Text

R EGULATORY INFORMATION DISTRIBUTION SYSTEM

<RIDS)

I

ACCESSION

NBR: 8707250101

DOC. DATE: 87/07/21

NOTARIZED.'O

DOCV.ET 'i

ACIL: 50-251

Turkey Point

P lant'nit 4i Florida Power

and Lighb

C

05000251

AUTH. NAME

AUTHOR AFFILIATION

dERDTi A. R.

Reg ion 2i Office of Director

RECIP. NAME

REC IP IENT AFFILIATION

WOODY'. Q.

Fl ori da Power

'~ Light Co.

SUBJECT:

Advises of error in Paragraph

13 of Insp Rept 50-251/87-16.

Under di'scussion

of effects of changes

in axial offset

on

reactor

coolant inventory calculationsi change for 5/ offsset

change

should

be

3 3

u~ not

50 gal 1 ons

as stated.

DISTRIBUTION CODE:

IE01D

COPIES

RECEIVED: LTR

ENCL

. SIZE:

TITLE: General

(50 Dkt)-Insp Rept/Notice

of Violation Response

NOTES:

REC IP IENT

ID CODE/NAME

PD2-2

PD

INTERNAL: *EOD

NRR

MOR ISSEAUi D

NRR/DREP /EP B

NRR/DRIS

DIR'RMANi J

REG

F LE

LE

01

COPIES

LTTR ENCL

1

A

1

1

1

REC IP IENT

ID CODE/NAME

'McDONALDiD

DEDRO

NRR/DOEA DIR

NRR/DREP/RPB

NRR/PMAS/ILRB

OGC/HDS2

RES

DEPY, Gl

COPIES

LTTR ENCL

1

1

2

1

XTERNAL:

LPDR

NSIC

NRC

PDR

TOTAL NUMBER QF

CQP IES REQUIRED:

LTTR

20

ENCL

F orida Power and Light Company

~

~

~

~

~

TTN:

Nr. C. 0.

Woody

Group Vice President

Nuclear

Energy Department

P. 0.

Box 14000

Juno Beach,

FL

33408

Gentlemen:

SUBJECT:

CORRECTION TO

REPORT

NO. 50-251/87-16

A calculational

error

has

been

found in paragraph

13

(page 35) of the

subject report.

Under the discussion of the effects of changes

in axial offset

on reactor coolant inventory calculations,

the change for a

5X offset change

should

be 3.3 gallons

and not 50 as stated.

The error resulted

from the use of

the entire reactor coolant

system

volume

(8043 cubic feet) in the calculation,

instead of the core volume (536 cubic feet).

This error does

not affect any of

the findings of the report.

We regret

any inconvenience it may have

caused

you.

Sincerely,

8707250101

870721

PDR

ADOCK 0500025i

8

PDR

Alan R. Herdt, Chief

Engineering

Branch

Division of Reactor Safety

cc: P:

M. Wethy, Vice President

Turkey Point Nuclear Plant

5. J. Baker, Plant Manager

Turkey Point Nuclear Plant

~W. Bladow, Plant

QA Superintendent

~ Arias, Jr.-, Regulatory

and Compliance

'upervisor

bcc:

C Resident

Inspector

.

ocument Control. Room

State of Florida

PBurnett:gb g~dape

~07//d./87

07//A/87

BWilson

07/g,/87

~o( LLO