Notification of 930216 Meeting W/Licensee in Rockville,Md to Discuss NRC Staff Questions Re Licensee Proposal to Change Review Level Earthquake from 0.5g to 0.3g
ML17306B269
Person / Time
Site: Palo Verde  
Issue date: 02/01/1993
From: Trammell C
Office of Nuclear Reactor Regulation
To: Quay T
Office of Nuclear Reactor Regulation
References
NUDOCS 9302040073
Download: ML17306B269 (14)


Text

February 1,

1993 Docket Nos.

50-528, 50-529 and 50-530 MEMORANDUM FOR:

FROM:

SUBJECT:

DATE & TINE:

LOCATION:

PURPOSE:

Theodore R. Quay, Director Project Directorate V

Division of Reactor Projects III/IV/V Charles H. Trammell, Senior Project Manager Project Directorate V

Division of Reactor Projects III/IV/V FORTHCOMING HEETING WITH ARIZONA PUBLIC SERVICE COMPANY (PALO VERDE NUCLEAR GENERATING STATION)

Tuesday, February 16, 1993 9:00am - ll:45am U.S.

NRC Headquarters One White Flint North 11555 Rockville Pike Rockville,, Maryland 20852 Room 2F21 To discuss the NRC staff questions regarding the licensee's proposal to change the review level earthquake from 0.5g to 0.3g.

PARTICIPANTS*:

NRC C. Trammell L. Tran B.

Rothman G. Giese-Koch D. Wheeler A. Hurphy N. Chokshi E. Zurflueh R. Hernan J.

Chen APS G. Michael D.

Fan G.

Pod A. Dutt J. Fisher R. HcGuire R. Sewell R.

Kennedy cc:

See next page Original signed by Charles H. Trammell, Senior Project Manager Project Directorate V

Division of Reactor Projects III/IV/V

  • Meetings between NRC technical staff and applicants or licensees are open for interested members of the public, petitioners, intervenors, or other parties to attend as observers pursuant to "Open Meeting Statement of NRC Staff Policy," 43 Federal Re ister 28058, 6/28/78.

DISTRIBUTION:

See next page OFC PDV LA 9302040073 3020i t

i,', ',:,,

-'!'DR ADQCK 05000528 P

9 PDR)

PDV D

NAME DATE DFoster 93 ammell:lh 93 TQuay

>L 93 OFFICIAL, RECORD COPY DOCUMENT NAME:PVMTG.NOT

~p,R REGNI

~o

+

fl C

O p

Vl 0>

+0

+**++

UNITED STATES NUCLEAR REGULATORY COMMISSION WASHINGTON, D.C. 20555 February 1,

1993 Docket Nos. 50-528, 50-529 and 50-530 MEMORANDUM FOR:

FROM:

SUBJECT:

DATE 5 TIME:

LOCATION:

PURPOSE:

Theodore R. quay, Director Project Directorate V

Division of Reactor Projects III/IV/V Charles H. Trammell, Senior Project Manager

'Project Directorate V

Division of Reactor Projects III/IV/V FORTHCOMING MEETING WITH ARIZONA PUBLIC SERVICE COMPANY (PALO VERDE NUCLEAR GENERATING STATION)

Tuesday, February 16, 1993 9:00am ll:45am U.S.

NRC Headquarters One White Flint North 11555 Rockville Pike Rockville, Maryland 20852 Room 2F21 To discuss the NRC staff questions regarding the licensee's proposal to change the review level earthquake from 0.5g to 0.3g.

PARTICIPANTS*:

NRC C. Trammell L. Tran B.

Rothman G. Giese-Koch D. Wheeler A. Murphy N. Chokshi E. Zurflueh R. Hernan J.

Chen APS G. Michael D.

Fan G.

Pod A. Dutt J. Fisher R. McGuire R. Sewell R. Kennedy cc:

See next page va. p Charles H. Trammell, Senior Project Manager Project Directorate V

Division of Reactor Projects III/IV/V

  • Meetings between NRC technical staff and applicants or licensees are open for interested members of the public, petitioners, intervenors, or other parties to attend as observers pursuant to "Open Meeting Statement of NRC Staff Policy," 43 Federal Re ister 28058, 6/28/78.

Arizona Public Service Company Palo Verde CC:

Nancy C. Loftin, Esq.

Corporate Secretary 8 Counsel Arizona Public Service Company P. 0.

Box 53999, Mail Station 9068

Phoenix, Arizona 85072-3999 James A. Beoletto, Esq.

Southern California Edison Company P. 0.

