ML17317B322

From kanterella
Jump to navigation Jump to search
Forwards Suppl IE Bulletin 79-01A, Environ Qualification of Class IE Equipment (Deficiencies in Environ Qualification of Asco Solenoid Valves). Action Required
ML17317B322
Person / Time
Site: Cook  
Issue date: 06/06/1979
From: James Keppler
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
To: Dolan J
INDIANA MICHIGAN POWER CO.
References
NUDOCS 7907190272
Download: ML17317B322 (9)


Text

CENTRAL FILES JUN 6 t979 Docket No. 50-31 Docket No.

- 16 American Electric Power Service Corporation Indiana and Michigan Power Company ATTN:

Mr. John E. Dolan, Vice Chairman Engineering and Construction 2 Broadway New York, NY 10004 Gentlemen:

Enclosed is supplement IE Bulletin No. 79"01A. It requires action by you with regard to power reactor facilities with an operating license except for the ll SEP plants which are listed in Enclosure 3.

This Bulletin is also being sent for information to the ll SEP plants and all power reactor facilities with a construction permit.

No action or written response is required for construction permit facilities or the ll SEP plants.

Should you have questions regarding this Bulletin or the actions required of you, please contact this office.

Sincerely, James G. Keppler Director

Enclosure:

IE Bulletin No.79-01A cc w/encl:

Mr. D. V. Shaller, Plant Manager Central Piles

Director, NRR/DPM
Director, NRR/DOR PDR Local PDR NSIC TIC Ronald Callen, Michigan Public Service Commission Citizens for a Better Environment RIII RIII Hei n/blk Keppler 6/4/79

+(+

0 U.S.

NUCLEAR REGULATORY COMMISSION OFFICE OF INSPECTION AND ENFORCEMENT REGION III June 6,

1979 IE Bulletin No.79-01A SUPPLEMENT NO.79-01A TO IE BULLETIN 79-01 ENVIRONMENTAL QUALIFICATION OF CLASS 1E EQUIPMENT (DEFICIENCIES IN THE ENVIRONMENTAL QUALIFICATION OF ASCO SOLENOID VALVES)

Description of Circumstances:

Recently, a noncompliance report under 10 CFR Part 21 was received by the NRC from the Henry Pratt Company, manufacturer of butterfly valves which are installed in the primary containment at the Three Mile Island Unit 2 Nuclear Station.

These butterfly valves are used for purge and exhaust purposes and are required to operate during accident conditions.

The report discusses the use of an unqualified solenoid valve for a safety-related valve function which requires operation under accident conditions.

The solenoid valve in question is Catalogue No. HT-8331A45, manufactured by the Automatic Switch Company (ASCO) of Florham Park, New Jersey.

This pilot valve is used to pilot control the pneumatic valve actuators which are installed on the containment ventila-tion butterfly valves at this facility.

The deficiency in these solenoid valves identified in the Part 21 Report concerns the parts made of acetal plastic material.

The acetal disc holder assembly and bottom plug in the pilot valve assembly are stated by ASCO to have a maximum service limit of 400,000 Rad integrated dosage and 200 degrees F

temperature.

According to ASCO, exposure of these acetal plastic parts to specified maximum environmental conditions may render the solenoid pilot valve inoperable which would cause the associated butterfly valve to malfunction.

Further investigation at ASCO by the NRC staff has revealed that the valve seals in most ASCO solenoid valves contain Buna "N" elastomer material, which reportedly has a maximum service limit of 7,000,000 Rad integrated dosage and 3.80 degrees F temperature.

The investigation further revealed that ASCO has available a line of qualified solenoid operated pilot valves (ASCO Catalogue No. NP-2) which have no plastic parts, utilize ethylene propylene or viton elastomers and have a continuously energized operating life of four years, under normal ambient conditions up to 140 degrees F.

According to the manu-facturer, at the end of this period, the coil, manual operator (optional fea-ture) and all resilient parts must be replaced.

These preventive maintenance instructions are specified in the installation and instruction bulletins which are provided to the purchaser with each shipment of solenoid valves.

