MNS-18-003, End of Cycle 25 In-service and Steam Generator In-service Inspection Summary Reports

From kanterella
(Redirected from ML18023A160)
Jump to navigation Jump to search

End of Cycle 25 In-service and Steam Generator In-service Inspection Summary Reports
ML18023A160
Person / Time
Site: McGuire Duke Energy icon.png
Issue date: 01/11/2018
From: Teresa Ray
Duke Energy Carolinas
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
MNS-18-003
Download: ML18023A160 (28)


Text

{{#Wiki_filter:' .'.:-_~\\,: \\ ~ ~~DUKE ~ 11 ENERGY"' Serial No: MNS-18-003 January 11, 2018 U.S. Nuclear Regulatory Commission Attn: Document Control Desk Washington, DC 20555-0001

Subject:

Duke Energy Carolinas, LLC (Duke Energy) McGuire Nuclear Station, Unit 1 Docket Number 50-369 Renewed Facility License Number NPF-9 Thomas D. Ray, P.E. Site Vice President McGuire Nuclear Station Duke Energy MG01VP I 12700 Hagers Ferry Road Huntersville, NC 28078 o: 980.875.4805 f: 980.875.4809 Tom.Ray@duke-energy.com End of Cycle 25 In-service and Steam Generator In-service Inspection Summary Reports p.,ursuant to American Society of Mechanical Engineers (ASME) Section XI, as amended by ASME Code Case N-532-5, Duke Energy hereby submits the In-service Inspection Summary Report for the McGuire Unit 1 outage designed M1 R25. Additionally, pursuant to ASME Section XI and McGuire Technical Specification 5.6.8, Duke Energy submits the Steam Generator In-service Inspection Summary Report for the McGuire Unit 1 outage designed M1 R25. This submittal document contains no regulatory commitments. If there are any questions or if additional information is needed, please contact Brian Richards of Regulatory Affairs at (980) 875-5171. Sincere!:, ~ >?;7 n Thomas D. Ray : : McGuire Unit 1 Outage M1 R25 In-service Inspection Summary Report McGuire Unit 1 Outage M1 R25 Steam Generator In-service Inspection Summary Report

. -"r U.S. Nuclear Regulatory Commission January 11, 2018 Page 2 xc: C. Haney, Regional Administrator U.S. Nuclear Regulatory Commission - Region II Marquis One Tower 245 Peachtree Center Ave. NE, Suite 1200 Atlanta, GA 30303-1257 Electronic: A. Hutto, NRC Senior Resident Inspector Andy.Hutto@nrc.gov M. Mahoney, Project Manager Michael. Mahoney@nrc.gov P. Hooper, Standards and Inspections (NC DOL) phil.hooper@labor.nc.gov

McGuire Unit 1 Outage M1 R25 In-service Inspection Summary Report

CASE N-532-5 FORM OAR-1 OWNER'S ACTIVITY REPORT Report Number ________ O_w_n_e_r'_s_A_c_ti_v_it~y_R_e~p_o_rt_fo_r_R_ef_u_e_li_n_g-'-O_u_ta~g~e_M_1_R_2_5 _______ _ Plant Unit No. (if applicable) McGuire Nuclear Station, 12700 Hagers Ferry Rd, Huntersville, NC 28078-9340 Commercial service date -------- 12/01/1981 Refueling outage no. _M_1_R_2_5 __ _ Current inspection interval _IS_l_-4c..ct.c.ch,_, C--'----"-o_n-'-ta_in-'-m-'-'-'-e.C.Cn-'-t-.c.3c..:rd"----------------------- (1st. 2nd, 3rd, 4th, other) Current inspection period ISi-2nd, Containment-2nd (1st, 2nd, 3rd) Edition and Addenda of Section XI applicable to the inspection plans 2007 with 2008 addenda Date and revision of inspection plans See attachment Edition and Addenda of Section XI applicable to repair/replacement activities, if different than the inspection plans Same Code Cases used: The following Code Cases are permitted by the ISi Plans: N-513-3, N-526, N-532-5, N-586-1, N-613-1, N-639, N-643-2, N-648-1, N-663, N-706-1, N-716, N-722-1, N-729-1, N-731, N-735, N-770-1 (If applicable) CERTIFICATE OF CONFORMANCE I certify that (a) the statements made in this report are correct; (b) the examinations and tests meet the Inspection Plan as required by the ASME Code, Section XI; and (c) the repair/replacement activities and evaluations supporting the completion of M1 R25 conform to the requirements of Section XI. (refueling outage number) Signed ~~-_M_*~_. ____ Date CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of North Carolina and employed by The Hartford Steam Boiler Inspection and Insurance Co. of Hartford, CT have inspected the items described in this Owner's Activity Report, and state that, to the best of my knowledge and belief, the Owner has performed all activities represented by this report in accordance with the requirements of Section XI. By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the repair/replacement activities and evaluation described in this report. Furthermore, neither the Inspector nor his e layer shall be liable in any anner for any personal injury or property damage or a loss of any kind arising from or c nected with this inspectio

  • Page 1 of4 Commissions A)f>;; Y 7~ At. #;..s;: t./

National Board, State, Province, :nd Endorsements r

CASE N.. 532-5 Attachment McGuire Unit 1 End of Cycle 25 lnservice Inspection Report The McGuire Nuclear Station Unit 1 Fourth Ten Year lnservice Inspection (ISi} Plan complies with 10CFR50.55a(g), which implements, by reference, the American Society of Mechanical Engineers (ASME) Boiler and Pressure Vessel Code, Section XI, 2007 Edition with 2008 Addenda. This summary report is being submitted pursuant to the reporting requirements of ASME Section XI as amended by ASME Code Case N-532-5, "Repair/Replacement Activity Documentation Requirements and lnservice Inspection Summary Report Preparation and Submission Section XI, Division 1". Contained within this summary report are the form OAR-1 (Owner's Activity Report) and Tables 1 and 2 of Code Case N-532-5 for McGuire Nuclear Station during cycle 25 and Refueling Outage 25 (M1 R25, Note format change). M1 R25 is the second (and last) outage of the second ISi period in the fourth inspection interval. M 1 R25 is the first outage of the second Containment period in the third inspection interval. This report includes all Repair/Replacement activities from April 17, 2016 through October 16, 2017, cycle 25. Date and Revision of lnservice Inspection Plans: Fourth Interval lnservice Inspection Plans The following document comprises the McGuire Nuclear Station 4th Interval lnservice Inspection Plan for Unit 1 {Class 1, 2, and 3 Components): "Fourth Interval lnservice Inspection Plan, McGuire Nuclear Station Unit 1 and Unit 2, General Requirements" - Document "MISl-1462.10-0040-GEN REQ UNIT 1 SECOND AND THIRD PERIODS AND UNIT 2", Rev 1, dated 05/28/2015. The following document comprises the McGuire Nuclear Station 4th Interval lnservice Inspection Pressure Test Plan for Unit 1: "McGuire Nuclear Station - Fourth Interval lnservice Inspection Plan - Pressure Test Plan", Document MISl-1462.20-0040-PTPLAN, Rev 1, dated 06/18/2015. Containment lnservice Inspection Plan The following document comprises the McGuire Nuclear Station 3rd Interval Containment lnservice Inspection Plan for Unit 1 {Class MC): "McGuire Nuclear Station - Third Interval Containment lnservice Inspection Plan - Containment - Units 1 & 2", Document #MC.:ISIC3-1042-0001, Rev. 4, dated 11/22/2016. Page 2 of 4

CASE N-532-5 McGuire Nuclear Unit 1 Form OAR-1 Owner's Activity Report Table 1 Items with Flaws or Relevant Conditions that Required Evaluation for Continued Service Examination Category and Item Description Evaluation Description Item Number Item was evaluated by Engineering in NCR Minor leak on line upstream of 1 RN-884 02032731and found to be acceptable. This is D-B / 02.10 NOT considered an analytical evaluation. This (Drain on KD return line) item was repaired during M1 R25, see enlry in table 2. RN vent line piping failed when OPS attempted to remove pipe cap. Temp EC 410138 installed under WO 20204203 and evaluated in NCR D-B / 02.10 Leak on line upstream of 1 RN-188 during M1 R25 02156405 to be acceptable for continued interim (Vent on 1B KC HX) service until repair was performed. This is NOT considered an analytical evaluation. This item was code repaired during M1 R25, see entry in table 2. A relevant condition was identified during VT-3 examination of support. As-found condition was F-NF1.20 Relevant condition on 1MCR-Nl-701 during M1R25 evaluated as acceptable for continued service by Engineering (Ref NCR 2153388 and NOE exam report VT-17-098). This is NOT considered an analvtical evaluation. A relevant condition was identified during VT-3 examination of support. As-found condition was F-NF1.20 Relevant condition on 1 MCA-NV-H39 evaluated as acceptable for continued service by Engineering (Ref NCR 2149188 and NOE exam report VT-17-065). This is NOT considered an analytical evaluation. A relevant condition was identified during VT-3 examination of support. As-found condition was F-NF1.30 Relevant condition on 1 MCA-RN-2052 evaluated as acceptable for continued service by Engineering (Ref NCR 2146009 and NOE exam report VT-17-048). This is NOT considered an analytical evaluation. Thickness readings below 87.5% of nominal wall were Items were evaluated by Engineering NCR R-A / R.17 observed during UT examination of wall thickness grid at 02156282 and found to be acceptable. This is weld 1RNFW197-19, 1RN1F661 and 1RN535-4during NOT considered an analytical evaluation. M1R25. Page 3 of 4

CASE N.. 532-5 McGuire Nuclear Unit 1 Form OAR~1 Owner's Activity Report Table 2 Abstract of Repair/Replacement Activities Required For Continued Service Code Item Description Description of Work Date Completed Repair/ Replacement Class Plan Number 1 Snubber 1-MCR-NV-1096 Snubber replaced due to failure 10/8/2017 W020203536 of existinQ snubber (broke) 2 Snubber 1-MCR-NC-0910 Snubber replaced due to failure 10/6/2017 WO 20203157 of functional test Replaced 1VA-AH-0030 / 1A KF Pump AHU Cooling Coil 3 1A KF Pump AHU Coil (on-line leak). Component was 9/10/2017 WO 20175767 isolated until repair completed. Ref NCR's 02132243 & 02131707. Replace piping in the vicinity of weld 1RN1FW195-15 (MCFI-3 RN piping in vicinity 1 RN195). Leak discovered 10/11/2017 WO 20203931 of weld 1RN1FW195-15 during weld prep for EOG examination during M1 R25. Ref NCR 02156395. 3 RN piping upstream of 1 RN-884 Code repair to pipe upstream of 10/9/2017 WO 20082987 1RN-884. Ref. NCR 02032731 Code repair to pipe upstream of 3 RN piping upstream of 1 RN-883 1 RN-883. This was a EOG item 1017/2017 WO 20101843 from the issue at 1 RN-884. Code repair to broken pipe 3 RN piping upstream of 1 RN-188 upstream of 1RN-188. Ref 10/1312017 W020204203 NCR 02156405. Page 4 of4