Box 800

Rosemead, California 91770'enior Resident Inspector U.S. Nuclear Regulatory Commission HC-03 Box 293-NR Buckeye, Arizona 85326 Regional Administrator, Region V

U. S. Nuclear Regulatory Commission 1450 Maria Lane Suite 210 Walnut Creek, California 94596 Mr. Charles B. Brinkman, Manager Washington Nuclear Operations ABB Combustion Engineering Nuclear Power 12300 Twinbrook Parkway, Suite 330 Rockville, Maryland 20852 Mr. William A. Wright, Acting Director Arizona Radiation Regulatory Agency 4814 South 40 Street

Phoenix, Arizona 85040 Chairman Maricopa County Board of Supervisors ill South Third Avenue
Phoenix, Arizona 85003 Jack R.
Newman, Esq.

Newman 5, Holtzinger, P.C.

1615 L Street, N.W., Suite 1000 Washington, D.C.

20036 Curtis Hoskins Executive Vice President and Chief Operating Officer Palo Verde Services 2025 N. 3rd Street, Suite 220 Phoenix, Arizona 85004 Roy P.

Lessey, Jr.,

Esq.

Bradley W. Jones, Esq.

Arkin, Gump, Strauss, Hauer and Feld El Paso Electric Company 1333 New Hampshire Ave.," Suite 400 Washington, D.C.

20036 Mr. William F.

Conway Executive Vice President, Nuclear Arizona Public Service Company Post Office Box 53999

Phoenix, Arizona 85072-3999

February 1,

1993 DISTRIBUTION i Docket File'RC 8 Local PDRs PD V Reading T. Hurley/F. Hiraglia, 12G18 J. Partlow, 12G18 J.

Roe H. Virgilio T. quay C. Trammell D. Foster A. Chaffee, 11AI

OGC, 15B18 E. Jordan, MNBB3701 B. Grimes, llE4 Receptionist OWFN A. Murphy, NLS217A ACRS (10),

P315 N. Chokshi, NLS217A L. Tran

OPA, 2G5 B. Rothman, 7H15 E. Zurflueh, NLS217A G. Giese-Koch, 7H15 NRR Mailroom, 12G18 D. Wheeler, 12G18 R. Hernan, 14C7 P. O'Dell, 12E4'.
Chen, NLS324 W. Scott, 10A19 J. Mitchell, 17G21 K. Perkins, RV G. Cook, Region V

t/

h

p,H Htcy WpO oO R

/4, +**++

DOCKETNO. 50-528, 50-530 MEMORANDUMFOR:

(

UNITED STATES NUCLEAR REGULATORY COMMISSION WASHINGTON, D.C. 20555 December.

29, 1992 59-529 Regulatory Publications Branch Division of Freedom of Information and Publications Services Office of Admlnlstratlon and Resources Management ISTR IBUTION Docket File PDV Reading Fi1e DFoster CTramme11 Tray FROM:

SUBJECT:

Office of Nuclear Reactor Regulation

,RECEIPT OF PETITION FOR DIRECTOR'S DECISION UNDER i0 C.F.R.

5 2.206 One signed original of the Federal Register Notice Identified below is enclosed for your transmittal to the Office of the Federal Register for publication. Additional conformed copies (

5

) of the Notice are enclosed for your use.,

Notice ot Receipt of Application for Construction Permit(s) and Operating License(s).

Notice of Receipt of Partial Application for Construction Permit(s) and Facility License(s): Time for Submission ot Views on Antitrust Matters.

Notice of Consideration of Issuance of Amendment to Facility Operating License. (Call with

.day Insert dato).

Notice of Receipt of Application for Facility License(s); Notice of Availability of Applicant's Environmental Report; and Notice of Consideration of Issuance of Facility License(s) and Notice of Opportunity for Hearing.

Notice of Availabilityof NRC DraftIFlnal Environmental Statement.

Notice of Limited Work Authorization.

Notice of Availabilityof Satety Evaluation Report.

Notice of Issuance of Construction Permit(s).

Notice of issuance of Facility Operating License(s) or Amendment(s).

Order.

Exemption.

0 Notice of Granting Exemption.

Environmental Assessment.

Notice of Preparation ot Environmental Assessment.

G Receipt of Petition for Director's Decision Under 10 CFR 2.206.

Issuance of Final Director's Decision Under 10 CFR 2.206.

Other.

Division of Reactor Projects III/IV/V

Enclosure:

As stated contact: Charl es H. Trail+el 1 30i 504-3121 OSI'ICC&

SURNAMK OATK NRc poRM ste uoieot NRcM 0240 OFFICIAL RECORD COPY

bl I

CP,R HKCI/

Wp

+

0 Cy I

nO

~.

