ML17320A847

From kanterella
Jump to navigation Jump to search
Advises That Review of Inservice Testing Programs Indicates Deletion of License Condition (3)(C) Unwarranted
ML17320A847
Person / Time
Site: Cook  
Issue date: 11/05/1983
From: Varga S
Office of Nuclear Reactor Regulation
To: Dolan J
AMERICAN ELECTRIC POWER SERVICE CORP., INDIANA MICHIGAN POWER CO. (FORMERLY INDIANA & MICHIG
References
NUDOCS 8311210002
Download: ML17320A847 (4)


Text

~

~

'ocket Nos., 50-315 and 50-316

+g 05.1983

',Docket'Fi-1 e' Wigginton C Pariish D Eisenhut OELD ACRS (10)

NRC.PDR Local PDR E Jordan J Taylor ORB gl Itr~Dphn.Dolan, Yice President Indiana and IIichigan Electric Company c/o Bmerican Electric Power Service Corporation 1 Riverside P'laza

Columbus, Ohio 43216 Dear Hr.

Dolan'n October 29, 1979 in letter.number )EP:HRC'.0259, Indiana and Michigan Electric Company requested that Hdense condition (3)(c) be deleted from Facility Opemting License DPR-74 for the. Donald C. Cook Nuclear.

Plant, Unit No..2.

This license condition requires that.the check valves providing pressure isolation protectioh of,low pressure 'safety system fr'om the full reactor pressure be periodically leak tested..

Since 'l980,.we have.per formed $ressure

'fpo'fation Valve (PIV) reviews for new plants and operating plants as they enter.ed. the Inservice.Testing. (IST) review.

The requirement to leak test PIVs has.been retained and has been put into each plant's Technical Specifications.

tte are currently reviewing the Donald C. Cook Nuclear Plant IST.programs and it is our intent.to include the PIY issue in that geview.

Therefore, vie will not remove the license condition at this time.

ll In. the near future we expect to begin disc0ssions on the IST review. If you wish to pursue the PIY issue further, we will be glad to do so as part of that review.

Sincerely, ccrc See next page Steven.A. Yarga, Chief.

Operating Reactors Branch I'Jo.

1 Division of Licensing 8311210002 831105 PDR ADOCK 05000315 p

PDR ORBgl

~

~ 0 ~ ~ ~ ~ ~ ~ 0 ~\\

AHigg.lnt.on;.e

.uR J.c.~......

ORBgl OFFICEIW SURNAME$

~ ~ ~ ~ ~ 1 ~

DATE$

~

~

~

~

~ ~ ~ ~ ~

~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~I~ 0 ~ ~ ~ ~ ~ ~ ~ ~ ~ ~

NRG FORM 318 (10-80) NRCM 0240 OFFICIAL RECORD COPY USGPO: 1981~~960

-4 3hag Ifl 0

~

".:;iaan

"- lec.ric Company cc:

Mr, M.

P. Rlexich Vice President-Nuclear Engineering American Electric Power Service Corporation l Riverside Plaza

Columbus, Ohio 43215 Gerald Charnoff, Esquire
Shaw, Pi ttman, Potts and Trowbridge

)S00 M Street, N.W.

l'ashington, D.

C.

20036 M.

G. Smith Jr., Plant Manager Donald C.

Cook Nuclear Plant P.

0.

Box 458 Bridgnan, Michigan 4910'6 U.

S. Nuclear Regulatory Commission Residen-Inspectors Office 7700 Red Arrow Highway Stevensville, Michigan 49127 The. Honorable Tom Corcoran United States House of Representatives Washington, D.

C.

20515 James G.

1;eppler Reqioia: Administrator - Region III U.

S.

N clear Regulatory Commission 799 Roosevelt Road Glen E 1 lyn, I 1 1 inoi s 60137

ta II