McGuire Unit 1 Outage M1 R25 Steam Generator In-service Inspection Summary Report J

Steam Generator In-service Inspection Summary Report McGuire Nuclear Station Unit 1 MJR25 Fall Outage 2017 Location: McGuire Nuclear Station, 12700 Hagers Feny Road Huntersville, N.C. 28078-9340 Approved Controlled Distribution Copy No. Original Uncontrolled Distribution 2 3 NRC Docket No. 50-369 National Board No. 44 Commercial Service Date: December 1, 1981 Owner: Duke Energy Carolinas, LLC 526 South Church St. Charlotte, N.C. 28202 Revision 0 Date: Date: Date: Document Completion Date: ____ _ Assigned To McGuire Nuclear Station Document Control Master File MC 1201.35 NRC Document Control Hartford Steam Boiler Inspection and Insurance Corporation (AlA) State of North Carolina Department of Labor

CASES OF ASME BOILER AND PRESSURE VESSEL CODE FORM OAR-1 OWNER'S ACTIVITY REPORT Report Number Owner's Activity Report for SG Inspection Outage M1 R25 Plant McGuire Nuclear Station, 12700 Hagers Ferry Rd Huntersville NC 28078-9340 CASE (continued) N-532-5 Unit No~. -~------Commercial servicedate December 1, 1981 Refueling outage no. ~M~1~R=25~------ (if applicable) Currentinspectioninterval _____________ __,4.,,_th,__ _______________________ _ 11st, 2nd, 3rd, 4th, other) Current inspection period ______________ =2n=d~----------------------~ (1st, 2nd, 3rd) Edition and Addenda of Section XI applicable to the inspection plans 2007 Edition through 2008 Addenda Date and revision of inspection plans ____ __,4~-7~-1~7~R=e~v=2-"{M~-~IS~IS=G~-=0~16=9=.0=30=*=00~4=0,_) ________________ _ Edition and Addenda of Section XI applicable to repair/replacement activities, if different than the inspection plans Same as Pla=n~--- Code Cases used for inspection and evaluation: ~N~-5=3=2~-5~---------------------------- (if applicable, including cases modified by Case N-532 and later revisions) CERTIFICATE OF CONFORMANCE I certifythat(a)thestatementsmade in this report are correct; (b)theexaminationsand tests meet the Inspection Plan as required by the ASME Code, Section XI; and ( c) the repair/replacement activities and evaluations supporting the completion of.,.,M,..,_1'""R2,.,5'------ ______ _ conform to t h ~ ~ Signed Mitch Hatley Principal Engineer Owner or Owner's Deslgnee, Title (refueling outage number) Date /J / Jo/'..., -~-, '-1--1--------------- CERTIFICATE OF INSERVICE INSPECTION I, the undersi~ holping.a.Ya lid commission issue~ b~e National Board of Boiler and Pressure Vessel Inspectors and employed byH/J-/(Tl-'E)&)).s:J&IJ""f. t!ua:.__~

  • ,'()lfJE~~;k_have inspected the items described in this Owner's Activity Report, and state that. to the best of my knowledge and belief. the Owner has performed all activities represented by this report in accordance with the requirements of Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the air/replacement activities and ev luation described in this report. Furthermore. neither the Inspector nor his employer shall be liable ny mannerfor any personal inj or property damage or a loss of any kind arising from or connected with this inspection.

CASES OF ASME BOILER AND PRESSURE VESSEL CODE TABLE 1 ITEMS WITH FLAWS OR RELEVANT CONDITIONS THAT REQUIRED EVALUATION FOR CONTINUED SERVICE Examination Category and Item Number Category 8-Q 816.20.001 816.20.002 816.20.003 816.20.004 Item Description Steam Generator Tubing in U-Tube Design TABLE 2 Evaluation Description No ASME Section XI Acceptance Requirement Exceeded (Reference Attached Inspection Report) ABSTRACT OF REPAIR/REPLACEMENT ACTIVITIES REQUIRED FOR CONTINUED SERVICE Code Class None Item Description None Description of Work None Date Completed None Repair/Replacement Plan Number None

McGuire MlR25 Steam Generator Tube Inspection Report Pursuant to McGuire technical specification 5.6.8 the following information is provided:

a. The scope of inspections performed on each SG Bobbin Inspection Full length bobbin probe inspection of 50% tubes. The 50% sample contained:

All tubes with previous indications, e.g., wear, DNT, PLP, PRX, etc. All tubes surrounding plugged tubes one tube deep. Periphery tubes two rows deep in the hot leg and cold leg (outer perimeter and open lane). 50% of rows 5-6/ull length. Array Inspection J 00% of periphery tubes (5 tubes in from periphery) with array probe from top of tubesheet to the first support in both hot leg (TEH to OJ H) and cold leg (TEC to OJ C). Special interest inspections were also pe,formed on selected indications. Visual Inspection Previously installed plugs Bowl cladding inspection Foreign object search and retrieval (FOSAR) of the tubesheet in all 4 steam generators.

b.

Degradation mechanisms found Degradation found included wear at support structures and presumed wear from foreign objects.

c.

Non-destructive examination techniques utilized for each degradation mechanism The bobbin probe was utilized for the detection of wear at support structures and frees pan locations and to size wear at support structures. The array probe was used to size the presumed foreign object wear.

d. Location, orientation (if linear), and measured sizes (if available) of service induced indications.

There were 337 indications of fanbar (FB) wear reported. Forty-eight (48) of these indication were newly reported. The deepest offanbar wear indication was 3J% TW. The average growth rate was -0.2 % TWIEFPY. There were nine (9) indications of lattice grid (LG) wear reported. There were no newly reported lattice grid wear indications. The deepest of lattice grid wear indication was 2J% TW. The average growth rate for lattice grid wear was -0.3%TW/EFPY. There were twenty-two (22) indications of presumed foreign object wear with no part present reported. The deepest presumed foreign object wear was 20% TW. One of these indications was newly reported, its depth was J6% TW. The complete listing for service induced indications is attached.

e.

Number of tubes plugged during the inspection outage for each degradation mechanism There were no tubes plugged in the IA, JB, JC, or JD SGs.

f.

Total number and percentage of tubes plugged to date, and the effective plugging percentage in each steam generator. Steam Generator1 IA JB JC JD Total Prior to MIR25 2 4 5 8 19 MIR25 0 0 0 0 0 Total 2 4 5 8 19 % Plugged/Effective Plugging % 0.03% 0.06% 0.08% 0.12% 0.07% 1= There are 6633 tubes per steam generator

g. The results of condition monitoring, including the results of tube pulls and in-situ testing.

The cumulative SG EFPYfor EOC-23(MJR23) was 15.80, EOC-24 (MJR24) was 17.11 and EOC-25 (MJR25) was 18.55. As of EOC-25, the McGuire steam generators had operated 17.56 EFPY since the first in-service inspection after replacement. In total, the McGuire steam generators had operated 18.55 EFPY since replacement. Condition monitoring structural and leakage integrity were met for fanbar, lattice grid and presumed foreign object wear. An NDE maximum depth call of 48.9 %TWor less for fanbar wear is sufficient to demonstrate a minimum degraded tube burst pressure of 3L1P, 4050 psi, at 0.95 probability with 50% confidence. The worst case depth call for fanbar wear observed during the inspection was an NDE depth of 31 %TW. An NDE maximum depth call of 51. 3 %TW or less for lattice grid wear is sufficient to demonstrate a minimum degraded tube burst pressure of 3L1P, 4050 psi, at 0.95 probability with 50% confidence. The worst case depth call for lattice grid wear observed during the inspection was an NDE depth of 21 %TW. An NDE maximum depth call of 51. 7%TW or less for FO wear is sufficient to demonstrate a minimum degraded tube burst pressure of 3L1P, 4050 psi, at 0.95 probability with 50% confidence. The worst case depth call for FO wear observed during the inspection was an NDE depth of 20%TW. During FOSAR, a total of 21 metal objects were found with 12 removed. All foreign objects that were not removed have a technical evaluation demonstrating that tube integrity will be met through the next scheduled inspection at MJR28. There was no wear was associated with any foreign object. No degradation was detected in the plug visual or bowl cladding inspections. No in-situ tests or tube pulls were pe,formed.