VI O~

YJ i~

+~

~O

+%*Jr+

DOCKET NO. 50-528, and 50-530 MEMORANDUMFOR:

1 UNITED STATES NUCLEAR REGULATORY COMMISSION WASHINGTON, D.C. 20555 December 22, 1992 50-529 Regulatory Publications Branch Division of Freedom of Information and Publications Services Office of Administration and Resouices Management DISTRIBUTION W Docket File PDV Reading File DFoster CTrammell TQuay FROM:

h.

ONce of Nuclear Reactor Regulation WITHDRAWAL OF Af1ENDt1ENT REQUEST - PALO VERDE NUCLEAR GENERATING STATION, UNIT NOS. 1, 2, AND 3 (TAC NOS. N83103,

f183104, IIND Yi83105)

One signed original of the Federal Register Notice Identified below Is enclosed for your transmittal to the Office of the Federal Register for publication. Additional,conformed copies (

5

) of the Notice are enclosed for your use.

Notice of Receipt of Application for Construction Permit(s) and Operating License(s).

Notice of Receipt of Partial Application for Construction Permit(s) and Facility License(s): Time for Submission of Views on Antitrust Ma'tters.

Notice of Consideration of Issuance of Amendment to Facility Operating License. (Call with day Insert date).

Notice of Receipt of Application for Facility License(s); Notice of Availability of Applicant's Environmental Report; and Notice of Consideration of Issuance of Facility License(s) and Notice of Opportunity for Hearing.

Notice of Availabilityof NRC Draft/Final Environmental Statement.

Notice of Limited Work Authorization.

Notice of Availabilityof Safety Evaluation Report.

Notice of Issuance of Construction Permit(s).

Notice of Issuance of Facility Operating License(s) or Amendment(s).

Order.

Exemption.

D Notice of Granting Exemption.

Environmental Assessment.

Notice of Preparation of Environmental Assessment.

Receipt of Petition for Director's Decision Under 10 CFR 2.206.

Issuance of Final Director's Decision Under 10 CFR 2.206.

Q oth. Withdrawal of Amendment R

s Division of Reactor Projects III/IV/V

Enclosure:

As stated contact: C-Trammel l (301) 504-3121 CFFICK suRNAMK

~ ~ 4 0 ~ ~ ~ ~ ~ ~

OATK

~ 1

~

~

~

~ 0

~ ~

~

NRC FORM SIO IIO/eol NRCM 0240 OF'FICIAL RECORD COPY

V

'I 14 4

December 22, 2

Docket Nos.

50-528, 50-529 and 50-530 Hr. William F.

Conway Executive Vice President, Nuclear Arizona Public Service Company P.O.

Box 53999

Phoenix, Arizona 85072-3999

Dear Hr. Conway:

SUBJECT:

WITHDRAWAL OF AMENDMENT REQUEST PALO VERDE NUCLEAR GENERATING STATION, UNIT NOS.

1, 2, AND 3 (TAC NOS.

M83103, H83104, AND H83105)

By letter dated March 20,

1992, you applied for an amendment to the operating licenses for the Palo Verde facilities which proposed a change to the surveillance requirement for the containment purge valve isolation system in the technical specifications.

The change would provide an alternate surveillance requirement to be applied when the system is inoperable.

By letter dated October 15,

1992, we explained why we had concluded that the change was not necessary, and advised you that we considered the proposed change to be withdrawn unless you notified us within 10 days that this was incorrect.

Since this time has

passed, we consider the matter closed.

Accordingly, we have filed the enclosed Notice of Withdrawal of Application for Amendments to Facility Operating Licenses with the Office of the Federal Register for publication.

Sincerely, Original signed by Charles H. Trammell, Senior Project Manager Project Directorate V

Division of Reactor Projects III/IV/V Office of Nuclear Reactor Regulation

Enclosure:

Notice cc w/enclosure:

See next page DISTRIBUTION:

Docket File PDV Reading File HVirgilio DFoster

OGC, 15B18 ACRS(10),

P-315 PDV Plant File OPA 2G5 NRC

& Local PDRs JRoe TQuay CTrammell

DHagan, 3206 OC/LFDCB, 4503
KPerkins, RV OFC NAME DATE LA PDV DFoster ammell:lh D

PDV TQuay l+/> /

OFFICIAL RECORD COPY DOCUMENT NAME:PV83103. WIL

gp,S >EOIj

~p pO Ilh p

p Cy

+0 t7 +**++

UNITED STATES NUCLEAR REGULATORY COMMISSION WASHINGTON, D.C. 20555 December 22, 1992

'ocket Nos.

50-528, 50-529 and 50-530 Mr. William F.

Conway Executive Vice President, Nuclear Arizona Public Service Company P.O.

