ML17326B251

From kanterella
Jump to navigation Jump to search
Advises That 860522 Requested Changes to Bases Section of Tech Specs Re Definition & Frequency of Fire Watch Patrols Do Not Alter Intent of Tech Specs & Consistent W/Staff Discussions.Changes May Be Implemented
ML17326B251
Person / Time
Site: Cook  
Issue date: 07/15/1986
From: Youngblood B
Office of Nuclear Reactor Regulation
To: Dolan J
AMERICAN ELECTRIC POWER SERVICE CORP., INDIANA MICHIGAN POWER CO. (FORMERLY INDIANA & MICHIG
References
NUDOCS 8607220149
Download: ML17326B251 (9)


Text

. CPoR RFQI 0

A 4

O

~O

++*++

t UNITED STATES NUCLEAR REGULATORY COMMISSION WASHINGTON, D. C. 20555 i g JUL 1986 Docket Nos.:

50-315 and 50-316 Mr. John Dolan, Vice President Indiana and Michigan Electric Company c/o American Electric Power Service Corporation I Riverside Plaza

Columbus, Ohio 43216

Dear Mr. Dolan:

By letter dated May 22, 1986, the Indiana and Michigan Electric Company (IMEC) requested changes to the Bases sections of the Technical Specifications for the Donald C.

Cook Nuclear Plant, Unit Nos.

1 and 2.

These changes involve I) a definition of continuous fire watch, 2) a clarification of the frequency of patrol for an hourly fire watch patrol, and 3) a further addition to the de-finition of Operable for a fire-rated assembly and/or sealing device.

Me have evaluated each of the proposed changes and find that they do not change the intent of the Technical Specifications and are-Consistent with staff discussions on the issues.

The continuous fire watches at the D.C.

Cook Nuclear Plant have been assigned as one person to each of a number of fire zones within an area.

For a number of areas these fire zones are readily accessible and easily viewed by a single fire watch on a frequency of about every fifteen minutes.

This method of applying the fire watches will reduce the number of persons within the areas at a given time.

Because some zones have high radiation and the person is not required to be in the zone at all times, the exposures to fire watches may also be reduced.

The fifteen minutes patrol with a margin of five minutes is acceptable.

The change to clarify the frequency of the hourly fire watch patrols by defining the intervals as sixty minutes with a margin of fifteen minutes is consistent with other Technical Specification surveillance frequencies which allow margins of 25%.

This change is acceptable.

The last proposed change is to add to the definition of Operable for a fire-rated assembly and/or sealing device.

To the extent that these assemblies and sealing devices are capable of performing their intended safety function either auto-matically or manually each time they are opened, we find the proposed change acceptable provided that the failed component is repaired in a prudent and reasonable time period and the safety function is maintained.

Me believe this is explicit in the proposed change and therefore find it acceptable.

8b07220149 abo PDR ADQCI pD F

As we stated

above, we find the proposed changes to the bases sections do not change the intent of the Technical Specifications.

The changes may be im-plemented at the convenience of IHEC. If there are any questions on this

matter, please let us know.

Sincerely B.J.

You od, Director PWR Project Directorate 84 Division of PWR Licensing-A

Enclosure:

Unit I - Page B 3/4 7-8 Unit 2 - Pages B 3/4 7-7 and B 3/4 7-8

Mr. 'John Dolan Indiana and Michigan Electric Company Donald C.

Cook Nuclear Plant CC:

Mr. M. P. Alexich Vice President Nuclear Operations American Electric Power Service Corporation 1 Riverside Plaza

Columbus, Ohio 43215 Attorney General Depar tment of Attorney General 525 West Ottawa Street Lansing, Michigan 48913 Township Super visor Lake Township Hall Post Office Box 818 Bridgman, Michigan 49106 W. G. Smith, Jr., Plant Manager Donald C.

Cook Nuclear Plant Post Office Box 458 Bridgman, Michigan

49106, U.S. Nuclear Regulatory Commission Resident Inspectors Office 7700 Red Arrow Highway, Stevensville, Michigan 49127 H

Gerald Charnoff, Esquire Shaw', Pittman, Potts and Trowbridge, 1800 M St'rect, N.W.

, Washington, DC 20036,,

I I

Mayor,.City of Bridgeman Post Office Box 366 Bridgman, Michi'gan 49106 Special Assistant to the Governor Room 1 - State Capitol Lansing, Michigan 48909 Nuclear Facilities and;,Environmental Monitoring Section Office Division of Radiological Health Department of Public Health 3500 N. Logan Street Post Office Box 30035 Lansing, Michigan 48909 The Honorable John E. Grotberg United States House of Representatives Washington, DC 20515 Regional Administrator, Region III U.S. Nuclear Regulatory Commission 799 Roosevelt Road Glen El lyn, Illinois 60137 J. Feinstein American Electric Power Service Corporation 1 Riverside Plaza

Columbus, Ohio 43216

A,~

lt

~(

1'I 4

)

3/4.7.9 Cont.

The purpose of the charcoal filter fire suppression T/S is to account for detection and suppression of fires in the charcoal filters.

Manual operation of these systems is allowed because tvo-plaint heat detection with control room and local annunciation of trouble conditions is provided for the charcoal filters.

The OPERABILITY of the fire suppression system protecting the charcoal filters is only required vhen there is charcoal in the filters.

