APPENDIX A NOTICE OF VIOLATION Tennessee Valley Authority Browns Ferry, Unit 3 License No.
DPR-68 Based on the NRC inspection May 21-25, 1979, certain of your activities were apparently not conducted in full compliance with NRC requirements as indicated below.
These items have been categorized as described in correspondence to you dated December 31, 1974.
As required by Technical Specification 6.3.a.l, detailed written procedures, including applicable checkoff lists covering normal operation and components involving nuclear safety of the facility shall be prepared, approved and adhered to.
Operating Instruction 74, "RHR Systems",
Drawing No. 47W811-1, "Flow Diagram RHR System",
and Drawing No. 47W859-1, "Flow Diagram, Emergency Equipment Cooling Water" require certain valves lined up for LPCI mode during normal operation are locked open.
Contrary to the above, two outlet valves (HCV 74-33 and HCV 74-44) at the discharge side of RHR Heat Exchangers 3B and 3D were not locked during the normal operation on May 24, 1979.
Other ESF valves not locked during the operation were EECW RHR Pump Seal Heat Exchanger Valves Nos.
- 561, 572 and 614.
This is an infracti.on.