ML17319B465

From kanterella
Jump to navigation Jump to search
Forwards Franklin Research Ctr Request for Addl Info Per IE Bulletin 80-11 Re Masonry Wall Const.Assumptions,Modeling Techniques & Procedures Used in Analysis Should Be Described.Info Requested by 820823
ML17319B465
Person / Time
Site: Cook  
Issue date: 07/13/1982
From: Varga S
Office of Nuclear Reactor Regulation
To: Dolan J
INDIANA MICHIGAN POWER CO. (FORMERLY INDIANA & MICHIG
References
IEB-80-11, NUDOCS 8207300040
Download: ML17319B465 (10)


Text

JUL 13 198K Docket. Nos. 50-315 and 50-316 f<r. John Dolan, Vice President Indiana and ffichigan Electric Company Post Office Box 18 Bowling Green Station New York, New York 10004 DISTRIBUTION

>Docket File NRC PDR Local PDR ORB 1 File D. Eisenhut OELD OISE (1)

R. Cilimberg C. Parrish RZXKIIK)IIIIIII NSIC ACRS (10)

J.

Heltemes FRC (w/o encl)

Dear tlr. Dolan:

SUBJECT:

IE BULLETIN80-11 MASONRY HALL CONSTRUCTION In our review of D. C.

Cook 1

8 2 responses to IE Bulletin 80-11, we have identified additional information which we will need in order to complete our review.

Franklin Research Center under contract to the NRC has developed the enclosed request for additional information.

He request that you provide the information by August 23, 1982.

This request for information is in accordance with the Ot<B Clearance No. 3150-0065, which expires Hay 31, 1983.

Sincerely, ggiginal signed by P, A. Varga Steven A. Varga, Chief Operating Reactors Branch No.

1 Division of Licensing

Enclosure:

As stated cc:

See next page

'a07SO0040 Sa07lS PDR ADOCK 05000315 8

PDR OFFICEI SURNAME/

DATE Q ORB

'RC'I'I'llfib'5i'gf 7//0L/82

~

~ ~

~

Io ~ 0

~ ~ ~Opt

~ 0

~\\ ~ ~ ~ 0

~ ~ ~ ~ ~ ~ 0 ~ 0 ~ ~ ~ ~ ~ ~ ~ 0 ~ 0 ~ ~ ~ 0 ~

~ 0 ~ ~ 0 ~ ~ 0 ~ ~ 0 ~ 0 ~ 0 ~ 0 ~ ~ ~ ~ 0 ~ ~

~ 0 ~ ~ 0 ~ 0 ~ 0 ~ 000 ~ 0 ~ 00 ~ 0 ~ 0 ~ 0 NRC FORM 318 (1040) NRCM 0240 OFFICIAL RECORD COPY

~~

t 4'

y"f

~

~

E i

II I

P 1

I

~ '

J E

~"

i 4

t I

r Ig 0

Mr. JoKn Dolan Indiana and Michigan Electric Company cc:

Mr. Robert W. Jurgensen Chief Nuclear Engineer American Electric Power Service Corporation 2 Broadway New York, New York 10004 Gerald Charnoff, Esquire Shaw, Pittman,,Potts and Trowbridge 1800 M Street, N.W.

Washington, D. C.

20036 Maude Preston Palenske Memorial Library 500 Market Street St. Joseph, Michigan 49085 W.

G. Smith, Jr., Plant Manager Donald C. Cook Nuclear Plant P. 0.

Box 458 Bridgman, Michigan 49106 U. S. Nuclear Regulatory Commission Resident Inspectors Office 7700 Red Arrow Highway Stevensville, Michigan 49127 William J. Scanlon, Esquire 2034 Pauline Boulevard Ann Arbor, Michigan 48103 The Honorable Tom Corcoran United States House of Representatives Washington, D. C.

20515 James G. Keppler Regional Administrator - Region III U. S. Nuclear Regulatory Commission 799 Roosevelt Road Glen El lyn, Illinois 60137

gV p1 l

~ <

I

j TECHNICAL EVALUATION An evaluation based on the information available in References 2, 3, 4, and 5 was conducted and the following concerns were identified:

the Licensee response to IE Bulletin 80-11 must be more thorough to facilitate proper evaluation.

A more detailed discussion of the Licensee's reevaluation criteria is needed.

The discussion should cover in detail all analytical approaches and assumptions, and address such topics as allowable stresses and load combinations.

Before a final technical evaluation report can be issued, the Licensee is requested to provide the., following information:

l.

Describe the assumptions, modeling techniques, and procedures used in the analysis.

2.

