delay relays and timers necessary for proper functioning of the trip systems.
The functional test vill consist of verifying continuity across the inhibit vith a volt-ohmmeter.
8 ~
9>>
(~o 11 ~
13 ~
Instrument checks shall bc performed in accordance vith the definition of Instrument Check (scc section 1
0 ~
Definitions).
An instrument check is not applicable to a particular setpoint, such as Upscale, but is a qua1itative check that the instrument is behaving and/or indicating in an acceptable manner for the particular plant condition.
Instrument check is included in this table for convenience and to indicate that an Instrument Check villbe performed on the instrunent.
Instrument checks are not required vhen these instruments arc not required to be operable or are tripped Calibraticn frequency shall be once/year.
DELETE portion of t.hc logic ia functionally tested during outage only The detector vill be inserted during each operating cycle and thc proper amount of travel into the core verified functional test villconsist of applying simulated inputs (scc note 3).
Local alarm lights representing upscale and dovnscale tripe <<ill be verified, but no rod block vill bc produced at this time.
The inoperative trip F11 be initiated to produce a rod block (SRH and IJN inoperative also bypassed vith the mode avitch in RUN) ~
The functions that cannot be verified to produce a rod block directly vill be verified during the operating cycle.
106 Amendment No.
86