.0 REGULATORY INFORMATION DISTRIBUTION SYSTEM (RIDS)

ACCESSION NBR:8106010283 DOC ~ DATE: 81/05/26 NOTARIZED:

NO FACIl:50 315 Dona'ld C ~

Cook Nuclear Power Plantt Unit 1< Indiana 50 316 Donald CD Cook Nuclear Power Planti Unit 2P India AUTH BYNAME AUTHOR AFFILIATION HUNTERPR ~ ST Indiana 8 Michigan Electr ic Co, RECIP ~ NAME'ECIPIENT AFFILIATION DENTONPH ~ RE Office of Nuclear Reactor Regulationi Director

SUBJECT:

Submits info re main steam pr essure monitors 8 containment water l evel monitoring sysioer 810512'el con Exposur e to hydrogen combustion environ would-not adver sely affect oper ation of containment water level monitoring.sys.

DISTRIBUTION CODE:

AOOIS COPIES RECEIVED:LTR l ENCL +

SIZE:

TITLE: Gener al Distribution for after Issuance of Operating License NOTES: ILE:3 copies all materials Send 3 copies of all material to I8E ~

DOCKET 05000315 05000315 05000316 RECIPIENT ID CODE/NAME ACTION:

VARGA P S ~

04 INTERNAL: D/DIRPHUM FAC08 IRE 06 OELD 11 RAD ASMT BR COPIES LTTR ENCL 13 RECIPIENT ID CODE/NAME DIR P DIV OF LIC NRC PDR 02 0

~

R 10 EG F ILE 01 COPIES LTTR" ENCL EXTERNAL; ACRS NSIC 09 05 16 1

1 LPDR 03

~UN Oa 1981 b

TDTAL NUMBER OF COPIES REQUIRED:, LTTR Pf ENCL

INDIANA II MICHIGAN ELECTRIC COMPANY P. O. BOX 18 BOWLING GR E EN STATION NEW YORK, N. Y. 10004 May 26, 1981 AEP:NRC:00500B Donald C.

Cook Nuclear Plant Unit Nos.

1 and 2

Docket Nos.

50-315 and 50-316 License Nos.

OPR-58 and OPR-74 Supplementary Information to AEP:NRC:0500A Mr. Harold R. Oenton, Director Gffice of Nuclear Reactor Regulation

'.S.

Nuclear Regulatory Commission Washington, D. C.

20555

Dear Mr. Denton:

This letter serves to provide additional information with regard to our AEP:NRC:00500A submittal, dated April 24,

1981, as requested by members of your staff during a telephone conversation held on May 12, 1981.

Specifically, the Staff has requested that we provide the bases for excluding the "Main Steam Pressure Monitors" (MSPM) and the Containment Water Level Monitoring System" from the list of "Inadequate Core Cooling/Hydrogen Control Equipment Inside Containment" contained in Attachment No.

3 of the aforementioned submittal.

A discussion of these items follows.

(1)

Main Steam Pressure Monitors As stated in our response to IE Bulletin No.79-01B, the MSPM are located outside reactor containment.

(

Reference:

Attachment No.

1 to AEP:NRC:00356A, dated March 7, 1980).

Since this equipment is located outside of reactor containment, the MS pressure monitors would not be susceptible to the effects of a hydrogen combustion environment and hence are not within the scope of Attachment No.

3 to AEP:NRC:0500A.

(2)

Containment Water L'evel Monitorin S stem A containment water level monitoring system will be installed in accordance with the requirements of Item II.F.l,, of NUREG-0737 as described in our letter of January 9,

1981 (AEP:NRC:00398).

The in-containment portions of this system will be environmentally qualified to meet the 8 1 0 6 0 0 3. ~~

Mr. Harold R. Denton AEP: NRC: 005008-NUREG.

Based on the conservative heat transfer calculations presented in Attachment No.

4 to our AEP:NRC:00500A submittal, and the LOCA/MSLB qualification of the in-containment portions of the system being installed to meet the requirements of NUREG-0737, we believe that exposure 'to a hydrogen combustion environment would not adversely affect operation of the contain-ment water level monitoring system.

The function performed by the system is not essential to either achieve and maintain the reactor in a safe shutdown condition or to assure adequate hydrogen control capability.

At the Cook Plant, Emergency Core Coo1ing System (ECCS) switchover from the injection mode to the sump recirculation mode does not rely on indication of containment water level.

Switchover is accomplished by manual actions based on Refueling Water Storage Tank (RWST) level indication with the containment water level indication provid-ing backup information.

The RWST level moni,tors are located outside reactor containment and would not be susceptible to the effects of a hydrogen combustion environment.

In addition, the residual heat removal (RHR) pumps would be automatically

tripped, as a backup measure to the operator action, when the RWST reaches the low-low level

(

References:

Response

to NRC guestion Nos.

212.1 and 212.30 contained in Appendix 'g'o the Cook Plant Final Safety Analysis Report (FSAR) - Amendment Nos.

77 and 78 dated July 1977 and October 1977 respectively).

Conservative calculations indicate that injection of the "minimum usable RWST volume", specified in the plant technical specifications (350,000 gallons), into containment will result in adequate NPSH for the RHR and containment spray pumps when the pumps are aligned to take suction from the recirculation sump.

(

Reference:

Response

to NRC guestion No. 212.29 (Part 2) contained in Appendix 'g'o the FSAR).

For these reasons, it is clear that indication of containment water level is not essential for proper ECCS switchover.

Very truly yours, cc:

John E. Dolan - Columbus R.

K. Jurgensen R.

C. Callen G. Charnoff D. V. Shaller - Bridgman Region II? Site Inspector - Bridgman Vice President