APPENDIX B NOTICE. OF DEVIATION Tennessee Val 1 ey Authority Browns Ferry License Nos. DPR-33, DPR-52 and DPR-68 Based on the NRC inspection'onducted on May 18-22 and June 9-10, 1981, certain of your activities appear to deviate from your commitments to the Commission and from applicable guides,.

codes, or standards which are approved by the Commission as indicated. below:

Weld Penetration Pi in

. S stem Unit The Browns Ferry FSAR indicates that the Code applicable to the containment piping penetrations is ASME Section III'1965'dition).

ASME Section III refers to. ASME.Section VIII for radiography on containment penetration welds.,

ASME Section VIII, provides fi,lm density, penetrameter, and location marker requirements for the. radiography.

Contrary; to. the.

above, the. examples of main steam and. feedwater system piping containment penetration weld radiographs listed below do not comply with the. code film-density, penetrameter and location marker requirements.

GMS-1.-36 GMS-1;38 GMS-1-36 GMS-2-'2 GMS-2-38 GMS-3-36 X-7A X-7B;..

X-9A X-7D X"9B X-7A Main Steam Main Steam Feedwater-Main Steam Feedwater Main Steam 1,

1

=1 2

2.

3 8<09090eeo 8<08ac PDR ADOCK 05000259 8

PDR g4