REGULAT~ "Y INFORMATION DISTBIBUTIOI" ".YSTEM (BIDS)

ACCESS ION NBR:7902060182 DOC,. DATF: 79/01/31 NOTARIZED:

YES FACIL:50-250 Turkey Point Plant, Unit 3, Florida Power and Light C

50-251 Turkey Point Plant, Unit 4, Florida Power and Light C

AUTH.NAME AUTHOR AFFILIATION UHBIG,R.E.

Florida Power 8, Light Co.

RECIP.NAME RECI,PIENT AFFILIATION STELLO, V.

Division of Operating Reactors

SUBJECT:

Suhmits reauired d'ocuments for amend nf Appendix A of Licenses DPB;31 8, DPR-41,re deletion of Tech Spec 1.16.1, which concerns fuel residence time limit.Also forwards SFB re proposed changes.

DOCKS 050 05000251 DISTRIBUTI()N CODE-AOOI S COP IFS RFCEIVFD-LTR + ENCL SIZF- ~

~

TITLF-GFNFRAL DI STBIBUTION F()R AFTER ISSUA'NCF OF ()PEBATING I I C NOTES:

ACTION:

I NTEBNAL-E XTEBNAL:

RECIPIENT ID CODE/NA)(E 05 Bc ding 8.- /

I 18E 15 CORE PERF BB 17 FNGB BR 19 PLANT SYS BB 21 EFI T TBT SYS 03 LP0R 23 ACBS C()PI ES LTI'R ENCL 7

7 I

2 2

I I

I I

I I

I

.I I

I 16 16 REC I,P I ENT ID CODE/NAME 02 NBC PDR 14'A/EDO 16 AD SYS/PROJ 18 REAC SFTY BR 20 EEB 22 BBINKMAN 04 NSI C COP I'ES LTTR FNCL 8 $979 TOTAL NUMBFB OF COPIES REQUIRED:. LTTR 38 ENCL 38

.O. BOX 529100, MIAMI,FL 33152

+>Illa<

=Q-

FLORIOA POWER & LIGHTCOMPANY January 31,1979 L-79-25 Director of.Nuclear Reactor Regulation Attention:

.Mr. Victor Stello, Director Division of Operating Reactors U.

S.. Nuclear Regulatory Commission Washington, D.

C..

20555

Dear Mr. Stello:

Re:

Turkey Point Units 3 and 4

Docket Nos. 50-250 and 50-251.

Proposed Amendment to Facility 0 eratin Licenses DPR-31 and DPR-41 In accordance with 10 CFR 50.30, Florida Power

& Light Company submi,ts herewith three (3) si gned originals and forty (40) copies of a request to amend Appendix,A of Facility Operating Licenses DPR-31 and DPR-41.

The proposed amendment is described below and shown on the accompanying Technical Specificati'on page bearing the date of this letter in the lower right.'hand corner.

~Pa e 1-6 Technical Speci'fication. 1.16.1 (Fuel Residence Time Limit) is deleted, for reasons discussed in the attached safety evaluation.

Specification 1.16.2 is renumbered 1.16.

The proposed amendment.has been reviewed by the Turkey Point Plant Nuclear Safety Committee and the Florida

Power,

& Light Company Nuclear Review Board.

They have concluded that it does not involve an unreviewed safety question.

Ver

yours, Robert E. Uhri g Vice 'President Advanced Systems and Technology'EU/MAS/cpc Attachment cc:,

Mr..James P. O'Reilly, Region II Robert Lowenstein,, Esquire o'7902060182 PEOPLE... SERVING PEOPLE

1.16 REACTOR COOLANT 'PUMPS The reactor shall not be operated with less than three reactor coolant pumps in operation.

1'.17 LOW POMER PHYSICS TESTS Low power physics tests are tests below a nominal 5/ of rated:

power which measure fundamental characteristics of the reactor core and related instrumentation.

1-6 1/29/7g

SAFETY EVAL'UAT ION'e:

Turkey 'Point Un.its 3

8 4

Proposed'ech Spec Change F.uel'esidence Time I.

Introduction This evaluation. suppoi ts a proposal to delete Technical Speci.fication 1.16.1

(:Fuel,.Residence Time Limit'.

I'I'.

01 S CUSS 1 on Technical Specification 1.16.1: limits the fuel residence times to 27,000 EFPH for Turkey Point Unit 3 and 30,000 EFPH for Unit 4.

These restrictions were,incorporated'o assure that no clad flattening,

('col'lapse)".would be predicted, according to the approved l9estinghouse

.model;, for the l.imiting initial core.- fuel regions.

'Florida 'Power 8 Light 'Company requests that Technical Speci,fication

1. 1'6.1 be de'1eted'.

The all owabl'e fuel resi dence time for no cl ad flattening is a reload cycle dependent val'ue which consi'ders fuel

'esign, fuel,burnup. and the core operating environment.

For, exampl'e, Unit 3 has

a. predicted clad flattening time in excess of 50,000 EFPH, for Cycle 5 '(no i.ni:tial core fuel), and Unit 4 has a 34,'000 EFPH'alue for Cycle 5.

Both units satisfy Technical Specification 1.16.1.

for the present Cycle 5 operations.

However, this speci.fication can be unnecessarily, restrictive on allowable fuel burnups in future reload cycles.

A fuel residence time Technical 'Specification limi.t is not needed since each fuel region is checked during a,reload design, process to assure that clad fl'attening is not predicted.

'Further,,for each reload cycle our Turkey Point Plant 'Nuclear Safety Commi'ttee reviews and approves the Reload Safety Evaluation (RSE) report, which documents that clad flattening is not predicted during the upcoming cycle.

It is noted that most operating plants do not have fuel residence time limitations

.based'n clad flattening, but these plants do assure that a no-clad-flattening design, basis is satisfied as a result of the reload design process and revi ew.

I:II.

Con cl us.i ons Based on the considerations discussed

above, (1), the amendment does not involve a signifi'cant increase in the,probabili,ty or consequences of accidents previously consi'dered and does.not involve a significant decrease in a safety margin, (2') there is reasonable assurance that the health and safety of the publ'ic wi'll not be endangered by operation in. the.proposed
manner, and (3) such acti.vi,ties will 'be conducted in compliance with the Comnission's regulations and the issuance of this amendment will not be inimical to the common defense and security or to the health and safety of the public.

STATE OF FLORIDA

)

)

COUNTY OF DADE

)

ss.

Robert E. Uhrig, being first duly sworn, deposes and says:

That he is a Vice President of Florida Power 6 Light, Company, the Licensee herein; That he has executed the foregoing document; that the state-ments made in this said document are true and correct to the best of his knowledge, information, and belief, and that he is authorized to execute the document on behalf of said Licensee.

Robert E. Uhrig Subscribed and sworn to before me this

/

day of NOTARY PUBLI in and for the county of Dade, State of Florida l1y commission expires:

<((<g<4((<<,

PDTA' A1DUC NATE Ot: ROLDh g ~gDE CCt'("~"CW

~ ~~"'AES "LAB"<I BCNDiO TiiRU, f:AYHABD RCtiCING AGB,CY.'

<