AUG 8 0 1981
g~//OLd
ZE Sg Z~~0gg
Val 1 ey Authority
ATTN:
Mr. H. G. Parri s
Manager of Power
500A Chestnut Street Tower II
Chattanooga,
TN
37401
gyp O9 l981
Gentlemen:
Subject:
Report Nos. 50-259/81-2
50-260/81-21
and 50-296/81-21
This refers to the routine safety inspection
conducted
by Mr. G. A. Belisle and
others
of this office
on August 3-7,
1981,
of activities
authorized
by
NRC
Operating
License
Nos.
DPR-52 and
DPR-68 for the
Browns
Ferry facility
and to the discussion
of our findings held with Mr.
H.
L. Abercrombie,
Plant
Superintendent,
at the conclusion of the inspection.
Areas
examined
during
the
inspection
and
our findings
are
discussed
in the
enclosed
inspection
report.
within these
areas,
the inspection
consisted
of
.selective
examinations
of procedures
and representative
records,
interviews with
personnel,
and observations
by the inspectors.
Within the scope of this inspection,
no violations or deviations were disclosed.
Me have
examined
actions
you
have
taken with regard
to previously identified
enforcement matters.
These are discussed
in the enclosed
inspection report.
In accordance
with 10 CFR 2.790 of the Commission's
regulations,
a copy of this
letter
and the enclosed
report will be placed in the
NRC's Public Document
Room.
If the report contains
any information that you believe to
be
exempt
from dis-
closure
under
10 CFR 9.5(a)(4), it is necessary
that you:
(a) notify this office
by telephone within ten days
from the date of this letter of your intention to
file a request for withholding; and (b) submit within twenty-five days
from the
date of this letter
a written application to this office to withhold such infor-
mation.
If your receipt of this letter
has
been
delayed
such that less
than
seven
days are available for your review, please notify this office promptly so
that
a
new
due
date
may
be established.
Consistent
with section
2.790(b)(1),
such application must be accompanied
by an affidavit, executed
by the owner of the
information which identifies the document or part thereof
sought to be withheld,
and
a full statement
of the reasons
on the basis of which it is claimed that the
information
should
be withheld
from public disclosure.
This section
further
requires
the statement
to address
with specificity the considerations
listed in
The information sought to be withheld shall
be incorporated
as far as possible into a separate
part of the affidavit. If we do not hear
from
you in this regard within the specified periods
noted above,
the report will be
placed in the Public Document
Room.
Si09090329
Si0820
ADOCK 05000259
G
~/PI
fig
It
I'
l
AUG 2 0 198>
Valley Authority
Should you have
any questions
concerning this letter,
we will be glad to discuss
them with you.
R.
C. Lewis, Chief
Reactor Projects
Branch
1
Division of Resident
and
Reactor Project Inspection
Enclosure:
Inspection Report Nos. 50-259/81-21,
50-260/81-21
and 50-296/81-21
cc w/encl:
H. J.
Green, Director of Nuclear Power
H. L. Abercrombie, Plant Superintendent
R.
E. Rogers, Project Engineer