Special Rept:On 891130,control Room HVAC Area Fire Doors 436 & 437 Declared Inoperable Due to Bottom Seal Not Functioning.On 891216,charging Pump Room Door 364 Declared Inoperable.On 891201,crack Discovered in Retardant Matl
ML17328A535
Person / Time
Site: Cook  
Issue date: 01/03/1990
From: Blind A
INDIANA MICHIGAN POWER CO. (FORMERLY INDIANA & MICHIG
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
NUDOCS 9001120204
Download: ML17328A535 (4)


Text

ACCELERATED DISTRIBUTION DEMONS~TION SYSTEM REGULATORY INFORMATION DISTRIBUTION SYSTEM (RIDS)

ACCESSION NBR:9001120204 DOC.DATE: 90/01/03 NOTARIZED: NO DOCKET FACIL:50-315 Donald C.

Cook Nuclear Power Plant, Unit 1, Indiana 05000315 50-316 Donald C.

Cook Nuclear Power Plant, Unit 2, Indiana 05000316 AUTH.NAME AUTHOR AFFILIATION BLIND,A.A.

Indiana Michigan Power Co.

(formerly Indiana

& Michigan Ele RECIP.NAME RECIPIENT AFFILIATION Document Control Branch (Document Control Desk)

SUBJECT:

Special rept:on 891130,Fire Doors 436

& 437 inoperable

& on 891216 Fire Door 364 inoperable.

DISTRIBUTION CODE:

IE22D COPIES RECEIVED:LTR J ENCL ~

SIZE:

3 TITLE: 50.73/50.9 Licensee Event Report (LER), Incident Rpt, etc.

NOTES:

RECIPIENT ID CODE/NAME PD3-1 LA GIITTER,J.

INTERNAL: ACRS MICHELSON ACRS WYLIE AEOD/DSP/TPAB DEDRO NRR/DET/EMEB9H3 NRR/DLPQ/LHFB11 NRR/DOEA/OEAB11 NRR/DST/SELB 8D NRR/DST/SPLB8D1 NUDOCS-ABSTRACT RES/DSIR/EIB EXTERNAL: EG&G WILLIAMS,S LPDR NSIC MAYS,G NUDOCS FULL TXT COPIES LTTR EN 1

1 CL RECIPIENT ID CODE/NAME PD3-1 PD ACRS MOELLER AEOD/DOA.

AEOD/ROAB/DSP NRR/DET/ECMB 9H-NRR/DET/ESGB 8D NRR/DLPQ/LPEB10 NRR/DREP/PRPB11 NRR/DST/SICB 7E DER/ RXB 8E RGGG FILE 01 L ST LOBBY WARD NRC PDR NSIC MURPHY,G.A COPIES LTTR ENCL NOTE TO ALL"RIDS" RECIPIENTS:

PLEASE HELP US TO REDUCE WASTE! CONTACT THE DOCUMENT CONTROL DESK, ROOM Pl-37 (EXT. 20079) TO ELIMINATEYOUR NAME FROM DISTIUBUTION LISTS FOR DOCUMENTS YOU DON'T NEED!

TOTAL NUMBER OF COPIES REQUIRED:

LTTR 38 ENCL

&8-

Indiana Michigan Power Company Cook Nuclear Plant P.O. Box 458 Bridgman. MI 49106 616 465 5901 lMblANA NICHlGiAN POMfER January 3,

1986 I

Donald C.

Cook Nuclear Plant Unit Nos.

1 and 2

Docket Nos.,50-31S and SO-316 License Nos.

DPR-58 and DPR-74 Document Control One white Flint North 11555 Rockv'ie Pike Rockville, Maryland 20852 Attn: A.B. Davis

Dear Mr. Davis:

This special report is being submitted in accordance with Technical Specification 3.7.10 action a, to 1) inform you

. that, the following four fire barriers have been inoperable longer than allowed by Technical Specification 3.7.10 action a,

and 2) serve as a follow-up as committed in previous letters dated September 19, 1989 and November 13, 1989.

Fire Door 436, the Unit One Control Room HVAC

door, was declared inoperable on November 30, to its bottom seal not functioning properly.

returned to operab'.lity on December ll, 1989.

watch, as required by'echnical Specification action a, was maintained while the door was inoperable.

area

1989, due 3t was A fire 3.7..10 Fire Door 437, separating the Unit One and Unit Two Control Room HVAC areas, was declared inoperable on November 30,
1989, due to its bottom seal not functioning.

Et was returned to operability on December 12, 1989.

A fire watch, as required by Technical Specification 3.7.10 action a, was maintained while the door was inoperable.

Fire Door 364., the Unit One Charging Pumps Room door, was declared inoperable on December 16,

1989, due to its failure to close properlv.

Xt was returned to operability on December 26, 1989.

A fire watch, as required by Technical Specification 3.7.10 action a was maintained while the door was inoperable.

9OC> 1 120204 9r.r0:I Ol":

Pfrr-,

Pgrnt-.I; O'-;,OOO'-. > ~

A crack was identified in the TSI fire retardant material covering the 2A-P2 cable raceway at the auxiliary building 621'levation on December 1,

1989.

The TSI material was repaired and restored to operability on January 2,

1990.

A fire watch, as required by Technical Specification 3.7.10 action a, was maintained while the TSI material was inoperable.

In previous letters dated September 19, 1989 and November. 13,

1989, we informed you that Fire Dampers 1-HV-ACF-Dl and 1-HV-ACF-D2 in the Unit One P-250 Computer Room were declared inoperable due to a failure of the fire damper. release mechanism common to the dampers.

Following an engineering evaluation which determined that the dampers would close reliably when reset according to a specific procedure, administrative controls were established on the resetting of the

dampers, and the dampers were all restored to operability on December 8,

1989.

A fire watch, as required by Technical Specification 3.7.10 action a, was maintained while the dampers were inoperable.

In a previous letter dated November 13,

1989, we informed you that the block ventilation ducts for ventilation fans 2-HV-SGRS-4A, 2-HV-SGRS-lA, 2-HV-SGRS-3, 2-HV-SGRX-1, 2-HV-SGRX-2, 2-HV-SGRX-3, and 2-HV-SGRX-5 were declared inoperable fire barriers due to a 1/8" gap between the ducts and their respective ceiling interfaces.

Following an engineering evaluation to determine how to best seal the gaps, the gaps were sealed and the assemblies declared operable on December 8,

1989.

A fire watch, as required by Technical Specification 3.7.10 action a, was maintained while the barriers were inoperable.

In a previous letter dated November 13,

1989, we informed you that Fire Door 387, the Unit One Reactor Cable Tunnel Quadrant 42 door, was declared inoperable due to the failure of its latching mechanism.

The engineering evaluation of the necessary repairs determined that a design change is required to provide an adequate repair to the affected door.

The design change is now in progress.

We will inform you through a follow-up report when the design change is complete and the door has been restored to operability.

Respectfully, W~~ A.A. Blind Plant Manager See attached distribution