Actuation of spray water onto the charcoal filters requires both the manual opening of the system isolation valve and reaching the high temperature alarm setpoint for the automatic opening of the system deluge valve.

Because of the inaccessibility of the lover containment to personnel during operation due to ALARA radiation exposure concerns, the use of one or more CCTVs in the lower containment,.to monitor for fire and smoke, is an acceptable substitute to an hourly fire watch, if the fire suppression system becomes inoperable.

All hourly fire watch patrols are performed at intervals of sixty minutes with a margin of fifteen minutes.

A continuous fire watch requires that a trained individual be in the specified area at all times and that each fire zone within the specified area be patrolled at least once every fifteen minutes with a margin of five minutes.

3 4 7 0 I E

SSEHBL ES The OPERABILITY of the fi're barriers and barrier penetrations ensure that fire damage will be limited.

These design features minimize the possibility of a single fire involving more than one fire area prior to detection and extinguishment.

The fire barriers, fire barrier penetrations for conduits, cable trays and piping, fire dampers, and fire doors are periodically inspected to verify their OPERABILITY.

The ventilation seals are seals around ventilation duct work penetrating fire barriers.

For the purpose of determining OPERABILITY, an OPERABLE fire rated assembly and/or sealing device is one that is capable of performing its intended safety function.

D.

C.

COOK - UNIT l B 3/4 7-8 1$ JUg )886

o=".er tasks

{e."., an operator cn tour) provided >at such personnel ul illed the above sta=ed requirements.

As a minimum, each area affected by an isolated low pressure CO system must be visited every twenty-five (25) to thirty-five (35) 'minutes by the Roving Fire Watch Patrol.

Such measures will provide the necessary level of fire protection while affording necessary provisions for personnel safety.

In the event that portions of the fire suppression systems are inoperable, alternate backup fire fighting equipment is required to be made available in the affected areas until the inoperable equipment is restored to service.

When the inoperable fire-fighting equipment is intended for use as a

backup means of fire suppression, a longer period of time is allowed to provide an alternate means of fire fighting than if the inoperable equipment is the primary means of Xire suppression.

The surveillance requirements provide assurance that the minimum OPERABILITY requirements of the fire suppression systems are met.

An

-allowance is made for ensuring a sufficient 'volume of Halon and CO in the storage tanks by verifying either the weight, level, or pressure o$ the tanks.

In the event the fire suppression water system becomes &operable, immediate corrective measures must be taken since this system provides the major fire suppression capability of the plant~

The requirement for a twenty-four hour report to the Commission provides for prompt evaluation of the acceptability of the corrective measures to provide adequate fire suppression capability for the continued protection of the nuclear plant.

The purpose of the charcoal.filter fire suppression T/S is to account for detection and suppression of fires in the charcoal filters.

Hanual operation of these systems is allowed because two-point heat detection with control room and,local annunciation of trouble conditions is provided for the charcoal filters.

The OPERABILITY of the fire suppression system. protecting the charcoal filtersM only required when there is charcoal in the filters.

Actuation of spray water onto the charcoal filters requires both the manual opening of the system isolation valve and reaching the high temperature alarm setpoint for the automatic opening of the system deluge valve.

Because of the inaccessibility of the lower containment to personnel during operation due to ALARA radiation exposure

concerns, the use of one or more CCTVS in the lower containment to monitor for fire and smoke, is an acceptable substitute to a continuous fire watch, if the fire suppression system becomes inoperable.

All hourly fire watch patrols are performed at intervals of sixty minutes with a margin of fifteen minutes.

. A continuous fire watch requires that a trained individual be in the specif'ied area at all times and that each fire zone within the specified area is patrolled at least once every fifteen minutes with a margin of five minutes..

D.

C, COOK - UNIT 2 B 3/4 7-7

~s JUL 198>

B S

3/4.7.10 FIRE RATED ASSEMBLIES The OpERABILITY of the fire barriers and barrier penetrations ensures that fire damage will be limited.

These design features minimize the possibility of a single fire involving more than one fire area prior to detection and extinguishment.

The fire barriers, fire barr].er penetrations for conduits, cable trays and piping, fire dampers, and fire doors are periodically inspected to verify their OpERABILITY.

The ventilation seals are seals around ventilation duct work penetrating fire barriers.

For the purpose of determining OPERABILITY, an OPERABLE fire rated assembly/sealing device is one that is capable of performing its intended safety function.

D.

C.

COOK - UNIT 2 B 3/4 7-8

~

~ 15 JUL 1986 As we stated

above, we find the proposed changes to the bases sections do not change the intent of the Technical Specifications.

The changes may be im-plemented at the convenience of IMEC. If there are any questions on this

matter, please let us know.

Enclosure:

Unit 1 - Page B 3/4 7-8 Unit 2 - Pages B 3/4 7-7 and B 3/4 7-8 Sincerely, B.J.

Youngbl ood, Director PWR Project Directorate k'4 Division of PWR Licensing-A DISTRIBUTION:

NRC PDR Local PDR PWR84 Reading BJYoungblood Reading OELD EJordan BGrimes JPartlow DWigginton MDuncan ACRS(10)

PWR

/DPWR-A DWigginton/rad 071'86 PWgP/

PWR-A Rg /DPWR-A MDuhb BJYouggblood 07// /86 07/ID/86 J

lbaan 07/6/86

W>>

I W$ 'l' I

r l>>W

>>I 'J,'f wilt >>

P,W Wfl f

W ~ )

v'>>

'