Forwards LER 79-023/03L-0
Date released: 09/27/2018 Download: ML18024B199


LER 79-023/03L-0:on 791202,diesel Generator 3C Tripped Following Start of RHR Pump 3B.Caused by Excessive Voltage Output of Frequency Generator Due to Component Drift.Voltage Output Corrected & Speed Sensing Panels Calibr
ML18024B200
Person / Time
Site: Browns Ferry Tennessee Valley Authority icon.png
Issue date: 12/31/1979
From:
TENNESSEE VALLEY AUTHORITY
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
Download: ML18024B200 (3)
Forwards LER 79-023/03L-0
ML18024B198
Person / Time
Site: Browns Ferry Tennessee Valley Authority icon.png
Issue date: 12/31/1979
From: Calhoun J
TENNESSEE VALLEY AUTHORITY
To: OREILLY J P
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
Download: ML18024B198 (2)