ML17326B512

From kanterella
Jump to navigation Jump to search
Special Rept:On 881219,fire Doors 392 & 386 Inoperable. Caused by Failure to Replace Screws Missing from Astragal Covering Gap Between Two Sections of Door Due to Time Needed to Obtain Certified Parts.Repair by 890215 Expected
ML17326B512
Person / Time
Site: Cook  
Issue date: 01/18/1989
From: Will Smith
INDIANA MICHIGAN POWER CO. (FORMERLY INDIANA & MICHIG
To:
NRC OFFICE OF ADMINISTRATION & RESOURCES MANAGEMENT (ARM)
References
NUDOCS 8901300170
Download: ML17326B512 (3)


Text

gCCEKRATED Dl%kIEtUTlON DEMONSTRallON SYSTEM REGULATORY INFORMATION DISTRIBUTION SYSTEM (RIDS)

ACCESSION NBR:8901300170 DOC.DATE: 89/01/18 NOTARIZED: NO DOCKET FACIL:50-315 Donald C.

Cook Nuclear Power Plant, Unit 1, Indiana 05000315 50-'316 Donald C.

Cook Nuclear Power Plant, Unit 2, Indiana 05000316 AUTH.NAME AUTHOR AFFILIATION SMITHgW.G.

Indiana Michigan Power Co. (formerly Indiana

& Michigan Ele RECIP.NAME RECIPIENT AFFILIATION Document Control Branch (Document Control Desk)

SUBJECT:

Special rept:on 890119,Fire Door 392 inoperable due to screws missing from astragal covering gap bewteen 2 doors.

DISTRIBUTION CODE:

IE22D COPIES RECEIVED:LTR

(

ENCL

+

SIZE:

TITLE: 50.73 Licensee Event Report (LER), Incident Rpt, etc.

NOTES:

RECIPIENT ID CODE/NAME PD3-1 LA STANGgJ INTERNAL: ACRS MICHELSON ACRS WYLIE AEOD/DSP/TPAB ARM/DCTS/DAB NRR/DEST/ADE 8H NRR/DEST/CEB 8H NRR/DEST/ICSB 7

NRR/DEST/MTB 9H NRR/DEST/RSB 8E NRR/DLPQ/HFB 10

'NRR/DOEA/EAB 11 NRR/DREP/RPB 10 NUDOCS-ABSTRACT RES/DSIR/EIB RGN3 FILE 01 COPIES LTTR ENCL 1

1 1

1 1

1 1

1 1

1 1

1 1

2 1

1 1

RECIPIENT ID CODE/NAME PD3-1 PD ACRS MOELLER AEOD/DOA AEOD/ROAB/DSP DEDRO NRR/DEST/ADS 7E NRR/DEST/ESB 8D NRR/DEST/MEB 9H NRR/DEST/PSB 8D NRR/DEST/SGB 8D NRR/DLPQ/QAB 10 NRR/DREP/RAB 10 NRR/DRIS/SIB 9A atz2Dah RES/DSR/PRAB COPIES LTTR ENCL 2

1 2

1 1

1 1

1 1

1 1

1 1

1 EXTERNAL: EG&G WILLIAMS,S H ST LOBBY WARD NRC PDR NSIC MAYS,G FORD BLDG HOYiA LPDR NSIC HARRIS,J NOrE 'IO ALL 'RIDSii RZCIPZam.

PZEASE HELP US 'IO REEKS HASTE!

CGNEACT IHE DOCUMERZ 02~L DESK RXN Pl-37 (EXT. 20079)

%0 ELOGNKS ACR NME PKN DISHtIHPZICN LISTS FOR DOCX1MENXB KXJ DCH'T NEZDl TOTAL NUMBER OF COPIES REQUIRED:

LTTR 45 ENCL

Indiana Viichigan Power Company Coo'i,,'i ~.. ear Pia;',

P.O Box 456 B~,dgvan MI 49106 6'6 6" 599i January 18, 1989 lNDlANA NlCHIGAN POEM Donald C.

Cook Nuclear Plant Units 1

2 Docket Nos.

50-315, 50-316 License Nos.

DPR-58, DPR-74 U.S. Nuclear Regulatory Commission Document Control Desk Washington, D'.C.

20555

Dear Mr. Davis:

Thi letter is to inform you that Fire Doors 392 and 386 have been inoperable longer than the seven days allowed by Technical, Specification 3.7.10 Action a.

Fire Door 392, separating fire zones 43 and 91, was declared inoperable on December 19, 1988 due to screws being missing from the astragal covering the gap between the two sections of the door.

,Due to the length of time required to obtain certified parts, the door was not repaired and declared operable until January 18, 1989.

At the time the door was declared inoperable, a

roving fire watch patrol was established as required by Technical Specification 3.7.10 Action a, and was maintained until the door was returned to operable status.

Fire Door 386, separating fire zones 39 and

34B, was declared inoperable on December 16, 1988 due to a broken closing device.

Due to the requirement'o use only certified parts for fire door repairs, we are having to wait until the required parts certification is obtained before completing repairs.

It is expected that this fire door will be repaired and returned to operable status by February 15, 1989.

At the time Fire Door 386 was declared inoperable a roving fire watch patrol was established as required by Technical Specification 3.7.10 Action a.

This fire watch patrol will remain in effect until the fire door can be returned to operable status.

Respectfully, W. G. Smith, J

Plant Manager Pg) 01 70

<DR ADO 0 890g48 CH 050003! 5 PgQ WGS:afh

D. H.-Williams, Jr.