ML18024A976

From kanterella
Jump to navigation Jump to search
Notice of Violation from Insp on 790521-25
ML18024A976
Person / Time
Site: Browns Ferry  
Issue date: 06/25/1979
From:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
To:
Shared Package
ML18024A973 List:
References
50-259-79-14, 50-260-79-14, 50-296-79-14, NUDOCS 7908270199
Download: ML18024A976 (2)


Text

APPENDIX A NOTICE OF VIOLATION Tennessee Valley Authority Browns Ferry, Unit 3 License No.

DPR-68 Based on the NRC inspection May 21-25, 1979, certain of your activities were apparently not conducted in full compliance with NRC requirements as indicated below.

These items have been categorized as described in correspondence to you dated December 31, 1974.

As required by Technical Specification 6.3.a.l, detailed written procedures, including applicable checkoff lists covering normal operation and components involving nuclear safety of the facility shall be prepared, approved and adhered to.

Operating Instruction 74, "RHR Systems",

Drawing No. 47W811-1, "Flow Diagram RHR System",

and Drawing No. 47W859-1, "Flow Diagram, Emergency Equipment Cooling Water" require certain valves lined up for LPCI mode during normal operation are locked open.

Contrary to the above, two outlet valves (HCV 74-33 and HCV 74-44) at the discharge side of RHR Heat Exchangers 3B and 3D were not locked during the normal operation on May 24, 1979.

Other ESF valves not locked during the operation were EECW RHR Pump Seal Heat Exchanger Valves Nos.

561, 572 and 614.

This is an infracti.on.

C