Text
RfGULATORY~ FORMATION DISTRISUTION ST+M (RIDS) i ACCESSION NBR:8302070472 DOC ~ DATE: 83/02/01 NOTARIZED; NO FACIL:50"250 Turkey Point Pl anti Uni t 3i F l orida Power and Light C
50-251 Turkey Point Planti Unit 4i Florida Power -and Light C
AUTH BYNAME AUTHOR AFFILIATION UHRIGiR ~ Es Florida Power 8 Light Co ~
REC IP ~ NAME REC IP IENT A F F ILIATI ON VARGAiS ~ AD Operating Reactors Branch 1
DOCKET 05000250 05000251
SUBJECT:
Provides justification for continued operation 8
qualification info for safety evaluation Category II A Items 35i59 8 101iin response to NRC 821213 l,tr re environ qual ification of safety-related equipment.Wi thheld, 7
DISTRIBUTION CODE:
PA01'S COPIES -RECEIVED:LTR. + ENCL +
SIZE ~
TITLE: Proprietary Review Distribution-Operating Reactor NOTES:
RECIPIENT COPIES ID CODE/NAME LTTR ENCL NRR ORB1 BC ~9=08 7
7 INTERNAL: ELD/HOSE 1
0 RGN2
%0/
1 1
EXTERNALS ACRS
+1 u-iS NRC PDR 1
0 RECIPIENT ID'CODE/NAME REG FILE
+4%
LPDR NTIS COPIES LTTR ENCL 1
1 1
0 1
0
'TOTAL NUMBER OF COPIES REQUIRED:
LTTR 19 ENCL 15
M I il M
w
<<( kf c",I'(f)I,
<<4
)M li Q f ',,
>)f1 I W
(f<<ihf J
((8
)f C<<
I
)
'0 I ff f If 1 ] II/ t I(, f,<<If Ikf 0 fklk, I I
)1I
)
,f;I IM W I IM C) y n ki IliI
<< 'II Me I'M M M
. BOX 14000, JUNO BEACH, FL 33408 gyral /
FLORIDA POWER & LIGHTCOMPANY February I, I 983 L-83-47 Office of Nuclear Reactor Regulations Attention:
Mr. Steven A. Varga, Chief Operating Reaclors Branch No.
I Division of Licensing U. S. Nuclear Regulatory Commission Washington, D.C. 20555
Dear Mr. Varga:
Re:
Turkey Point Units No. 3 Bc 4 Docket Nos. 50-250 and 50-25 I Environmental Qualification SER In response to your letter of December I 3, I 982, regarding environmental qualification of safety related electrical equipment, Florida Power 8
Liaht has conducted a review of Technical Evaluation Reoorts tha'ere prepared by the Franklin Research Center.
With the exception of the three component items listed below, ovr review indicates that FPL has previously transmitted justification for continued operation for all of the equipment identified in the Technical Evaluction Report.
We therefore reaffirm that these previously submitted justifications for continued operation will apply to the component items listed in the Franklin Research Center reports.
This is in accord with the conclusions reached by Franklin Research Center identified in Appendix D of their report.
For the Safety Evaluation Category II A items number 35, 59 and IOI, we are herein providing a justification for continued operation for item 35 and additional qualification information regarding items 59 and IOI that we believe shows that these last two are qualified:
Item 35: Pyco RTD Model l2240300448 CS The test specimen was preaged prior to the LOCA test to l20OC for 7 days.
Conservatively assuming that for each I OoC decrease in temperatvre the life doubles, the test demonstrates that the equipment would last for 2.63 years in the less than 50OC ambient temperature of the containment building.
Since publication of the Pyco qualification test report, Pyco has amended the part numbering system used for their RTDs.
The digit, "I", was added to designate nuclear equipment.
Pyco states that RTDs tested as P/N 22-4030 are identical to P/N I 22-4030.
PEOPLE... SERVING PEOPLE Presently Pyco is retesting these RTDs more rigorously with respect to aging.
The RTDs were installed in December l98I.
The results of the additional testing will be available in March l983.
At that time the RTDs wiii have reached only one*alt of their present quaii'ied iife. ~$0~
This provides vs with a large enough margin to make a decision based on the new test information as to replacement ar con'inued use of 'he Pyco 8302070472 8302 PPR
@POCK 05 PPR P
A
Page 2 Turkey Point Units No. 3 Bc 4 Docket Nos. 50-250 and 50-25 I Environmental Qualification SER Item 59:
Technology of Energy Corp. Acoustic Monitor Model E2273A (sensor)/500 (Charge Converter)
Enclosed is a TEC letter dated March 23, l983 recommending that TEC Model l60 Transient Shield be installed to protect the Model 500 Charge Converter from direct steam impingement.
The l60 Transient Shield has been installed on Unit 3 and is being installed on Unit 4 at this time.
The enclosed TEC qualification test report 5 I 7-TR-03 Rev.
2 provides evidence that the TEC Acoustic Monitor system is qualified and will not fail due to environmental conditions.
Item I 0 I: Rockbestos Cable Model Firewall III Enclosed is a IO/23/8I letter from Rockbestos indicating that the test results are applicable to the item in question.
This information was provided in our submittal dated September 24, l982 in response to request 4C.
The TEC Qualification test report 5I7-TR-03 Rev. 3 is proprietary information and we request that it be exempt from public disclosure.
Certification of the proprietary nature of above listed information will be included in our response described in L-83-23 (January 20, l 983).
If you or your staff have any questions regarding the above information, please contact us.
Very truly yours, Robert
. Uhrig Vice President Advanced Systems & Technology REU/JES/cab Attachment cc:
J. P. O'Reilly, Region II Harold F.'Reis, Esquire PNS-LI-83-066-I
e 0
r.
a.
WA i