SG - A Service Induced Indications McGuire 1 1EOC25 MNS 20171001 11/27/2017 10:53:44 +----+----+---------+----+----+----+-----+----+---------+---------+---------+---------+-------+-------+----+----+----+------+------+------+--+-----+ I ROW COL VOLTS DEG IND PER CHN LOCN INCH1 INCH2 UTIL1 UTIL2 CRLEN CRWID CEG BEGT ENDT PDIA PTYPE CAL L IDXI +----+----+---------+----+----+----+-----+----+---------+---------+---------+---------+-------+-------+----+----+----+------+------+------+--+-----+ I 78 19 .43 66 PCT 13 207 TSC .80 .30 .20 01C TEC .560 ZYAXP 7 C 1511 I I I 77 20 .39 141 PCT 12 207 TSC .23 .22 .20 01C TEC .560 ZYAXP 7 C 1571 I I I 79 20 .56 134 PCT 20 203 TSC .32 .30 .20 01C TEC .560 ZYAXP 8 C 1661 I I I 81 20 .54 106 PCT 15 207 TSC 1.26 .22 .27 01C TEC .560 ZYAXP 7 C 1581 I I I 80 21 .80 62 PCT 18 207 TSC 1.30 .24 .20 01C TEC .560 ZYAXP 8 C 1671 I I I 82 21 .33 225 PCT 12 207 TSC .90 .30 .27 01C TEC .560 ZYAXP 7 C 1591 I 82 21 .14 122 PCT 8 207 TSC

1. 77

.30 .20 01C TEC .560 ZYAXP 7 C 1591 I 82 21 .26 70 PCT 10 207 TSC 2.03 .30 .27 01C TEC .560 ZYAXP 7 C 1591 I I I 3 30 .47 86 PCT 14 207 TSC 10.20 .54 .27 01C TEC .560 ZYAXP 6 C 471 I I I 98 33 .22 128 PCT 9 207 TSC .75 .35 .20 01C TEC .560 ZYAXP 6 C 2081 I 98 33 .15 113 PCT 8 207 TSC 3.35 .35 .20 01C TEC .560 ZYAXP 6 C 2081 I I I 60 47 .09 271 PCT 6 P5 FB5 -1.12 WAR TEC TEH .560 ZBAZX 13 H 361 I I I 72 53 .13 274 PCT 6 P5 FB5 1.46 WAR TEC TEH .560 ZBAZX 6 H 261 I I I 61 54 .17 92 PCT 7 P5 FB4 1.24 WAR TEC TEH .560 ZBAZX 14 H 601 I I I 108 57 .39 264 PCT 15 P5 FB5

1. 57 WAR TEC TEH

.560 ZBAZX 6 H 171 L I I 110 57 .30 96 PCT 14 P5 FB5 1.47 WAR TEC TEH .560 ZBAZX 3 H 231 I I I 81 58 .41 277 PCT 19 P5 FB4 -1. 03 WAR TEC TEH .560 ZBAZX 5 H 571 I I I 111 58 .11 255 PCT 6 P5 FB5 1.12 WAR TEC TEH .560 ZBAZX 5 H 211 I I I 84 59 .19 271 PCT 8 P5 FB5 -.67 WAR TEC TEH .560 ZBAZX 6 H 511 I I I 98 59 .43 81 PCT 16 P5 FB4 -1.63 WAR TEC TEH .560 ZBAZX 6 H 481 I I I 100 59 .21 261 PCT 9 P5 FB4 -1. 67 WAR TEC TEH .560 ZBAZX 6 H 471 I I I 45 60 .25 74 PCT 11 P5 FB4 1.29 WAR TEC TEH .560 ZBAZX 14 H 931 I I I 49 60 .12 280 PCT 7 P5 03H -1.56 WAR TEC TEH .560 ZBAZX 13 H 1031 I I I 79 60 .23 86 PCT 12 P5 FB4 -. 76 WAR TEC TEH .560 ZBAZX 5 H 681 I I I 81 60 .40 92 PCT 19 P5 FB4 -.80 WAR TEC TEH .. 560 ZBAZX 5 H 691 I I I 83 60 .35 80 PCT 14 P5 FB4 -. 72 WAR TEC TEH .560 ZBAZX 6 H 551 I I +----+----+---------+----+----+----+-----+----+---------+---------+---------+---------+-------+-------+----+----+----+------+------+------+--+-----+ I ROW COL VOLTS DEG IND PER CHN LOCN INCH1 INCH2 UTIL1 UTIL2 CRLEN CRWID CEG BEGT ENDT PDIA PTYPE CAL L !DX I +----+----+---------+----+----+----+-----+----+---------+---------+---------+---------+-------+-------+----+----+----+------+------+------+--+-----+ 1 ST Max

SG - A Service Induced Indications McGuire 1 1EOC25 MNS 20171001 11/27/2017 10:53:44 +----+----+---------+----+----+----+-----+----+---------+---------+---------+---------+-------+-------+----+----+----+------+------+------+--+-----+ I ROW COL VOLTS DEG IND PER CHN LOCN INCHl INCH2 UTILl UTIL2 CRLEN CRWID CEG BEGT ENDT PDIA PTYPE CAL L IDXI +----+----+---------+----+----+----+-----+----+---------+---------+---------+---------+-------+-------+----+----+----+------+------+------+--+-----+ 95 60 . 37 105 PCT 18 PS FB4 -. 87 WAR TEC TEH . 560 ZBAZX 5 H 701 95 60 . 21 113 PCT 11 PS FB5 -1. 49 WAR TEC TEH . 560 ZBAZX 5 H 701 94 79 79 113 70 72 112 55 95 95 97 99 99 99 94 100 112 112 112 112 105 109 111 111 111 111 115 86 61 62 62 62 63 63 63 64 64 64 64 64 64 64 65 65 65 65 65 65 66 66 66 66 66 66 66 67 .33 .23 .21 .32 90 90 305 81 PCT PCT PCT PCT .14 278 PCT .14 301 PCT . 24 113 PCT .13 .17 .17 65 PCT 108 PCT 259 PCT .16 265 PCT .28 .45 .27 .28 81 PCT 85 PCT 82 PCT 80 PCT .35 279 PCT .15 .29 .36 .28 .25 284 113 98 287 PCT PCT PCT PCT 286 PCT .18 261 PCT .24 .34 .49 .22 .10 .21 92 111 100 84 PCT PCT PCT PCT 94 PCT 104 PCT 13 12 11 16 6 8 12 6 9 9 9 11 17 11 11 14 8 15 17 14 13 8 12 17 22 12 6 11 PS FB5 PS FB4 PS FB4 PS FB7 PS FB3 PS FB5 PS FB3 PS FB3 PS FB3 PS FB5 PS FB2 PS FB3 PS FB4 PS FB5 PS FB5 PS FB5 PS FB2 PS FB4 PS FB5 PS FB6 PS FB4 PS FB4 PS FB4 PS FB4 PS FB6 PS FB7 PS FB4 PS FB4 -1.49 -.80 .88 .65 .55 1.26 1.24 .86 -. 78 -.66 .61 -. 96 -1.07 -1.26 -1.18 .72 .66 1.49 .84 1.39 -.89 -.85 -. 78 1.21 -1.12 -1.13 .85 1.50 WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR TEC TEH TEC TEH TEC TEH TEC TEH TEC TEH TEC TEH TEC TEH TEC TEH TEC TEH TEC TEH TEC TEH TEC TEH TEC TEH TEC TEH TEC TEH TEC TEH TEC TEC TEC TEC TEH TEH TEH TEH TEC TEH TEC TEH TEC TEC TEC TEC TEH TEH TEH TEH TEC TEH TEC TEH .560 ZBAZX .560 ZBAZX .560 ZBAZX .560 ZBAZX .560 ZBAZX .560 ZBAZX .560 ZBAZX .560 ZBAZX .560 ZBAZX .560 ZBAZX .560 ZBAZX .560 ZBAZX .560 ZBAZX .560 ZBAZX .560 ZBAZX .560 ZBAZX .560 ZBAZX .560 ZBAZX .560 ZBAZX .560 ZBAZX .560 ZBAZX .560 .560 .560 .560 .560 ZBAZX ZBAZX ZBAZX ZBAZX ZBAZX .560 ZBAZX .560 ZBAZX 6 H 5 H 5 H 5 H 6 H 5 H 3 H I 601 I 821 821 I 151 I 771 I 921 I 201 I 14 H 1131 5 H 5 H 5 H 6 H 6 H 6 H 6 H 6 H 5 H 5 H 5 H 5 H I 931 931 I 941 I 781 781 781 I 861 I 851 I 961 961 961 961 I 5 H 1071 6 H 5 H 5 H 5 H 5 H I 931 I 1081 1081 1081 1081 I 5 H 1091 I 5 H 1181 I +----+----+---------+----+----+----+-----+----+---------+---------+---------+---------+-------+-------+----+----+----+------+------+------+--+-----+ I ROW COL VOLTS DEG IND PER CHN LOCN INCHl INCH2 UTILl UTIL2 CRLEN CRWID CEG BEGT ENDT PDIA PTYPE CAL L !DX I +----+----+---------+----+----+----+-----+----+---------+---------+---------+---------+-------+-------+----+----+----+------+------+------+--+-----+ 2 ST Max

SG - A Service Induced Indications McGuire 1 1EOC25 MNS 20171001 11/27/2017 10:53:44 +----+----+---------+----+----+----+-----+----+---------+---------+---------+---------+-------+-------+----+----+----+------+------+------+--+-----+ I ROW COL VOLTS DEG IND PER CHN LOCN INCH! INCH2 UTILl UTIL2 CRLEN CRWID CEG BEGT ENDT PDIA PTYPE CAL L IDXI +----+----+---------+----+----+----+-----+----+---------+---------+---------+---------+-------+-------+----+----+----+------+------+------+--+-----+ 102 67 .19 94 PCT 10 PS FB3 .73 WAR TEC TEH .560 ZBAZX 5 H 1141 102 67 .32 279 PCT 16 PS FB5 1.36 WAR TEC TEH .560 ZBAZX 5 H 1141 102 67 .21 277 PCT 11 PS FB6 1.27 WAR TEC TEH .560 ZBAZX 5 H 1141 I 106 67 .36 100 PCT 14 PS FB4 -1.32 WAR TEC TEH .560 ZBAZX 6 H 1021 106 67 .28 96 PCT 11 PS FB5 -1.43 WAR TEC TEH .560 ZBAZX 6 H 1021 I 110 67 .30 279 PCT 15 PS FB5 -1.58 WAR TEC TEH .560 ZBAZX 5 H 1121 I 114 67 .29 97 PCT 12 PS FB3 -. 72 WAR TEC TEH .560 ZBAZX 6 H 1001 114 67 .74 275 PCT 24 PS FB4 -1. 70 WAR TEC TEH .560 ZBAZX 6 H 100/ 114 67 .31 277 PCT 12 PS FB6 1.26 WAR TEC TEH .560 ZBAZX 6 H 100/ I 116 67 .23 92 PCT 9 PS FB3 -.94 WAR TEC TEH .560 ZBAZX 6 H 991 I 37 68 .27 259 PCT 11 PS FB5 -.88 WAR TEC TEH .560 ZBAZX 16 H 191 I 43 68 .40 78 PCT 15 PS FB5 -. 90 WAR TEC TEH .560 ZBAZX 16 H 20/ I 77 68 .23 99 PCT 12 PS FB4 1.08 WAR TEC TEH .560 ZBAZX 5 H 1231 I 97 68 .15 107 PCT 8 PS FB6 .99 WAR TEC TEH .560 ZBAZX 5 H 124/ I 103 68 .24 284 PCT 13 PS FB3 -1.13 WAR TEC TEH .560 ZBAZX 5 H 1251 103 68 .31 87 PCT 16 PS FB4 -.99 WAR TEC TEH .560 ZBAZX 5 H 1251 I 111 68 .19 106 PCT 10 PS FB4 .65 WAR TEC TEH .560 ZBAZX 5 H 1261 I 113 68 .37 99 PCT 18 PS FB4 -. 53 WAR TEC TEH .560 ZBAZX 5 H 1271 113 68 .24 276 PCT 13 PS FB4 .80 WAR TEC TEH