The final items of concern identified during this investigation deals with the application'f Class "A", "B", or "F", solenoid coils which are exposed to an accident environment.

In this regard, ASCO representatives stated that the

IE Bulletin No.79-01A June 6,

1979 high temperature coils identified as Class "HT" or "HB" are the only coils con-sidered suitable for service under accident conditions;

whereas, Class "A", "B",

and "F" coils are not.

With respect to the corrective measures to be taken to resolve the above concerns, ASCO recommends the following:

1.

The parts of the solenoid valve made of acetal plastic material should be replaced with similar parts made of metal which can be provided by ASCO.

2.

The valve seals and gaskets which are made of Buna "N" material should be replaced with either ethylene propylene or viton elastomers, considered by ASCO as suitable for the service intended.

3.

Review and determine that the coils of the solenoid valves installed inside containment are Class "HT" or "HB" as required for high temperature environmental conditions.

4.

Review and determine that the solenoid enclosures installed inside contain-ment have at least a

NEMA 4 enclosure rating.

5.

Establish a preventive maintenance program to assure replacement of those valve parts identified above in the time period recommended in the appro-priate ASCO valve bulletin.

6.

ASCO also stated that all unqualified solenoid valves inside containment be retrofitted to qualified ASCO No. NP-1 valves in lieu of the above.

7.

Questions from licensees to ASCO concerning corrective measures should reference both catalogue and serial numbers of each valve in question.

These numbers are stamped on the metal nameplate on each solenoid valve.

Action to be Taken by Licensees of all Power Reactor Facilities (except those ll SEP Plants listed on Enclosure

3) with an Operating License:

1.

Determine whether or not ASCO solenoid valves are used or planned for use in safety-related systems at your facility(ies).

2.

If such valves are used or planned for use, identify the safety system involved and determine that:

(a) valves which could be sub)ected to a LOCA environment are qualified to that environment.

Specifically -that no parts made of acetal plastic'or Buna "N" materials or Class "A">

B or "F" solenoid coils are used in such valves; (b) a preventive main-tenance program is being conducted such that the solenoid coil, the manual operator (if applicable),

and the resilient parts of the valve are being replaced in accordance with the time period established by the manufacturer and documented as the qualified life of the assembled component.

IE Bulletin No.79-01A June 6, 1979 3.

All holders of operating licenses of power reactor facilities are obligated to meet the review and reporting requirements established in previously issued IE Bulletin 79-01, regarding environmental qualifica-tion of electrical equipment installed in their plants.

No additional written response to this Supplement IE Bulletin is required other than those responses described above.

NRC inspectors will continue to monitor the licensees'rogress in completing the requested action described above.

If additional information is required, contact the Director of the appropriate NRC Regional Office.

Approved by GAO, B180225 (R0072); clearance expires 7/31/80.

Approval was given under a blanket clearance specifically for identified generic problems.

Enclosures:

1.

List of IE Bulletins Issued in the past 12 months 2.

List of SEP Plants (ll)

IE Bulletin No.79-01A June 6,

1979 LISTING OF IE BULLETINS ISSUED IN LAST TWELVE MONTHS Bulletin Subject No.

Date Issued Issued To 79-Q Short Period Scrams at BWR Facilities 5/31/79 All GE BWR Facilities with an OL 79-11 Faulty Overcurrent Trip Device in Circuit Breakers for Engineered Safety Systems 5/22/79 All Power Reactor Facilities with an OL or a CP 79-10 79-09 79-08'equalification Training Program Statistics Failures of GE Type AK-2 Circuit Breaker in Safety Related Systems Events Relevant to BWR Reactors Identified During Three Mile Island Incident 5/11/79 4/17/79 4/14/79 All Power Reactor Facilities with an OL All Power Reactor Facilities with an OL or CP All BWR Power Reactor Facilities with an OL 79-07 Seismic Stress Analysis of Safety-Related Piping 4/14/79 All Power Reactor Facilities with an OL or CP 79-06B Review of Operational Errors and System Mis-alignments Identified During the Three Mile Island Incident 4/14/79 All Combustion Engineer-ing Designed Pressurized Water Power Reactor Facilities, with an Operating Licensee 79-06A (Rev 1)

