ML17328A844

From kanterella
Jump to navigation Jump to search
Amend 152 to License DPR-58,allowing Decrease in Min Measured Flow Requirements Found in Tech Spec Table 3.2-1
ML17328A844
Person / Time
Site: Cook American Electric Power icon.png
Issue date: 01/04/1991
From: Marsh L
Office of Nuclear Reactor Regulation
To:
Shared Package
ML17328A845 List:
References
NUDOCS 9101140077
Download: ML17328A844 (9)


Text

gp,R RECT Cq 0 Cy nO IA

~+

o~

Cy k~*y4 UNITED STATES NUCLEAR REGULATORY COMMISSION WASHINGTON, D. C. 20555 INDIANA MICHIGAN POWER COMPANY DOCKET.N0.-50-315 DONALD G.-COOK NUCLEAR PLANT -UNIT NO.

1 AMENDMENT TO FACILITY OPERATING. LICENSE Amendment No. 152 License No. DPR-58 1.

The Nuclear Regulatory Commission (the Commission) has found that:

A.

The application for amendment by Indiana Michigan Power Company (the licensee) dated July 23, 1990, complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act), and the Commission's rules and regulations set forth in 10 CFR Chapter I; B.

The facility will operate in conformity with the application, the provisions of the Act, and the rules and regulations of the Commission; C.

Thet e is reasonable assurance (i) that the activities authorized by this amendment can be conducted without endangering the health and safety of the public, and (ii) that such activities will be conducted in compliance with the Commission's regulations; D.

The issuance of this amendment will not be inimical to the common defense and security or to the health and safety of the public; and E.

The issuance of this amendment is in accordance with 10 CFR Part 51 of the Commission's regulations and all applicable requirements have been satisfied.

9iOii40077 9i0i04 PDR ADDCK 050003i5 p

PDR

2.

Accordingly, the license is amended by changes to the Technical Specifications as indicated in the attachment to this license amendment, and paragraph 2 AC.(2) of Facility Operating License No.

DPR-58 is hereby amended to read as follows:

Technical S ecifications The Technical Specifications contained in Appendices A and B, as revised through Amendment No. i52

, are hereby incorporated in the license.

The licensee shall operate the facility in accordance with the Technical Specifications.

3 ~

This license amendment is effective as of the date of its issuance.

FOR THE NUCLEAR REGULATORY COMMISSION

Attachment:

Changes to the Technical Specif ications Date of Issuance:

January 4, )99)

L. B. Marsh, Director Project Directorate III-1 Division of Reactor Projects III/IV/V Office of Nuclear Reactor Regulation

ATTACHMENT TO LICENSE AMENDMENT AMENDMENT NO.

TO FACILITY OPERATING LICENSE NO. DPR-58 DOCKET NO. 50-315 Revise Appendix A Technical Specifications by removing.-the pages identified below and inserting the attached pages.

The revised pages are identified by amendment number and contain marginal lines indicating the area of change.

RENOVE 2~2 2<<5 INSERT 2~2 2-5

t

668 658

~400 Ps f~

UNACCEPTABLE OPERATION 6ie

~~SO Ps p'~

~ 628

~l00 Ps ).

~000 Ps)~

~ 6lB 1840 Ps)'~

588 ACCEPTABLE OP ERATION 578 PRESSURE (PSIA)

.5

.6

,7

.8

.~

1.

l.l 1.2 PQVER tf~eciion oT noeinell BR EAKPO INTS (FRACTION RATED THERMAL POWER, T-AVG IN DEGREES F) 1840 2000 2100 2250 2400 (0.0, 622.1),

(1.13, 587.3),

(0.0, 633.8),

(1.08, 601.4),

(0.0, 640.8),

(1..06, 609.8),

(0.0, 650.7),

(1.02, 621.9),

(0.0, 660.1),

(0.98, 633.7),

(1.20, (1.20, (1.20, (1.20, (1.20, 577.5) 586.0) 591.3) 598.9) 606.2)

RATED THERMAL POWER

~ 3413 MMT FIGURE 2.1-1 REACTOR CORE SAFETY LIMITS COOK NUCLEAR PLANT - UNIT 1 2-2 AMENDMENT NO ~ 7g jfg$

152

TABLE 2.2-1 REACTOR TRIP SYSTEM INSTRUMENTATION TRIP SETPOINTS FUNCTIONAL UNIT TRIP SETPOINT ALLOWABLE VALUES

1. Manual Reactor Trip Not Applicable Not Applicable 2.

Power Range, Neutron Flux Low Setpoint

- less than or equal to 25% of RATED THERMAL POWER High Setpoint

- less than or equal to 109% of RATED THERMAL POWER Low Setpoint

- less than or equal to 26% of RATED THERMAL POWER High Setpoint

- less than or equal to 110% of RATED THERMAL POWER 3.

Power Range, Neutron Flux, High Positive Rate Less than or equal to 5% of RATED THERMAL POWER with a time constant greater than or equal to 2 seconds Less than or equal to 5.5% of RATED THERMAL POWER with a time constant greater than or equal to 2 seconds 4.

Power Range, Neutron Flux, High Negative Rate Less than or equal to 5% of RATED THERMAL POWER with a time constant greater than or equal to 2 seconds Less than or equal to 5.5% of RATED THERMAL POWER with a time constant greater than or equal to 2 seconds

5. Intermediate
Range, Neutron Flux Less than or equal to 25% of Less than or equal to 30%

RATED THERMAL POWER of RATED THERMAL POWER 6.

Source

Range, Neutron Flux Less than or equal to 10 5 counts per second Less thag or equal to 1.3 x 10 counts per second
7. Overtemperature Delta T See Note 1

See Note 3

8. Overpower Delta T See Note 2

See Note 4

9. Pressurizer Pressure

-- Low 10.Pressurizer Pressure

-- High Greater than or equal to 1875 psig Less than or equal to 2385 psig Greater than or equal to 1865 psig Less than or equal to 2395 psig 11.Pressurizer Water Level -- High Less than or equal to 92% of instrument span Less than or equal to 93%

of. instrument span 12.Loss of Flow Greater than or equal to 90$

of design flow per loop*

Greater than or equal to 89.1% of design flow per loop*

  • Design flow is 90,400 gpm per loop.

COOK NUCLEAR PLANT - UNIT 1 2-5 AMENDMENT No. g 118

C

TABLE 3.2-1 DNB PARAMETERS'IMITS PARAMETER 4 Loops in Operation at RATED THERMAL POWER Reactor Coolant System Tavg

< 570.9 F

Pressurizer Pressure

) 2050 psig Reactor Coolant System Total Flov Rate

) 361,600 gpm **

  • Indicated average of at least three OPERABLE instrument loops.
    • Limit not applicable during either a THERMAL POWER ramp increase in excess of 5 percent RATED THERMAL POWER per minute or a THERMAL POWER step increase in excess of 10 percent RATED THER.'fAL POWER.
      • Indicated value.

COOK NUCLEAR PLANT - UNIT 1 3/4 2-14 AMENDMENT NO. 9f~ 128>

'JW