560 ZBAZX 5

H 127/ 113 68 .29 286 PCT 15 PS FB5 -. 71 WAR TEC TEH .560 ZBAZX 5 H 1271 I 90 69 .43 100 PCT 20 PS FB4

1. 09 WAR TEC TEH

.560 ZBAZX 5 H 134/ I 92 69 .32 82 PCT 13 PS FB4 .92 WAR TEC TEH

  • .560 ZBAZX 6

H 120/ I 104 69 .18 119 PCT 10 PS FB4

1. 33 WAR TEC TEH

.560 ZBAZX 5 H 1311 I 106 69 .45 101 PCT 20 PS FB5 1.12 WAR TEC TEH .560 ZBAZX 5 H 1301 106 69 .31 102 PCT 15 PS FB6 1.15 WAR TEC TEH .560 ZBAZX 5 H 1301 I 108 69 .31 88 PCT 12 PS FB4 1.40 WAR TEC TEH .560 ZBAZX 6 H 116/ I 112 69 .22 291 PCT 12 PS FB2 .68 WAR TEC TEH .560 ZBAZX 5 H 129/ 112 69 .24 102 PCT 13 PS FB3 1.04 WAR TEC TEH .560 ZBAZX 5 H 129/ 112 69 .17 91 PCT 10 PS FB4 1.40 WAR TEC TEH .560 ZBAZX 5 H 1291 112 69 .17 275 PCT 10 PS FB6 1.56 WAR TEC TEH .560 ZBAZX 5 H 1291 I 95 70 .31 88 PCT 16 PS FB4 -. 74 WAR TEC TEH .560 ZBAZX 5 H 1401 +----+----+---------+----+----+----+-----+----+---------+---------+---------+---------+-------+-------+----+----+----+------+------+------+--+-----+ I ROW COL VOLTS DEG IND PER CHN LOCN INCH! INCH2 UTILl UTIL2 CRLEN CRWID CEG BEGT ENDT PDIA PTYPE CAL L !DX/ +----+----+---------+----+----+----+-----+----+---------+---------+---------+---------+-------+-------+----+----+----+------+------+------+--+-----+ 3 ST Max

SG - A Service Induced Indications McGuire 1 1EOC25 MNS 20171001 11/27/2017 10:53:44 +----+----+---------+----+----+----+-----+----+---------+---------+---------+---------+-------+-------+----+----+----+------+------+------+--+-----+ I ROW COL VOLTS DEG IND PER CHN LOCN INCH! INCH2 UTILl UTIL2 CRLEN CRWID CEG BEGT ENDT PDIA PTYPE CAL L IDXI +----+----+---------+----+----+----+-----+----+---------+---------+---------+---------+-------+-------+----+----+----+------+------+------+--+-----+ 95 70 .23 280 PCT 12 PS FB5 -1.47 WAR TEC TEH .560 ZBAZX 5 H 1401 109 58 74 74 76 114 69 85 93 93 109 109 117 70 82 86 86 88 88 94 94 104 104 104 112 77 85 109 70 71 71 71 71 71 72 72 72 72 72 72 72 73 73 73 73 73 73 73 73 73 73 73 73 74 74 74 .12 .39 .32 .30 .24 .34 76 PCT 84 PCT 98 PCT 96 PCT 97 PCT 96 PCT .18 252 PCT .22 109 PCT .43 285 PCT .20 262 PCT .30 .40 .63 .26 .23 101 PCT 106 PCT 90 PCT 91 PCT 246 PCT .23 236 .34 250 PCT PCT .65 90 PCT .30 276 PCT .44 79 PCT .30 275 PCT .19 239 PCT .17 228 PCT .20 238 PCT .23 76 PCT .31 241 PCT .38 69 PCT .33 62 PCT 7 15 16 15 10 16 10 12 20 11 15 19 16 11 13 10 14 22 12 17 12 11 10 11 12 16 18 17 PS FB4 PS FB6 PS FB4 PS FB5 PS FB4 PS FB4 PS FB4 PS FB5 PS FB5 PS FB6 PS FB4 PS FB5 207 TSC PS FB4 PS FB7 PS FB4 PS FB5 PS FB5 PS FB7 PS PS FB5 FB7 PS FB5 PS FB6 PS FB7 PS FB4 PS FB5 PS FB5 PS FB4 .89 .73 1.49 .78 1.44

1. 57

-. 53 .00 .12 .02 -.15 -.02 .13 1.40 1.81 .48

1. 73 1.69
1. 77 1.19
1. 70
1. 55

.29 1.58 1.02 -1.60 -1.69 1.52 WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR .20 .20 TEC TEH TEC TEH TEC TEH TEC TEH TEC TEH TEC TEH TEC TEH TEC TEH TEC TEH TEC TEH TEC TEH TEC TEH 01C TEC TEC TEH TEC TEH TEC TEH TEC TEH TEC TEH TEC TEH TEC TEH TEC TEH TEC TEH TEC TEH TEC TEH TEC TEH TEC TEH TEC TEH TEC TEH .560 ZBAZX .560 ZBAZX .560 ZBAZX .560 ZBAZX .560 ZBAZX .560 ZBAZX .560 ZBAZX .560 ZBAZX .560 ZBAZX .560 ZBAZX .560 ZBAZX .560 ZBAZX .560 ZYAXP .560 ZBAZX .560 ZBAZX .560 ZBAZX .560 ZBAZX .560 ZBAZX .560 ZBAZX .560 ZBAZX .560 ZBAZX .560 ZBAZX .560 ZBAZX .560 ZBAZX .560 ZBAZX .560 ZBAZX .560 ZBAZX .560 ZBAZX I 5 H 1411 16 H I 341 I 5 H 1521 5 H 1521 I 6 H 1381 I 5 H 1421 15 H I 361 I 5 H 1551 I 5 H 1561 5 H 1561 I 5 H 1571 5 H 1571 I 6 C 3261 18 H 17 H 18 H 18 H 18 H 18 H 18 H 18 H 17 H 17 H 17 H 17 H 17 H 17 H 17 H I 261 I 201 I 221 221 I 211 211 I 201 201 I 151 151 151 I 131 I 231 I 241 I 251 +----+----+---------+----+----+----+-----+----+---------+---------+---------+---------+-------+-------+----+----+----+------+------+------+--+-----+ I ROW COL VOLTS DEG IND PER CHN LOCN INCH! INCH2 UTILl UTIL2 CRLEN CRWID CEG BEGT ENDT PDIA PTYPE CAL L IDXI +----+----+---------+----+----+----+-----+----+---------+---------+---------+---------+-------+-------+----+----+----+------+------+------+--+-----+ 4 ST Max

SG - A Service Induced Indications McGuire 1 1EOC25 MNS 20171001 11/27/2017 10:53:44 +----+----+---------+----+----+----+-----+----+---------+---------+---------+---------+-------+-------+----+----+----+------+------+------+--+-----+ I ROW COL VOLTS DEG IND PER CHN LOCN INCH! INCH2 UTILl UTIL2 CRLEN CRWID CEG BEGT ENDT PDIA PTYPE CAL L IDXI +----+----+---------+----+----+----+-----+----+---------+---------+---------+---------+-------+-------+----+----+----+------+------+------+--+-----+ I 111 74 .10 24 PCT 6 P5 FB4 1.49 WAR TEC TEH .560 ZBAZX 17 H 261 I 72 75 .40 236 PCT 19 P5 FB4 1.36 WAR TEC TEH .560 ZBAZX 17 H 391 I 96 75 .36 54 PCT 18 P5 FB3 -.89 WAR TEC TEH .560 ZBAZX 17 H 331 96 75 .19 231 PCT 11 P5 FB5 -.89 WAR TEC TEH .560 ZBAZX 17 H 331 96 75 .51 72 PCT 23 P5 FB5 1.37 WAR TEC TEH .560 ZBAZX 17 H 331 I 99 76 .48 250 PCT 22 P5 FB4 .66 WAR TEC TEH .560 ZBAZX 17 H 401 I 113 76 .47 69 PCT 22 P5 FB4 -1.09 WAR TEC TEH .560 ZBAZX 17 H 411 113 76 .29 73 PCT 15 P5 FB6 .50 WAR TEC TEH .560 ZBAZX 17 H 411 I 94 77 .16 97 PCT 7 P5 FB4 .73 WAR TEC TEH .560 ZBAZX 18 H 491 94 77 .24 279 PCT 10 P5 FB5 1.19 WAR TEC TEH .560 ZBAZX 18 H 491 I 102 77 .47 85 PCT 18 P5 FB4 1.26 WAR TEC TEH .560 ZBAZX 18 H 471 102 77 .32 269 PCT 13 P5 FB5 1.56 WAR TEC TEH .560 ZBAZX 18 H 471 I 104 77 .14 221 PCT 8 P5 FB7 1.21 war TEC TEH .560 ZBAZX 17 H 451 I 106 77 .32 230 PCT 16 P5 FB4 .84 WAR TEC TEH .560 ZBAZX 17 H 441 106 77 .20 46 PCT 11 P5 FB5 -1.11 WAR TEC TEH .560 ZBAZX 17 H 441 I 47 78 .31 282 PCT 12 P5 FB5 -1.06 WAR TEC TEH .560 ZBAZX 20 H 2291 I 78 79 .28 78 PCT 12 P5 FB5

