LER 79-028/03L-0 on 790410:torque Required to Open Lower Ice Condenser Inlet Door 3-R Exceeded Tech Specs.Caused by Sheet Metal Screws Loose at Bottom of Door.Door Frame Edge Depressed
ML17317B187
Person / Time
Site: Cook 
Issue date: 05/09/1979
From: Beilman T
INDIANA MICHIGAN POWER CO.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
References
Download: ML17317B187 (2)
LER 79-027/03L-0 on 790416:during Refueling W/Emergency Diesel Generator AB inoperable,600 Volt Bus 11D Made Inoperable by Removal of Normal Feed Breaker T1112 for Cleaning.Caused by Personnel Error.Operators Reinstructed
ML17317B186
Person / Time
Site: Cook 
Issue date: 05/09/1979
From: Lease R
INDIANA MICHIGAN POWER CO.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
References
Download: ML17317B186 (2)
LER 79-019/03L-0 on 790413:while Performing Hydraulic Snubber Surveillance Insp,Snubbers GBD-S573 & GBD-S574 Found W/Drained Reserviors.Caused by Loose Pipe Unions Between Snubbers & Remote Reservoirs.Snubbers Replaced
ML17317B185
Person / Time
Site: Cook 
Issue date: 05/09/1979
From: Michael Brown
INDIANA MICHIGAN POWER CO.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
References
Download: ML17317B185 (2)
Forwards LERs 79-019/03L-0,79-027/03L-0 & 79-028/03L-0
ML17317B182
Person / Time
Site: Cook 
Issue date: 05/09/1979
From: Shaller D
INDIANA MICHIGAN POWER CO.
To: KEPPLER J G
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
References
Download: ML17317B182 (1)