Responds to NRC Ltr Re Violations Noted in Safety Insp Repts 50-315/86-30 & 50-316/86-30 on 860804-0908.Corrective Actions:Main Steam Safety Valve Setpoints Reset within Tech Spec Range.Procedure Will Be Modified
ML17324B142
Person / Time
Site: Cook  American Electric Power icon.png
Issue date: 11/07/1986
From: Alexich M
INDIANA MICHIGAN POWER CO. (FORMERLY INDIANA & MICHIG
To: James Keppler
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
References
AEP:NRC:1013, NUDOCS 8611250418
Download: ML17324B142 (3)


Text

e e

INDIANA8 MICHIGAN ELECTRIC COMPANY P.O. BOX 16631 COLUMBUS, OHIO 43216 November 7, 1986 AEP:NRC:1013 I

Donald C.

Cook Nuclear Plant Unit Nos.

1 and 2

Docket Nos.

50-315 and 50-316 License Nos.

DPR-58 and DPR-74 NRC INSPECTION REPORT NOS. 50-315/85030 (DRP)

AND 50-316/86030 (DRP)

Mr. James G. Keppler, Regional Director U.S. Nuclear Regulatory Commission Region III 799 Roosevelt Road Glen Ellyn, IL 60137

Dear Mr. Keppler:

This letter is in response to Mr. W.

G. Guldemond's letter dated October 8,

1986, which forwarded the report on the routine safety inspection conducted by members of your staff.

This inspection was conducted from August 4 through September 8,

1986 on activities at the D.

C.

Cook Nuclear Plant, Units 1 and 2.

The Notice of Violation attached to Mr. Guldemond's letter identified two viol'ations.

Violation one is addressed in the attachment to this letter.

The inspection showed that action had been taken to correct violation two and therefore, no reply is required.

This document has been prepared following Corporate procedures which incorporate a reasonable set of controls to insure its accuracy and completeness prior to signature by the undersigned.

Very truly yours M. P. Alexich Vice President

~<

MPA/cm Attachment, cc:

John E. Dolan W.

G. Smith, Jr.

- Bridgman R.

C. Callen G. Bruchmann G. Charnoff NRC Resident Inspector

- Bridgman Sbi gggo418 8b1 O1<< 5 pDR Aooch 05 pDR 8

2 0 1986

~c 0/

Attachment to AEP:NRC:1013 Page 1

Inspection Report 315/86030; 316/86030 NRC Violation "10 CFR 50.73 (a)(2)(ii) requires that the licensee submit a Licensee Event Report (LER) for any event or condition that resulted in the condition of the power plant, including its'rincipal safety barriers, being seriously

degraded, or that resulted in the power plant being:

(a) in an unanalyzed condition that significantly compromised plant safety; (b) in a condition that was outside the design basis of the plant; or (c) in a condition not covered by the plant's Operating and Emergency Procedures.

Unit 1 and 2

Technical Specifications require all safety relief valves operable in Modes 1 through 3.

Contrary to the above, the licensee did not submit a Licensee Event Report when a number of the Unit 1 and Unit 2 main steam safety relief valves, a

principle safety barrier, were found degraded during a Technical Specification surveillance test with the units in Mode 3."

Res onse to NRC Violation Corrective Action Taken and Results Achieved Upon discovery that several of the main steam safety valve setpoints were out of technical specification tolerance the immediate corrective action

taken, as required by procedure 12 HHP 4030.STP.002 "Hain Steam Setpoint Verficiation-Secondary System Safety Valve Setting",

was to reset the safety valves setpoints to within their specified ranges.

Licensee Event Reports were not submitted at the time the valves were found to be out of tolerence, for reasons explained in LER No. 86-020-00.

This event and the corrective actions have since been reported in detail in LER No. 86-020-00 submitted on September 24, 1986.

Corrective Action To Be Taken To Avoid Further Violations Procedure 12 HHP 4030.STP.002 will be modified prior to the next scheduled surveillance to include instructions on reportability.

In the future condition reports will be initiated as documentation of any safety valves failing to be in compliance.

Date When Full Com liance Achieved Full compliance was achieved on September 24, 1986 upon issuance of LER No.

86-020-00.