Forwards LERs 79-061/03L-0 & 79-062/03L-0
Date released: 05/31/2018 Download: ML17326A400


LER 79-062/03L-0:on 791111,inoperable Steam Flow Channel 1 Taken Out of Trip Condition During Investigation of Channel Spec Reading.Caused by Incorrect Panel Indicator Labeling. Channel Placed in Trip Mode & Labeling Corrected
ML17326A402
Person / Time
Site: Cook American Electric Power icon.png
Issue date: 12/11/1979
From: Delong S
INDIANA MICHIGAN POWER CO.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
References
Download: ML17326A402 (3)
LER 79-061/03L-0:on 791111,during Startup,Steam Generator 4 Steam Flow Channel 1 Indicated 21% Lower than Redundant Channel.Caused by Oil Leak from Bellows to Transmitter Body Causing Drift Out of Spec.Transmitter Replaced