BFN-26 Table 10.6-1 REACTOR BUILDING CLOSED COOLING WATER SYSTEM AND EQUIPMENT DATA RBCCWS Design Pressure/Temperature Piping - 150 psig/230°F Equipment - 150 psig/200°F Raw Cooling Water Type River Water Normal Design Inlet Temperature 90°F Maximum Inlet Temperature 95°F RBCCWS Heat Exchangers Number Provided 2/unit - 1 common spare Materials Tubes Admiralty - SS for RBCCW HX1A and HX1B only Tube Sheets Carbon Steel - SS for RBCCW HX1A and HX1B only Shell Carbon Steel RBCCWS Pumps Number Provided 2/unit - 1 common spare Materials Casing Cast Steel Impeller Bronze Shaft Heat Treated High Carbon or Alloy Steel
BFN-26 Table 10.6-2 REACTOR BUILDING CLOSED COOLING WATER SYSTEM HEAT EXCHANGER OPERATING CONDITIONS Number of HX's in Heat Transfer (Btu/hr X 106)/HX operation per unit Normal 15.65 (Pre-uprated) 2 16.33 (Uprated) 2 Startup 15.80 (Pre-uprated) 2 16.04 (Uprated) 2 Cooldown 11.10 2
Shutdown 3.18 (Pre-uprated) 2 3.31 (Uprated) 2 Normal Flow (GPM)
Shell Side 1685 Tube Side 2550 Fluid Tube Side (river water)
Additives to minimize corrosion Shell Side (demineralized water)
Additives to minimize corrosion Seismic Coefficients 1.0g horizontal 0.07g vertical
BFN-26 TABLE 10.6-3a REACTOR BUILDING CLOSED COOLING WATER SYSTEM HEAT LOADS (Pre-uprated)
One Unit MODE OF SERVICE NORMAL OPERATION COOLDOWN SHUTDOWN STARTUP AC POWER FAILURE P(Pal)
Tin°F Tout°F P(Pal)
Tin°F Tout°F P(Pal)
Tin°F Tout°F P(Pal)
Tin°F Tout°F P(Pal)
Tin°F Tout°F System Equipment No. of Units Total 106Btu/hr Total GPM Total 106Btu/hr Total GPM Total 106Btu/hr Total GPM Total 106Btu/hr Total GPM Total 106Btu/hr Total GPM Fuel Pool Heatr 2
9 100 112 0.1 100 112 0.1 100 112 9
100 112 Exchange 8.8 1500 1.0 167 1.0 167 8.8 1500 Reactor Recirculation 2
10 100 115 10 100 115 10 100 115 10 100 115 Pump and Motor 0.9 120 0.9 120 0.9 120 0.9 120 Drywell Atmosphere 8*
16.8 100 110 15.0 100 110 16.8 100 110 16.8 100 107 15.0 100 110 Cooler 5.19 1038 6.4 1274 5.19 1038 3.62 1038 6.4 1274 Reactor Bldg. Equipment 1
1.5 100 125 1.5 100 125 1.5 100 125 Drain Tank Cooler 0.5 40 0.5 40 0.5 40 Drywell Equipment 1
1.5 100 125 1.5 100 125 1.5 100 125 1.5 100 125 Drain Sump Cooler 0.5 40 0.5 40 0.5 40 0.5 40 Sample Cooler 4
3 100 111 3
100 111 3
100 111 0.04 6.5 0.04 6.5 0.04 6.5 Cleanup Recirculating 2
10 100 120 10 100 120 10 100 120 10 100 120 Pump Cooler 0.17 15 0.17 15 0.17 15 0.17 15 Cleanup System 1
8 100 150 7.5 100 143 5
100 171 Nonregenerative Heat Exchanger 15.1 610 12.7 587 17.1 482 Closed Cooling Water Heat Exchanger 2
4 90 102.3 0.75 90 110.2 0.1 90 104.2 4
90 102.4 0.1 90 107.3 Raw Cooling Water Loop - Tube Side 31.3 5100 22.2 2200 6.36 900 31.6 5100 7.8 900 Closed Cooling Water 2
12 118.5 100 5
118.9 100 1.5 110.4 100 10 119.4 100 2.1 110.9 100 Heat Exchanger CCW Loop - Shell Side 31.30 3369.5 22.2 2249.5 6.36 1220 31.6 3241.5 7.8 1434
- This number of drywell atmosphere coolers is the total number in operation which must provide cooling for heat loads listed with a 25 percent standby capability (two coolers and fans not in operation). Spare fans may be placed in service at operator discretion to provide additional margin.
There is a total of ten drywell atmosphere coolers located in each unit's drywell.
BFN-26 TABLE 10.6-3b REACTOR BUILDING CLOSED COOLING WATER SYSTEM HEAT LOADS (Uprated)
One Unit MODE OF SERVICE NORMAL OPERATION COOLDOWN SHUTDOWN STARTUP AC POWER FAILURE P(Pal)
Tin°F Tout°F P(Pal)
Tin°F Tout°F P(Pal)
Tin°F Tout°F P(Pal)
Tin°F Tout°F P(Pal)
Tin°F Tout°F System Equipment No. of Units Total 106Btu/hr Total GPM Total 106Btu/hr Total GPM Total 106Btu/hr Total GPM Total 106Btu/hr Total GPM Total 106Btu/hr Total GPM Fuel Pool Heat 2
9 100 112 0.1 100 112 0.1 100 112 9
100 112 Exchanger 9.24 1500 1.0 167 1.0 167 9.24 1500 Reactor Recirculation 2
10 100 115 10 100 115 10 100 115 10 100 115 Pump and Motor 0.9 120 0.9 120 0.9 120 0.9 120 Drywell Atmosphere 8*
16.8 100 110 15.0 100 110 16.8 100 110 16.8 100 107 15.0 100 110 Cooler 5.45 1038 6.4 1274 5.45 1038 3.62 1038 6.4 1274 Reactor Bldg. Equipment 1
1.5 100 125 1.5 100 125 1.5 100 125 Drain Tank Cooler 0.5 40 0.5 40 0.5 40 Drywell Equipment 1
1.5 100 125 1.5 100 125 1.5 100 125 1.5 100 125 Drain Sump Cooler 0.5 40 0.5 40 0.5 40 0.5 40 Sample Cooler 4
3 100 111 3
100 111 3
100 111 0.04 6.5 0.04 6.5 0.04 6.5 Cleanup Recirculating 2
10 100 120 10 100 120 10 100 120 10 100 120 Pump Cooler 0.17 15 0.17 15 0.17 15 0.17 15 Cleanup System 1
8 100 150 7.5 100 143 5
100 171 Nonregenerative Heat Exchanger 15.86**
610 12.7**
587 17.1**
482 Closed Cooling Water Heat Exchanger 2
4 90 103.3 0.75 90 110.2 0.1 90 104.2 4
90 102.4 0.1 90 107.3 Raw Cooling Water Loop - Tube Side 32.66 5100 22.2 2200 6.62 900 32.07 5100 7.8 900 Closed Cooling Water 2
12 118.5 100 5
118.9 100 1.5 110.4 100 10 119.4 100 2.1 110.9 100 Heat Exchanger CCW Loop - Shell Side 32.66 3369.5 22.2 2249.5 6.62 1220 32.07 3241.5 7.8 1434
- This number of drywell atmosphere coolers is the total number in operation which must provide cooling for heat loads listed with a 25 percent standby capability (two coolers and fans not in operation). Spare fans may be placed in service at operator discretion to provide additional margin.
There is a total of ten drywell atmosphere coolers located in each unit's drywell.