ML17308A216

From kanterella
Jump to navigation Jump to search
Ack Receipt of 831123 & s Informing NRC of Steps Taken to Correct Violations Noted in Insp Repts 50-389/83-57,50-389/84-01 & 50-389/86-02.Corrective Actions for Sprinkler Sys Obstructions Requested within 30 Days
ML17308A216
Person / Time
Site: Saint Lucie 
Issue date: 04/25/1986
From: Reyes L
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
To: Woody C
FLORIDA POWER & LIGHT CO.
References
NUDOCS 8605060262
Download: ML17308A216 (3)


See also: IR 05000389/1983057

Text

Florida Power

and Light Company

ATTN:

Mr. C. 0.

Woody

Group Vice President

Nuclear Energy Department

P. 0.

Box 14000

Juno

Beach,

FL

33408

Gentlemen:

SUBJECT:

REPORT

NOS. 50-389/83-57,

50-389/84-01

AND

0- 89/86-02

During our routine inspection of St. Lucie Unit 2 on September

6-9,

1983,

we

identified an apparent

deviation from your commitments to the Commission involv-

ing the automatic sprinkler systems

installed within the Unit 2 auxiliary build-

ing.

The principal concern

was the obstructions

to the ceiling level sprinkler

systems.

This is identified as Deviation 389/83-57-01.

Your letters of November 23,

1983 and March 14, 1984, did not concur with this

finding.

Therefore,

as noted

by our letter to you of April 5,

1984,

we forwarded

your response

to our Office of Nuclear Reactor Regulation for an evaluation.

t

NRC's evaluation indicates that the sprinkler systems

located in plant fire areas

containing redundant

safe

shutdown divisions should provide sufficient protection

to assure

that one shutdown division would remain free from damage

in the event

of fire.

To accomplish this objective requires

portions of the existing systems

at St. Lucie 2 to be modified by the installation of additional sprinkler heads,

relocation of existing heads

beneath

obstructions

or removal of the obstructions.

For fire areas

where only one shutdown train exists,

the present configuration is

considered

acceptable.

A copy of this evaluation is enclosed for your informa-

tion.

Therefore,

we would appreciate

your response

to us within 30 days

from your

receipt of this letter

as to the corrective actions which will be taken to

correct this deviation

and the date your corrective actions will be completed.

Should you have any questions

concerning this letter,

we will be glad to discuss

them with you.

Sincerely,

Original Signed by

Luis A. Reyes

~

~

~

Enclosure:

Evaluation of Fire Protection

Sprinkler Systems

cc w/encl:

(See

page

2)

Luis A. Reyes,

Deputy Director

Division of Reactor Projects

8605060262

860425

PDR

ADGCK 05000389

8

PDR

orida Power and Light Company

e

gpss

2 5

1986

~

~

~

cc w/encl:

K. N. Harris, Yice President

~

~

jb

A. Sager,

Plant Manager

at Weems,

gA Superintendent

~

~

bcc w/encl:

k F. Miraglia, NRR/PWRB

<D. Sells,

NRR/PWRB

D. Kubicki, NRR/PWRB

A. Herdt, RII

. Elrod, RII

. Conlon, RII

. Miller, RII

P. Madden, RII

G. Wiseman, RII

RC Resident

Inspector

Document Control

Desk

State of Florida

e

R

WMil r:pj

4/

/86

TCon on

4/if /86

RIby

AHA dt

4/g /86

ibson

4/~/86

RII

DVerrel 1 i

4/g.3j86