UNIT 3 PROPOSED CHANGES Bli0280277 SiiOiq PDR ADOCK 05000259 P
LZMZTING CONDITIONS FOR OPERATION SURVEILLANCE REQUIREMENTS co~~E& SYsXXM 4 7 CONT INMENT SYST MS three and one-third year intervals so that any ten-year interval would include four ILRT~s.
" These intervals may be extended up to ten months if necessary to coincide with refueling outage.
f.
Except for the initial ZLRT, all ZLRT~s shall be performed without leak repairs immediately prior to or during the test.
Zf leak repairs are necessary in order to perform ZLRT, they shall
'be preceded by local leak measurements where-possible.
The leak rate difference prior to and after repair shall be added to final integrated leak rate results, L~
ox Lt
~
Following each ZLRT, if the measured leak
margin to allow for leakage deterioration which may occur during the period between leak rate tests.
The primary containment leak rate test frequency is based on maintaining adequate assurance that the leak rate remains within the specification.
The leak rate test frequency is based on the NRC guide for developing leak rate testing and surveillance of reactor containment vessels.
Allowing the test intervals to be extended up to 10months permits some flexibilityneeded ta have the tests coincide with scheduled or unscheduled shutdown periods.
il The penetration and air purge piping leakage test frequency,'
along with the containment leak rate tests, is adequate to allow detection of leakage trends.
Whenever a bolted double-gasketed penetration is broken and remade, the space between the gaskets is pressurized to determine that the seals are performing properly.
Zt is expected that the majority of the leakage from
~ valves, penetrations and seals would be into the reactor'uilding.
However, it is possible that leakage into other parts of the facility could occur.
Such leakage paths that may affect significantly the consequences of accidents are to be minimized.
The primary containment is normally slightly pressurized during period of reactor operation.
Nitrogen used for inerting could leak out of the containment but air could not leak in to increase oxygen concentration.
Once the containment is filled with nitrogen to the required concentration, determining the oxygen concentration twice a week serves as an added assurance that the oxygen c'oncentzation will not exceed 4%.
3.7.B/3.7.C Standb Gas Treatment S stem and Seconda
'ontainment The secondary containment is designed to minimize any ground level release of radioactive materials which might result from a.
serious accident.
The reactor building provides secondary containment during reactor operation, when the drywell is sealed and in service; the reactor building provides primary containment when the reactor is shutdown and the drywell is open, as during refueling.
Because the secondary containment is an integral part of the complete containment
- system, secondary containment is required at all times that primary. containment is required as well as during refueling.
The standby gas treatment system is designed to filter and
'exhaust the reactor building atmosphere to the stack during secondary containment isolation conditions.
All three standby qas treatment system fans are designed to automatically start
'pon containment isolation and to maintain the reactor building pressure to the design negative pressure so that. all leakage should be in-leakage.
291
ENCLOSURE 2 JUSTIFICATION (TVA BFNP TS 168)
These proposed changes increase the extension period for performing the
'ntegrated leak rate testing (ILRT) for the primary containment from eight months to ten months and bring this specification into conformance with Standard Technical Specifications.
This change only allows ILRT intervals to be extended if necessary and does not change or effect any safety system.'our ILRT's will still be performed in any ten-year period as rdquired by 10'CFR Part 50.
e