1. 71 WAR TEC TEH

.560 ZBAZX 18 H 681 I 100 79 .43 92 PCT 16 P5 FB4 1.09 WAR TEC TEH .560 ZBAZX 18 H 631 100 79 .34 271 PCT 14 P5 FB5

1. 55 WAR TEC TEH

.560 ZBAZX 18 H 631 I 113 80 .38 52 PCT 19 P5 FB3 -. 75 WAR TEC TEH .560 ZBAZX 17 H 661 113 80 .30 235 PCT 16 P5 FB4 -1.38 WAR TEC TEH .560 ZBAZX 17 H 661 113 80 .30 71 PCT 16 P5 FB5 -1. 28 WAR TEC TEH .560 ZBAZX 17 H 661 113 80 .20 250 PCT 11 P5 FB6 -. 92 WAR TEC TEH .560 ZBAZX 17 H 661 I 85 82 .42 73 PCT 20 P5 FB3 -1. 00 WAR TEC TEH .560 ZBAZX 17 H 671 85 82 .25 64 PCT 14 P5 FB5 -.83 WAR TEC TEH .560 ZBAZX 17 H 671 I 105 82 .26 55 PCT 14 P5 FB4 -1.62 WAR TEC TEH .560 ZBAZX 17 H 681 I 60 83 .16 108 PCT 9 P5 FB4 -.96 WAR TEC TEH .560 ZBAZX 19 H 1891 I 94 83 .20 95 PCT 9 P5 FB4 1.25 WAR TEC TEH .560 ZBAZX 18 H 831 I 114 83 .22 42 PCT 12 P5 FB3 -. 93 WAR TEC TEH .560 ZBAZX 17 H 691 I 53 84 .24 67 PCT 9 P5 FB5 .85 WAR TEC TEH .560 ZBAZX 20 H 2481 +----+----+---------+----+----+----+-----+----+---------+---------+---------+---------+-------+-------+----+----+----+------+------+------+--+-----+ I ROW COL VOLTS DEG IND PER CHN LOCN INCHl INCH2 UTILl UTIL2 CRLEN CRWID CEG BEGT ENDT PDIA PTYPE CAL L IDXI +----+----+---------+----+----+----+-----+----+---------+---------+---------+---------+-------+-------+----+----+----+------+------+------+--+-----+ 5 ST Max

SG - A Service Induced Indications McGuire 1 1EOC25 MNS 20171001 11/27/2017 10:53:44 +----+----+---------+----+----+----+-----+----+---------+---------+---------+---------+-------+-------+----+----+----+------+------+------+--+-----+ I ROW COL VOLTS DEG IND PER CHN LOCN INCHl INCH2 UTILl UTIL2 CRLEN CRWID CEG BEGT ENDT PDIA PTYPE CAL L IDXI +----+----+---------+----+----+----+-----+----+---------+---------+---------+---------+-------+-------+----+----+----+------+------+------+--+-----+ I 77 84 .12 276 PCT 7 P5 FB4 -1. 23 WAR TEC TEH . 560 ZBAZX 17 H 81 I I 81 84 . 27 96 PCT 11 P5 FB5 -. 71 WAR TEC TEH . 560 ZBAZX 18 H 90 I I 85 84 . 23 234 PCT 13 P5 FB4 -1. 28 WAR TEC TEH . 560 ZBAZX 17 H 82 I 85 84 . 29 65 PCT 15 P5 FB5 -. 69 WAR TEC TEH . 560 ZBAZX 17 H 82 I I 93 84 . 24 63 PCT 13 P5 FB4 -. 95 WAR TEC TEH . 560 ZBAZX 17 H 831 I 101 84 . 36 63 PCT 18 P5 FB5 -. 63 WAR TEC TEH . 560 ZBAZX 17 H 841 I 50 87 .19 83 PCT 10 P5 FB6 . 98 WAR TEC TEH . 560 ZBAZX 21 H 121 I 66 87 . 09 267 PCT 6 P5 FB3 . 83 WAR TEC TEH . 560 ZBAZX 21 H 81 I 35 88 .16 268 PCT 7 P5 FB5 -. 91 WAR TEC TEH . 560 ZBAZX 22 H 161 I 55 88 .12 288 PCT 5 P5 FB3 -1. 95 WAR TEC TEH . 560 ZBAZX 22 H 171 I 56 89 .14 101 PCT 6 P5 FB4 -. 85 WAR TEC TEH . 560 ZBAZX 22 H 201 I 60 89 . 22 88 PCT 12 P5 FB5

1. 64 WAR TEC TEH

. 560 ZBAZX 21 H 191 I 50 91 .14 85 PCT 8 P5 FB2 . 78 WAR TEC TEH . 560 ZBAZX 21 H 32 I I 80 91 . 26 54 PCT 10 P5 FB4 -1. 03 WAR TEC TEH . 560 ZBAZX 20 H 39 I I 50 93 .14 83 PCT 8 P5 FB4 . 79 WAR TEC TEH . 560 ZBAZX 21 H 421 I 50 95 .11 258 PCT 7 P5 FB4 1.18 WAR TEC TEH . 560 ZBAZX 21 H 521 I 108 95 . 20 89 PCT 11 P5 FB6 2.18 WAR TEC TEH . 560 ZBAZX 19 H 461 I 64 97 .12 54 PCT 7 P5 FB4 -1. 07 WAR TEC TEH . 560 ZBAZX 21 H 571 I 58 101 .16 71 PCT 9 P5 FB4 -1. 24 WAR TEC TEH . 560 ZBAZX 21 H 771 I 72 101 .10 127 PCT 6 P5 FB4 -1. 27 WAR TEC TEH . 560 ZBAZX 19 H 751 I 74 103 .13 35 PCT 5 P5 FB5 . 60 WAR TEC TEH . 560 ZBAZX 20 H 109 I I 63 110 .11 300 PCT 5 P5 FB4

1. 03 WAR TEC TEH

. 560 ZBAZX 22 H 1251 I 86 119 . 94 271 PCT 19 78 01C -1. 73 . 22 .14 01C TEC . 560 ZYAXP 4 C 2261 I 88 119 .94 76 PCT 19 207 01C -2.86 .32 .27 01C TEC .560 ZYAXP 3 C 2301 I 49 126 .12 260 PCT 5 P5 FB4

1. 06 WAR TEC TEH

. 560 ZBAZX 22 H 2111 +----+----+---------+----+----+----+-----+----+---------+---------+---------+---------+-------+-------+----+----+----+------+------+------+--+-----+ I ROW COL VOLTS DEG IND PER CHN LOCN INCHl INCH2 UTILl UTIL2 CRLEN CRWID CEG BEGT ENDT PDIA PTYPE CAL L IDXI +----+----+---------+----+----+----+-----+----+---------+---------+---------+---------+-------+-------+----+----+----+------+------+------+--+-----+ Tubes: 124 Records: 171 6 ST Max

SG - B Service Induced Indications McGuire 1 1EOC25 MNS 20171001 11/27/2017 12:36:15 +----+----+---------+----+----+----+-----+----+---------+---------+---------+---------+-------+-------+----+----+----+------+------+------+--+-----+ I ROW COL VOLTS DEG IND PER CHN LOCN INCHl INCH2 UTILl UTIL2 CRLEN CRWID CEG BEGT ENDT PDIA PTYPE CAL L IDXI +----+----+---------+----+----+----+-----+----+---------+---------+---------+---------+-------+-------+----+----+----+------+------+------+--+-----+ 45 18 .27 266 PCT 14 PS FB4 .88 WAR TEH TEC .560 ZBAZX 26 C 63/ I 88 31 .18 284 PCT 9 PS 08H .30 WAR TEH TEC .560 ZBAZX 23 C 1731 I 96 35 .42 94 PCT 13 166 TSH 3.42 .20 .20 01H TEH .560 ZYAXP 4 H 1421 I 100 35 .10 230 PCT 6 207 TSH 2.15 .27 .14 01H TEH .560 ZYAXP 3 H 1881 I 97 36 .16 252 PCT 8 207 TSH 3.31 .27 .14 01H TEH .560 ZYAXP 3 H 1911 I 62 43 .42 281 PCT 21 PS 07H -1.62 WAR TEH TEC .560 ZBAZX 17 C 541 I 68 51 .29 93 PCT 13 PS FB5 -.97 WAR TEH TEC .560 ZBAZX 24 C 1181 I 45 52 .13 270 PCT 7 PS 06H .50 WAR TEH TEC .560 ZBAZX 24 C 1171 45 52 .12 102 PCT 6 PS FB4 -1.02 WAR TEH TEC .560 ZBAZX 24 C 1171 I 61 52 .17 81 PCT 9 PS FB5 1.64 WAR TEH TEC .560 ZBAZX 25 C 1171 I 46 57 .17 62 PCT 8 PS FB3 -2.06 WAR TEH TEC .560 ZBAZX 24 C 961 I 77 64 .29 263 PCT 16 PS FB4 -1.12 WAR TEH TEC .560 ZBAZX 19 C 711 I 81 64 .43 96 PCT 18 PS FB4 -1.21 WAR TEH TEC .560 ZBAZX 21 C 841 I 68 65 .25 222 PCT 12 PS FB4 -. 78 WAR TEH TEC .560 ZBAZX 24 C 561 I 82 65 .19 89 PCT 12 PS FB5 -1.61 WAR TEH TEC .560 ZBAZX 19 C 67/ I 94 65 .11 98 PCT 5 PS FB4 -1.09 WAR TEH TEC .560 ZBAZX 21 C 771 I 77 66 .23 91 PCT 13 PS FB4 -1.25 WAR TEH TEC .560 ZBAZX 19 C 60/ I 81 66 .29 88 PCT 13 PS FB5 1.34 WAR TEH TEC .560 ZBAZX 21 C 72/ I 74 67 .16 255 PCT 10 PS FB4 1.43 WAR TEH TEC .560 ZBAZX 19 C 581 I 76 67 .21 244 PCT 10 PS FB4 1.46 WAR TEH TEC .560 ZBAZX 21 C 701 I 80 67 .21 286 PCT 12 PS FB4 1.41 WAR TEH TEC .560 ZBAZX 19 C 571 I 82 67 .17 244 PCT 10 PS FB4 1.71 WAR TEH TEC .560 ZBAZX 19 C 561 I 94 67 .24 68 PCT 11 PS FB4 1.49 WAR TEH TEC .560 ZBAZX 21 C 651 I 91 68 .27 94 PCT 15 PS FB5 -1.18 WAR TEH TEC .560 ZBAZX 19 C 481 I 97 68 .21 93 PCT 13 PS FB5 -1.13 WAR TEH TEC .560 ZBAZX 19 C 491 I +----+----+---------+----+----+----+-----+----+---------+---------+---------+---------+-------+-------+----+----+----+------+------+------+--+-----+ I ROW COL VOLTS DEG IND PER CHN LOCN INCHl INCH2 UTILl UTIL2 CRLEN CRWID CEG BEGT ENDT PDIA PTYPE CAL L !DX/ +----+----+---------+----+----+----+-----+----+---------+---------+---------+---------+-------+-------+----+----+----+------+------+------+--+-----+ 1 ST Max