Review of Operational Errors and System Mis-alignments Identified During the Three Mile Island Incident 4/18/79 All Pressurized Water Power Reactor Facilities of Westinghouse Design with an OL 79-06A Review of Operational Errors and System Mis-alignments Identified During the Three Mile Island Incident 4/14/79 All Pressurized Water Power Reactor Facilities of Westinghouse Design with an OL Enclosure Page 1 of 3

a IE Bulletin No.79-01A June 6,

1979 Bulletin Subject No.

LISTING OF IE BULLETINS ISSUED IN LAST TWELVE MONTHS Date Issued Issued To 79-06 79-05A 79-05 79-04 79-03 79-02 Review of Operational Errors and System Mis-alignments Identified During the Three Mile Island Incident Nuclear Incident at Three Mile Island Nuclear Incident at Three Mile Island Incorrect Weights for Swing Check Valves Manufactured by Velan Engineering Corporation Longitudinal Welds Defects In ASME SA-312 Type 304 Stainless Steel Pipe Spools Manufactured by Youngstown Welding and Engineering Co.

Pipe Support Base Plate Designs Using Concrete Expansion Anchor Bolts 4/11/79 4/5/79 4/2/79 3/30/79 3/12/79 3/2/70 All Pressurized Water Power Reactors with an OL except B&W facilities All B&W Power Reactor Facilities with an OL All Power Reactor Facilities with an OL and CP All Power Reactor Facilities with an OL or CP All Power Reactor Facilities with an OL or CP All Power Reactor Facilities with an OL or CP 79-01 Environmental Qualification 2/8/79 of Class IE Equipment All Power Reactor Facilities with an OL or CP 78-14 78-13 Deterioration of Buna-N Component In ASCO Solenoids Failures in Source Heads of Kay-Ray, Inc.,

Gauges models

7050, 7050B,
7051, 7051B~

7060 j 7060B~

7061 and 7061B 12/19/78 10/27/78 All GE BWR facilities with an OL or CP All general and specific licensees with the subject Kay-Ray, Inc.

gauges Enclosure Page 2 of 3

IE Bulletin No.79-01A June 6,

1979 LISTING OF IE BULLETINS ISSUED IN LAST TWELVE MONTHS Bulletin No.

Subject Date Issued Issued To 78-12B Atypical Weld Material in Reactor Pressure Vessel Welds 3/19/79 All Power Reactor Facilities with an OL or CP 78-12A Atypical Weld Material in Reactor Pressure Vessel Welds 11/24/78 All Power Reactor Facilities with an OL or CP 78-12 Atypical Weld Material in Reactor Pressure 7essel Welds 9/29/78 All Power Reactor Facilities with an OL or CP 78-ll Examination of Mark I Containment Torus Welds 7/21/78 BWR Power Reactor Facilities for action:

Peach Bottom 2 and 3, Quad Cities 1 and 2, Hatch 1, Monticello and Vermont Yankee 78-10 Bergen-Paterson Hydraulic 6/27/78 Shock Suppressor Accumulator Spring Coils All BWR Power Reactor Facilities with an OL or CP 78-09 BWR Drywell Leakage Paths 6/14/79 Associated with Inadequate Drywell Closures All BWR Power Reactor Facilities with an OL or CP

'78-08 Radiation Levels from Fuel 6/12/78 Element Transfer Tubes All Power and Research Reactor Facilities with a Fuel Element transfer tube and an OL 78-07 Protection afforded by Air-Line Respirators and Supplied-Air Hoods 6/12/78 All Power Reactor Facilities with an OL, all class E and F Research Reactors with an OL, all Fuel Cycle Facilities with an OL, and all Priority 1

Material Licensees Enclosure Page 3 of 3

-.SEP Plants Plant Dresden 1

Region Yankee Rowe Big Rock Point San Onofre 1

Haddam Neck LaCrosse Oyster Creek R.

E. Ginna Dresden 2

Millstone Palisades V

Enclosure Page 1 of 1

j>>

P Cl