Specify the number of modes of vibration considered in the seismic analysis and show how the effect of higher modes of vibration has been considered.

3.

Indicate how earthquake forces in three directions were considered in the analysis.

4.

Indicate how the seismic analysis accounted for variations of frequency due to uncertainties in mass, materials, and other parameters used.

5.

Specify material types used and provide values of 'allowable stresses for masonry, mortar, grout, and reinforcement.

6.

Regulatory Guide 1.61 allows 4% damping for the operating basis earthquake (OBE) and 7% dumping for the safe shutdown earthquake (SSE).

Provide the damping values used in the analysis and justify them if they are higher than those allowed in Regulatory Guide 1.61.

7.

Provide any increase factors that may have been used for allowable stresses under abnormal conditions.

If they are higher than those factors listed in the SEB criteria [6], provide justification.

The SEB factors are listed below by type of stress.

Axial or flexural compression Bearing Reinforcement stress except shear Shear reinforcement and/or bolts Masonry tension parallel to bed joint.

Shear carried by masonry Masonry tension perpendicular to bed joint reinforced masonry unreinforced masonry 2.5 2.5 2.0 but not,.to exceed,0.9 fy 1.5 1.5 1.3 0

1.3 8.

Indicate the boundary conditions used for analyzing the masonry walls and provide justification for those boundary conditions.

9.

Indicate if the cracking of sections of the walls was given proper consideration in the analysis.

I%~'

10.

Provide information on loads and load combinations applicable to masonry walls.

Describe how interstory drift (both in-plane and out-of-plane) was accounted for.

12.

Provide information on construction practices and the availability of relevant quality assurance/quality control records to justify the use of allowable stresses applicable to the Special Inspection Category.

13.

Indicate whether the walls are stack bond or running bond.

If any stack bond wall exists, provide sample calculations to obtain moment and shear stress of a typical wall.

14.

Indicate how wall attachments (equipments, pipes) were considered in the analysis.

15.

Provide sample calculations for:

o Block pullout analysis o

Missile impact.

16.

With reference to the multiple wythes, clarify whether the collar joint strength was used in the analysis.

If so, justify the values used.

Also, on page 2 of Reference 2, the Licensee explained that when duro-wall reinforcing has not been used, the wall strength is a multiplication of a single wythe.

Explain how shear and tension can be transferred along, the collar joint so that the wall strength is a multiplication of single wythe strength.

Also, provide a sample calculation.

17.

Indicate if any nonlinear technique was used in the analysis.

If so, provide justification for its use.

If any existing test data are used to justify the technique, the applicability of the tests should be discussed for the following areas:

Nature of the loads Boundary conditions Materials used Wall sizes Amount and distribution of reinforcement.

18.

Provide the number of walls which are unreinforced.

Also, provide a

sample calculation illustrating how tension,

shear, and displqcement were obtained.

19 ~

Provide detailed drawings of the modifications used.

Also provide a sample calculation to illustrate that the modified wall will be qualified under the working stress design condition.

IJ/I) Franklin Research Center A 5vl~illAAID C

w I,:~...

f

5.

MFERENCES 1.

"Masonry Wall Design" NRC, 08-May-81 IE Bulletin 80-11 2.

G.

P.

Maloney (Indiana

& Michigan Electric Company)

Letter with attachment to J.

G. Keppler (NRC)

Sub3ect:

Response

to IE Bulletin 80-11, Masonry Wall Design July 10, 1980 3.

R.

S. Hunter (Indiana

& Michigan Electic Company)

Letter to J.

G. Keppler (NRC)

Subject:

Interim Supplemental

Response

to IE Bulletin 80-11 March 20, 1981 4.

R.

S. Hunter (Indiana

& Michigan Electric Company)

Letter to J.

G. Keppler (NRC)

Subject:

Supplemental

Response

to IE Bulletin 80-11 January 14, 1981 5.

R. S. Hunter (Indiana

& Michigan Electric Company)

Letter with attachments to James G. Keppler (NRC)

Subject:

Final Report'f the Description of Design Modifications and Plant Changes October 30, 1981 6.

Standard Review Plan, Section 3.8.4, Appendix A "Interim Criteria for Safety-Related Masonry Wall Evaluation" NRC, July 1981 7.

Uniform Building Code International Conference of Building Officials, 1979 8.

"Building Code Requirements for Concrete Masonry Structures" American Concr e te Institute, 1979 ACI 531-79 and Commentary ACI 531R-79 9.

Standard Review Plan, Section 3.7.2 "Seismic System Analysis" NRC, July 1981

-'-~'ranklin Research Center li"i'Ii

)

n E.