SG - B Service Induced Indications McGuire 1 1EOC25 MNS 20171001 11/27/2017 12:36:15 +----+----+---------+----+----+----+-----+----+---------+---------+---------+---------+-------+-------+----+----+----+------+------+------+--+-----+ I ROW COL VOLTS DEG IND PER CHN LOCN INCHl INCH2 UTILl UTIL2 CRLEN CRWID CEG BEGT ENDT PDIA PTYPE CAL L IDXI +----+----+---------+----+----+----+-----+----+---------+---------+---------+---------+-------+-------+----+----+----+------+------+------+--+-----+ 86 69 . 20 85 PCT 9 P5 FB6 1.15 WAR TEH TEC . 560 ZBAZX 21 C 561 102 89 78 88 5 89 95 97 97 99 64 94 94 102 106 116 105 94 96 108 110 114 114 114 57 84 69 70 71 71 72 72 72 72 72 72 73 73 73 73 73 73 74 75 75 75 75 75 75 75 76 77 .20 236 PCT .21 77 PCT .39 73 PCT .20 80 PCT .13 249 PCT .58 94 PCT .43 256 PCT .75 263 PCT .70 267 PCT .27 .18 .16 .27 87 PCT 98 PCT 94 PCT 279 PCT .14 109 PCT .13 274 PCT .18 313 PCT .27 106 PCT .58 291 PCT .64 95 PCT .19 284 PCT .20 263 PCT . 28 110 PCT .54 286 PCT .26 99 PCT .91 101 PCT .21 306 PCT 9 13 16 12 8 26 21 26 25 12 9 8 13 7 7 9 13 23 25 10 10 13 22 13 31 11 P5 FB6 P5 FB5 P5 FB5 P5 FB5 P5 07H P5 FB5 P5 FB5 P5 P5 P5 FB4 FB5 FB5 P5 FB5 P5 P5 P5 P5 P5 FB2 FB4 FB4 FB4 FB4 P5 FB5 P5 FB5 P5 FB5 P5 FB4 P5 FB6 P5 FB3 P5 FB5 P5 FB7 P5 FB5 P5 FB4 1.28 1.28 -. 78 -1.11 1.43 .00 -.20 .07 .24 .02 1.27 -1.82 -1. 57 -1.17 1.70 1.69 .89 -1.37 -1.29 -. 72 .76 1.21 -1. 25 1.39 1.48 -.99 WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR WAR TEH TEC TEH TEC TEH TEC TEH TEC 09C TEH TEH TEC TEH TEC TEH TEC TEH TEC TEH TEC TEH TEC TEH TEC TEH TEC TEH TEC TEH TEC TEH TEC TEH TEC TEH TEC TEH TEC TEH TEC TEH TEC TEH TEC TEH TEC TEH TEC TEH TEC TEH TEC .560 ZBAZX .560 ZBAZX .560 .560 .540 .560 .560 .560 .560 ZBAZX ZBAZX ZBAUC ZBAZX ZBAZX ZBAZX ZBAZX .560 ZBAZX .560 .560 .560 ZBAZX ZBAZX ZBAZX .560 ZBAZX .560 ZBAZX .560 ZBAZX .560 ZBAZX .560 ZBAZX .560 ZBAZX .560 ZBAZX .560 ZBAZX .560 ZBAZX .560 ZBAZX .560 ZBAZX .560 ZBAZX .560 ZBAZX 21 C 19 C 21 C 19 C 16 H 19 C 19 C 21 21 C C 21 C 38 C I 521 I 371 I 451 I 301 I 131 I 351 I 341 I 471 471 I 461 I 341 I 701 701 I 671 I 101 I 631 I 241 I 29 C 110 I 29 C 29 C 29 C 28 C 29 C 28 C 28 C I 321 I 29 C 1071 28 C 29 C 29 C 29 C 38 C 30 C I 261 I 1061 1061 1061 I 691 I 181 +----+----+---------+----+----+----+-----+----+---------+---------+---------+---------+-------+-------+----+----+----+------+------+------+--+-----+ I ROW COL VOLTS DEG IND PER CHN LOCN INCH! INCH2 UTILl UTIL2 CRLEN CRWID CEG BEGT ENDT PDIA PTYPE CAL L IDXI +----+----+---------+----+----+----+-----+----+---------+---------+---------+---------+-------+-------+----+----+----+------+------+------+--+-----+ 2 ST Max

SG - B Service Induced Indications McGuire 1 1EOC25 MNS 20171001 11/27/2017 12:36:15 +----+----+---------+----+----+----+-----+----+---------+---------+---------+---------+-------+-------+----+----+----+------+------+------+--+-----+ I ROW COL VOLTS DEG IND PER CHN LOCN INCHl INCH2 UTILl UTIL2 CRLEN CRWID CEG BEGT ENDT PDIA PTYPE CAL L IDXI +----+----+---------+----+----+----+-----+----+---------+---------+---------+---------+-------+-------+----+----+----+------+------+------+--+-----+ I 92 77 .19 307 PCT 10 P5 F84 -. 96 WAR TEH TEC .560 ZBAZX 30 C 161 92 77 .48 298 PCT 21 P5 FB5 -1.27 WAR TEH TEC .560 Z8AZX 30 C 161 I 94 77 .40 317 PCT 18 P5 F85 -1.15 WAR TEH TEC .560 ZBAZX 30 C 151 I 106 77 .32 85 PCT 15 P5 FB5 -1.20 WAR TEH TEC .560 Z8AZX 31 C 91 I 112 77 .53 96 PCT 21 P5 F84 -1.10 WAR TEH TEC .560 Z8AZX 31 C 81 112 77 .19 236 PCT 10 P5 F85 .80 WAR TEH TEC .560 Z8AZX 31 C 81 I 51 78 .17 289 PCT 9 P5 FB4 -.99 WAR TEH TEC .560 Z8AZX 40 C 181 I 89 78 .42 296 PCT 19 P5 F84 -1.03 WAR TEH TEC .560 Z8AZX 30 C 331 89 78 .19 135 PCT 10 P5 F84 1.06 WAR TEH TEC .560 Z8AZX 30 C 331 I 101 78 .22 302 PCT 11 P5 F84 1.00 WAR TEH TEC .560 Z8AZX 30 C 361 I 111 78 .29 269 PCT 14 P5 F85 -1.54 WAR TEH TEC .560 ZBAZX 28 C 251 I 76 79 .22 75 PCT 11 P5 F84 -1.17 WAR TEH TEC .560 Z8AZX 31 C 271 I 78 79 .31 110 PCT 15 P5 F85 1.46 WAR TEH TEC .560 Z8AZX 30 C 301 I 92 79 .19 85 PCT 10 P5 F85 -1. 31 WAR TEH TEC .560 Z8AZX 31 C 261 I 81 80 .18 78 PCT 9 P5 F82 -1. 92 WAR TEH TEC .560 ZBAZX 30 C 421 I 95 80 .24 123 PCT 12 P5 F84 1.20 WAR TEH TEC .560 Z8AZX 30 C 431 I 49 82 .22 292 PCT 11 P5 F85 .93 WAR TEH TEC .560 ZBAZX 38 C 941 I 86 83 .21 75 PCT 11 P5 FB4 -1.58 WAR TEH TEC .560 Z8AZX 32 C 271 I 110 83 .17 67 PCT 10 P5 FB4

1. 20 WAR TEH TEC

.560 Z8AZX 32 C 211 I 92 87 .28 104 PCT 13 P5 F84 1.16 WAR TEH TEC .560 ZBAZX 33 C 541 I 108 87 .12 296 PCT 6 P5 F84 -.63 WAR TEH TEC .560 Z8AZX 33 C 581 I 39 88 .07 96 PCT 4 P5 FB4 -1.00 WAR TEH TEC .560 Z8AZX 38 C 1181 I 65 88 .28 277 PCT 14 P5 F84 1.44 WAR TEH TEC .560 Z8AZX 38 C 271 I 106 89 .22 71 PCT 10 P5 FB5 -1.15 WAR TEH TEC .560 Z8AZX 33 C 651 +----+----+---------+----+----+----+-----+----+---------+---------+---------+---------+-------+-------+----+----+----+------+------+------+--+-----+ I ROW COL VOLTS DEG IND PER CHN LOCN INCHl INCH2 UTILl UTIL2 CRLEN CRWID CEG 8EGT ENDT PDIA PTYPE CAL L IDXI +----+----+---------+----+----+----+-----+----+---------+---------+---------+---------+-------+-------+----+----+----+------+------+------+--+-----+ 3 Tubes: 68 Records: 76 ST Max

