ML17325A913

From kanterella
Jump to navigation Jump to search
Notice of Violation from Insp on 880711-0808.Violation Noted:Negative Dc Ground Existed on Dc Ungrounded Battery Since 880102
ML17325A913
Person / Time
Site: Cook 
Issue date: 08/23/1988
From: Harrison J
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
To:
Shared Package
ML17325A912 List:
References
50-315-88-16, NUDOCS 8808300206
Download: ML17325A913 (1)


Text

NOTICE OF VIOLATION Indiana Nichi gan Power Company Docket No. 50-315 As a result of the inspection conducted on July 11-15, 18-22, 27, and August 8,

1988, and in accordance with 10 CFR Part 2, Appendix C - General Statement of Policy and Procedure for NRC Enforcement Actions (1987), the following violation was identified:

10 CFR 50, Appendix B, Criterion XVI, as implemented by the D.C.

Cook Operations equality Assurance

Program, Section 1.7. 16, requires that conditions adverse to quality be promptly corrected and action taken to preclude repetition of significant conditions adverse to quality.

Contrary to the above, a negative dc ground has existed on the Unit 1 250 V

dc normally ungrounded "CD" battery since January 2,

1988.

Action taken to preclude repetition was incomplete in that a comprehensive technical evaluation was not prepared to assure that the margin of safety had not been reduced for continued operations of safety-related equipment.

This is a Severity Level IV violation (Supplement I).

Pursuant to the provisions of 10 CFR 2.201, you are required to submit to this office within thirty days of the date of this Notice a written statement or explanation in reply, including for each violation:

(1) corrective action taken and the results achieved; (2) corrective action to be taken to avoid further violations; and (3) the date when full compliance will be achieved.

Consideration may be given to extending your response time for good cause shown.

Dated PU"23 BPS J.

J. Harrison, Chief Engineering Branch 8808300206 880823 PDR ADOCH, 050003iS G

PNU