SG - C Service Induced Indications McGuire 1 1EOC25 MNS 20171001 11/27/2017 12:46:26 +----+----+---------+----+----+----+-----+----+---------+---------+---------+---------+-------+-------+----+----+----+------+------+------+--+-----+ I ROW COL VOLTS DEG IND PER CHN LOCN INCH! INCH2 UTIL! UTIL2 CRLEN CRWID CEG BEGT ENDT PDIA PTYPE CAL L IDXI +----+----+---------+----+----+----+-----+----+---------+---------+---------+---------+-------+-------+----+----+----+------+------+------+--+-----+ I 68 53 .18 257 PCT 8 P5 FB4 -1. 61 WAR TEC TEH .560 ZBAZX 15 H 1921 I I I 75 54 .24 283 PCT 10 P5 FB4 -1.31 WAR TEC TEH .560 ZBAZX 12 H 891 I I I 95 54 .36 214 PCT 13 P5 FB4 1.20 WAR TEC TEH .560 ZBAZX 11 H 701 I I I 116 57 .18 74 PCT 9 207 TSC 12.79 .14 .14 01C TEC .560 ZYAXP 4 C 191 I 116 57 .69 99 PCT 17 207 TSC 13.71 .20 .20 01C TEC .560 ZYAXP 4 C 191 I 116 57 .50 91 PCT 14 207 TSC 14.15 .16 .25 01C TEC .560 ZYAXP 4 C 191 I I I 63 58 .63 73 PCT 22 P5 FB5 1.07 WAR TEC TEH .560 ZBAZX 18 H 181 I I I 70 59 .28 54 PCT 11 P5 FB5 -1. 35 WAR TEC TEH .560 ZBAZX 11 H 371 I I I 82 59 .25 94 PCT 10 P5 FB5 -. 72 WAR TEC TEH .560 ZBAZX 12 H 451 I I I 86 59 .35 241 PCT 13 P5 FB3 1.16 WAR TEC TEH .560 ZBAZX 11 H 331 I 86 59 .46 57 PCT 16 P5 FB5 -1.10 WAR TEC TEH .560 ZBAZX 11 H 331 I I I 90 59 .23 256 PCT 10 P5 FB3 .85 WAR TEC TEH .560 ZBAZX 12 H 431 I I I 96 59 .49 240 PCT 17 P5 FB4 1.19 WAR TEC TEH .560 ZBAZX 11 H 301 I I I 100 59 .19 291 PCT 8 P5 FB4 -1.57 WAR TEC TEH .560 ZBAZX 12 H 401 I 100 59 .20 45 PCT 9 P5 FB6 1.38 WAR TEC TEH .560 ZBAZX 12 H 401 I I I 69 60 .32 94 PCT 12 P5 FB4 -. 75 WAR TEC TEH .560 ZBAZX 17 H 281 I I I 73 60 .48 233 PCT 17 P5 FB4 -1.11 WAR TEC TEH .560 ZBAZX 11 H 381 I I I 75 60 .39 229 PCT 14 P5 FB4 -1.04 WAR TEC TEH .560 ZBAZX 11 H 391 I I I 77 60 .35 89 PCT 14 P5 FB4 -. 75 WAR TEC TEH .560 ZBAZX 12 H 481 I I I 79 60 .14 247 PCT 6 P5 FB4 -.83 WAR TEC TEH .560 ZBAZX 12 H 491 I I I 83 60 .46 62 PCT 16 P5 FB4 -1.21 WAR TEC TEH .560 ZBAZX 11 H 401 I I I 85 60 .76 70 PCT 24 P5 FB4 -.94 WAR TEC TEH .560 ZBAZX 11 H 411 I I I 95 60 .47 59 PCT 16 P5 FB4 -1.13 WAR TEC TEH .560 ZBAZX 11 H 421 I I I' 76 61 .38 92 PCT 15 P5 FB5 -. 30 WAR TEC TEH .560 ZBAZX 9 H 281 I I I 80 61 .27 72 PCT 11 P5 FB5 -. 50 WAR TEC TEH .560 ZBAZX 9 H 261 I I I 86 61 .37 87 PCT 15 P5

  • FB5

-1.51 WAR TEC TEH .560 ZBAZX 9 H 231 I I I 90 61 .27 274 PCT 11 P5 FB6 -. 67 WAR TEC TEH .560 ZBAZX 9 H 211 +----+----+---------+----+----+----+-----+----+---------+---------+---------+---------+-------+-------+----+----+----+------+------+------+--+-----+ I ROW COL VOLTS DEG IND PER CHN LOCN INCH! INCH2 UTIL! UTIL2 CRLEN CRWID CEG BEGT ENDT PDIA PTYPE CAL L IDXI +----+----+---------+----+----+----+-----+----+---------+---------+---------+---------+-------+-------+----+----+----+------+------+------+--+-----+ 1 ST Max

SG - C Service Induced Indications McGuire 1 1EOC25 MNS 20171001 11/27/2017 12:46:26 +----+----+---------+----+----+----+-----+----+---------+---------+---------+---------+-------+-------+----+----+----+------+------+------+--+-----+ I ROW COL VOLTS DEG IND PER CHN LOCN INCH1 INCH2 UTIL1 UTIL2 CRLEN CRWID CEG BEGT ENDT PDIA PTYPE CAL L IDX/ +----+----+---------+----+----+----+-----+----+---------+---------+---------+---------+-------+-------+----+----+----+------+------+------+--+-----+ I 94 61 .40 258 PCT 14 P5 FB5 -1.68 WAR TEC TEH .560 ZBAZX 20 H 43/ 94 61 .31 255 PCT 11 P5 FB6 -.60 WAR TEC TEH .560 ZBAZX 20 H 43/ I 96 61 .38 91 PCT 15 P5 FB5 -1.50 WAR TEC TEH .560 ZBAZX 9 H 18/ I 98 61 .30 84 PCT 12 P5 FB6 -.02 WAR TEC TEH .560 ZBAZX 9 H 17/ I 100 61 .43 91 PCT 16 P5 FB6 .61 WAR TEC TEH .560 ZBAZX 9 H 16/ I 110 61 .82 270 PCT 26 PS FB4 -1.20 WAR TEC TEH .560 ZBAZX 9 H 11 / I 114 61 .40 81 PCT 15 PS FB6 1.11 WAR TEC TEH .560 ZBAZX 9 H 6/ I 85 62 .27 100 PCT 11 P5 FB6 -1.79 WAR TEC TEH .560 ZBAZX 9 H 32/ I 99 62 .21 75 PCT 9 P5 FB7 .56 WAR TEC TEH .560 ZBAZX 9 H 33/ I 82 63 .23 79 PCT 10 PS FB5 -1.30 WAR TEC TEH .560 ZBAZX 9 H 54/ I 88 63 .23 246 PCT 10 PS FB4 1.51 WAR TEC TEH .560 ZBAZX 9 H 51/ I 102 63 .12 285 PCT 5 PS FB7 1.74 WAR TEC TEH .560 ZBAZX 9 H 44/ I 110 63 .23 91 PCT 10 P5 FB7

1. 73 WAR TEC TEH

.560 ZBAZX 9 H 40/ I 65 64 .08 263 PCT 4 P5 FB4

1. 74 WAR TEC TEH

.560 ZBAZX 18 H 56/ I 69 64 .24 105 PCT 10 PS FB4 1.12 WAR TEC TEH .560 ZBAZX 17 H 45/ I 95 64 .50 85 PCT 18 P5 FB5 -. 96 WAR TEC TEH .560 ZBAZX 9 H 61/ I 101 64 .47 271 PCT 17 P5 FBS -1.07 WAR TEC TEH .560 ZBAZX 9 H 62/ I 84 65 .28 90 PCT 11 P5 FBS -1.64 WAR TEC TEH .560 ZBAZX 9 H 82/ I 94 65 .28 247 PCT 11 PS FB5 -1.40 WAR TEC TEH .560 ZBAZX 9 H 77/ I 104 65 .09 65 PCT 4 PS FB4 -. 80 WAR TEC TEH .560 ZBAZX 9 H 72/ 104 65 .31 270 PCT 12 P5 FB4 1.15 WAR TEC TEH .560 ZBAZX 9 H 72/ I 108 65 .35 258 PCT 14 PS FB4 -1. 52 WAR TEC TEH .560 ZBAZX 9 H 70/ 108 65 .31 92 PCT 12 P5 FB5 -1.10 WAR TEC TEH .560 ZBAZX 9 H 70/ I 33 66 .10 232 PCT 5 PS FB5

1. 76 WAR TEC TEH

.560 ZBAZX 18 H 39/ I 75 66 .44 88 PCT 17 PS FB4 -1.29 WAR TEC TEH .560 ZBAZX 9 H 90/ I 64 67 .28 259 PCT 11 PS FB5 -1.17 WAR TEC TEH .560 ZBAZX 17 H 58/ +----+----+---------+----+----+----+-----+----+---------+---------+---------+---------+-------+-------+----+----+----+------+------+------+--+-----+ I ROW COL VOLTS DEG IND PER CHN LOCN INCH1 INCH2 UTIL1 UTIL2 CRLEN CRWID CEG BEGT ENDT PDIA PTYPE CAL L IDX/ +----+----+---------+----+----+----+-----+----+---------+---------+---------+---------+-------+-------+----+----+----+------+------+------+--+-----+ 2 ST Max

SG - C Service Induced Indications McGuire 1 1EOC25 MNS 20171001 11/27/2017 12:46:26 +----+----+---------+----+----+----+-----+----+---------+---------+---------+---------+-------+-------+----+----+----+------+------+------+--+-----+ I ROW COL VOLTS DEG IND PER CHN LOCN INCH! INCH2 UTILl UTIL2 CRLEN CRWID CEG BEGT ENDT PDIA PTYPE CAL L IDXI +----+----+---------+----+----+----+-----+----+---------+---------+---------+---------+-------+-------+----+----+----+------+------+------+--+-----+ I 66 67 .18 252 PCT 8 P5 FB5 -.94 WAR TEC TEH .560 ZBAZX 18 H 681 I 84 67 .39 98 PCT 15 P5 FB5 -1.28 WAR TEC TEH .560 ZBAZX 9 H 1121 I 88 67 .27 78 PCT 11 P5 FB4 1.11 WAR TEC TEH .560 ZBAZX 9 H 1101 I 90 67 .20 67 PCT 8 P5 FB6 -. 95 WAR TEC TEH .560 ZBAZX 9 H 1091 I 96 67 .26 111 PCT 11 P5 FB4

1. 33 WAR TEC TEH

.560 ZBAZX 9 H 1061 96 67 .27 89 PCT 11 P5 FB6 -1.15 WAR TEC TEH .560 ZBAZX 9 H 1061 I 110 67 .41 79 PCT 16 P5 FB4 -1.06 WAR TEC TEH .560 ZBAZX 9 H 991 I 61 68 .15 79 PCT 6 P5 FB5 .79 WAR TEC TEH .560 ZBAZX 17 H 711 I 93 68 .25 268 PCT 10 P5 FB5 -1.19 WAR TEC TEH .560 ZBAZX 9 H 1201 I 105 68 .31 76 PCT 12 P5 FB6 -1.03 WAR TEC TEH .560 ZBAZX 9 H 1221 I 107 68 .38 82 PCT 15 P5 FB5 -1.08 WAR TEC TEH .560 ZBAZX 9 H 1231 I 109 68 .33 97 PCT 13 P5 FB5 1.06 WAR TEC TEH .560 ZBAZX 9 H 1241 I 78 69 .34 246 PCT 13 P5 FB5 -1.49 WAR TEC TEH .560 ZBAZX 12 H 71 I 82 69 .64 89 PCT 22 P5 FB4 1.49 WAR TEC TEH .560 ZBAZX 9 H 1451 I 87 70 .32 100 PCT 13 P5 FB5 1.38 WAR TEC TEH .560 ZBAZX 12 H 311 I 93 70 .38 105 PCT 15 P5 FB5 -. 96 WAR TEC TEH .560 ZBAZX 12 H 321 I 90 71 .20 297 PCT 8 P5 FB4 -1.58 WAR TEC TEH .560 ZBAZX 12 H 261 90 71 .25 83 PCT 10 P5 FB5 -1.44 WAR TEC TEH .560 ZBAZX 12 H 261 I 77 72 .38 43 PCT 14 P5 FB4 .00 WAR TEC TEH .560 ZBAZX 11 H 231 I 82 73 .21 243 PCT 9 P5 FB5 1.64 WAR TEC TEH .560 ZBAZX 18 H 991 I 86 73 .52 82 PCT 18 P5 FB5 1.57 WAR TEC TEH .560 ZBAZX 17 H 941 I 90 73 .27 250 PCT 11 P5 FB5 1.55 WAR TEC TEH .560 ZBAZX 18 H 971 I 104 73 .18 109 PCT 8 P5 FB4 1.35 WAR TEC TEH .560 ZBAZX 17 H 901 I 93 74 .36 278 PCT 14 P5 FB4 -1.16 WAR TEC TEH .560 ZBAZX 18 H 1031 I 62 77 .42 257 PCT 16 P5 FB5 -1.01 WAR TEC TEH .560 ZBAZX 25 H 211 I +----+----+---------+----+----+----+-----+----+---------+---------+---------+---------+-------+-------+----+----+----+------+------+------+--+-----+ I ROW COL VOLTS DEG IND PER CHN LOCN INCH! INCH2 UTILl UTIL2 CRLEN CRWID CEG BEGT ENDT PDIA PTYPE CAL L IDXI +----+----+---------+----+----+----+-----+----+---------+---------+---------+---------+-------+-------+----+----+----+------+------+------+--+-----+ 3 ST Max


-~--------

SG - C Service Induced Indications McGuire 1 1EOC25 MNS 20171001 11/27/2017 12:46:26 +----+----+---------+----+----+----+-----+----+---------+---------+---------+---------+-------+-------+----+----+----+------+------+------+--+-----+ I ROW COL VOLTS DEG IND PER CHN LOCN INCH! INCH2 UTILl UTIL2 CRLEN CRWID CEG BEGT ENDT PDIA PTYPE CAL L IDXI +----+----+---------+----+----+----+-----+----+---------+---------+---------+---------+-------+-------+----+----+----+------+------+------+--+-----+ 63 88 .12 74 PCT 6 PS FB4 -. 97 WAR TEC TEH .560 ZBAZX 30 H 341 I 66 93 .11 237 PCT 5 PS 05H .39 WAR TEC TEH .560 ZBAZX 30 H 451 I 33 104 .41 88 PCT 15 PS 04H -1.54 WAR TEC TEH .560 ZBAZX 29 H 1371 I 29 124 .22 124 PCT 9 PS 04H -1.68 WAR TEC TEH .560 ZBAZX 29 H 2231 +----+----+---------+----+----+----+-----+----+---------+---------+---------+---------+-------+-------+----+----+----+------+------+------+--+-----+ I ROW COL VOLTS DEG IND PER CHN LOCN INCH! INCH2 UTILl UTIL2 CRLEN CRWID CEG BEGT ENDT PDIA PTYPE CAL L IDXI +----+----+---------+----+----+----+-----+----+---------+---------+---------+---------+-------+-------+----+----+----+------+------+------+--+-----+ 4 Tubes: 73 Records: 82 ST Max

SG - D Service Induced Indications McGuire 1 1EOC25 MNS 20171001 11/27/2017 12:50:05 +----+----+---------+----+----+----+-----+----+---------+---------+---------+---------+-------+-------+----+----+----+------+------+------+--+-----+ I ROW COL VOLTS DEG IND PER CHN LOCN INCHl INCH2 UTILl UTIL2 CRLEN CRWID CEG BEGT ENDT PDIA PTYPE CAL L IDX I +----+----+---------+----+----+----+-----+----+---------+---------+---------+---------+-------+-------+----+----+----+------+------+------+--+-----+ 34 7 .76 61 PCT 17 207 TSH .16 .41 .27 01H TEH .560 ZYAXP 6 H 186/ I 31 8 .79 53 PCT 18 207 TSH .20 .19 .27 01H TEH .560 ZYAXP 40 H 9/ I 58 41 .14 250 PCT 7 PS FB5 1.10 WAR TEC TEH .560 ZBAZX 18 H 169/ I 68 55 .18 261 PCT 8 PS FB6 .80 WAR TEC TEH .560 ZBAZX 18 H 97/ I 103 56 .18 78 PCT 8 PS FB4 -.83 WAR TEC TEH .560 ZBAZX 14 H 120/ I 72 57 .22 90 PCT 9 PS FB4 -1.26 WAR TEC TEH .560 ZBAZX 14 H 118/ I 51 60 .21 104 PCT 8 PS FB5 .90 WAR TEC TEH .560 ZBAZX 19 H 85/ I 92 65 .14 246 PCT 6 PS FB4 -1.00 WAR TEC TEH .560 ZBAZX 15 H 53/ I 47 68 .17 98 PCT 7 PS FB4 -.82 WAR TEC TEH .560 ZBAZX 19 H 56/ I 97 72 .16 242 PCT 7 PS FB4 -. 50 WAR TEC TEH .560 ZBAZX 14 H 34/ 97 72 .17 290 PCT 7 PS FB5 -. 25 WAR TEC TEH .560 ZBAZX 14 H 34/ I 98 73 .26 276 PCT 11 PS FB4 .99 WAR TEC TEH .560 ZBAZX 2 H 27/ I 87 74 .25 61 PCT 11 PS FB4 1.22 WAR TEC TEH .560 ZBAZX 26 H 20/ I 56 75 .27 104 PCT 11 PS FB5 -.35 WAR TEC TEH .560 ZBAZX 30 H 136/ I 110 77 .24 90 PCT 10 PS FB4 -.61 WAR TEC TEH .560 ZBAZX 25 H 67/ I 89 78 .42 80 PCT 16 PS FB5 -1.03 WAR TEC TEH .560 ZBAZX 24 H 55/ I 68 79 .31 84 PCT 11 PS FB5 -1.16 WAR TEC TEH .560 -ZBAZX 31 H 117/ I 100 79 .15 120 PCT 6 PS FB7 .58 WAR TEC TEH .560 ZBAZX 25 H 51/ I 67 80 .18 288 PCT 8 PS FB7 1.91 WAR TEC TEH .560 ZBAZX 30 H 120/ I 93 80 .26 66 PCT 11 PS FB6 -. 91 WAR TEC TEH .560 ZBAZX 24 H 17/ I 97 80 .19 276 PCT 8 PS FB7

1. 76 WAR TEC TEH

.560 ZBAZX 25 H 17/ I 99 80 .64 69 PCT 22 PS FB4 -. 93 WAR TEC TEH .560 ZBAZX 24 H 18/ 99 80 .29 67 PCT 12 PS FB5 -1.16 WAR TEC TEH .560 ZBAZX 24 H 18/ 99 80 .36 249 PCT 14 PS FB7 1.96 WAR TEC TEH .560 ZBAZX 24 H 18/ I 107 80 .30 237 PCT 12 PS FB4 .99 WAR TEC TEH .560 ZBAZX 24 H 19/ 107 80 .38 81 PCT 15 PS FB6 -.58 WAR TEC TEH .560 ZBAZX 24 H 19/ I 88 81 .19 299 PCT 8 PS FB5 1.41 WAR TEC TEH .560 ZBAZX 5 H 48/ +----+----+---------+----+----+----+-----+----+---------+---------+---------+---------+-------+-------+----+----+----+------+------+------+--+-----+ I ROW COL VOLTS DEG IND PER CHN LOCN INCHl INCH2 UTILl UTIL2 CRLEN CRWID CEG BEGT ENDT PDIA PTYPE CAL L IDX/ +----+----+---------+----+----+----+-----+----+---------+---------+---------+---------+-------+-------+----+----+----+------+------+------+--+-----+ 1 ST Max

SG - D Service Induced Indications McGuire 1 1EOC25 MNS 20171001 11/27/2017 12:50:05 +----+----+---------+----+----+----+-----+----+---------+---------+---------+---------+-------+-------+----+----+----+------+------+------+--+-----+ I ROW COL VOLTS DEG IND PER CHN LOCN INCHl INCH2 UTILl UTIL2 CRLEN CRWID CEG BEGT ENDT PDIA PTYPE CAL L IDXI +----+----+---------+----+----+----+-----+----+---------+---------+---------+---------+-------+-------+----+----+----+------+------+------+--+-----+ I 96 81 .40 282 PCT 15 P5 FB5 1.14 WAR TEC TEH .560 ZBAZX 5 H 521 I 91 82 .30 75 PCT 12 P5 FB4 1.25 WAR TEC TEH .560 ZBAZX 24 H 411 I 97 82 .22 246 PCT 9 P5 FB3 .56 WAR TEC TEH .560 ZBAZX 24 H 421 I 112 83 .25 122 PCT 10 P5 FB4 .93 WAR TEC TEH .560 ZBAZX 5 H 151 112 83 .20 100 PCT 8 P5 FB5 1.16 WAR TEC TEH .560 ZBAZX 5 H 151 I 76 85 .18 123 PCT 7 P5 FB4 .90 WAR TEC TEH .560 ZBAZX 3 H 271 I 77 86 .31 86 PCT 12 P5 FB5 -1.63 WAR TEC TEH .560 ZBAZX 3 H 231 I 85 86 .29 88 PCT 11 P5 FB5 -1.65 WAR TEC TEH .560 ZBAZX 3 H 221 I 87 90 .28 67 PCT 11 P5 FB4 -.89 WAR TEC TEH .560 ZBAZX 24 H 241 I 59 92 .25 106 PCT 10 P5 FB4 1.46 WAR TEC TEH .560 ZBAZX 31 H 571 I 45 98 .17 246 PCT 7 P5 FB5 -1.28 WAR TEC TEH .560 ZBAZX 30 H 261 I 15 142 .18 307 PCT 8 P5 07H .36 WAR TEC TEH .560 ZBAZX 30 H 1591 +----+----+---------+----+----+----+-----+----+---------+---------+---------+---------+-------+-------+----+----+----+------+------+------+--+-----+ I ROW COL VOLTS DEG IND PER CHN LOCN INCHl INCH2 UTIL1 UTIL2 CRLEN CRWID CEG BEGT ENDT PDIA PTYPE CAL L IDXI +----+----+---------+----+----+----+-----+----+---------+---------+---------+---------+-------+-------+----+----+----+------+------+------+--+-----+ 2 Tubes: 34 Records: 39 ST Max =i}}