Box 53999

Phoenix, Arizona 85072-3999

Dear Mr. Conway:

SUBJECT:

WITHDRAWAL OF AMENDMENT REQUEST PALO VERDE NUCLEAR GENERATING STATION, UNIT NOS.

1, 2, AND 3 (TAC NOS.

M83103, M83104, AND M83105)

By letter dated March 20, 1992, you applied for an amendment to the operating licenses for the Palo Verde facilities which proposed a change to the surveillance requirement for the containment purge valve isolation system in the technical specifications.

The change would provide an alternate surveillance requirement to be applied when the system is inoperable.

By letter dated October 15,

1992, we explained why we had concluded that the change was not necessary, and advised you that we considered the proposed change to be withdrawn unless you notified us within 10 days that this was incorrect.

Since this time has

passed, we consider the matter closed.

Accordingly, we have filed the enclosed Notice 'of Withdrawal of Application for Amendments to Facility Operating Licenses with the Office of the Federal Register for publication.

Sincerely,

Enclosure:

Notice W

Charles M. Trammell, Senior Project Manager Project Directorate V

Division of Reactor Projects III/IV/V Office of Nuclear Reactor Regulation cc w/enclosure:

See next page

Mr. William F.

Conway Arizona Public Service Company Palo Verde CC:

Nancy C. Loftin, Esq.

Corporate Secretary 3 Counsel Arizona Public Service Company P. 0.

Box 53999, Mail Station 9068

Phoenix, Arizona 85072-3999 James A. Beoletto, Esq.

Southern California Edison Company P. 0.

Box 800

Rosemead, California 91770 Senior Resident Inspector U.S. Nuclear Regulatory Commission HC-03 Box 293-NR Buckeye, Arizona 85326 Regional Administrator, Region V

U. S. Nuclear Regulatory Commission 1450 Maria Lane Suite 210 Walnut Creek, California 94596 Mr. Charles B. Brinkman, Manager Washington Nuclear Operations ABB Combustion Engineering Nuclear Power 12300 Twinbrook Parkway, Suite 330 Rockville, Maryland 20852 Mr. William A. Wright, Acting Director Arizona Radiation Regulatory Agency 4814 South 40 Street

Phoenix, Arizona 85040 Chairman Maricopa County Board of Supervisors 111 South Third Avenue
Phoenix, Arizona 85003 Jack R.
Newman, Esq.

Newman 8 Holtzinger, P.C.

1615 L Street, N.W., Suite 1000 Washington, D.C.

20036 Curtis Hoskins Executive Vice President and Chief Operating Officer Palo Verde Services 2025 N. 3rd Street, Suite 220 Phoenix, Arizona 85004 Roy P.

Lessey, Jr.,

Esq.

Bradley W. Jones, Esq.

Arkin, Gump, Strauss, Hauer and Feld El Paso Electric Company 1333 New Hampshire Ave., Suite 400 Washington, D.C.

20036

7590-01 UNIT D STAT S NUC AR REGU ATORY COMM SS ON R

ONA UB C SE ICE COMP N

T PALO VERDE NUC G

NE G

S AT 0 UNITS 2

AND 3 DOCK T NOS. 50-528 50-529 ND 50-530 OT CE OF W

D A

0 CATION OR M NDHEN S 0

CI Y OPERATING IC NS S

The U.S. Nuclear Regulatory Commission (the Commission) is announcing the withdrawal of an application dated March 20, 1992, for amendments to Facility Operating License Nos.

NPF-41, NPF-51, and NPF-74, issued to Arizona Public Service Company, et

+a

. (the licensee),

for operation of Palo Verde Nuclear Generating Station, Unit Nos.

1, 2, and 3, located in Maricopa County, Arizona.

Notice of consideration of issuance of the amendments was published in the FEDERAL REGISTER on May 13, 1992 (57 FR 20508).

The amendment request proposed a change to the surveillance requirements for the containment purge valve isolation system to provide an alternate surveillance requirement to be applied when the system is not operable.

By letter dated October 15, 1992, the NRC staff explained to the licensee why the proposed change was not necessary and that the NRC staff considered the proposed change to be withdrawn unless it was advised otherwise within 10 days.

No subsequent notice was received from the licensee.

Thus, the application for amendments is considered to be withdrawn.

For further details with respect to this action, see the application for amendments dated March 20,

1992, and the NRC staff's letters to the licensee dated October 15 and December 22, 1992.

These documents are available at the Commission's Public Document Room located in the Gelman Building, 2120 L Street, N.M, Washington, D.C. 20555 and at the local public document room in the Phoenix Public Library, 12 East HcDowell Road, Phoenix, Arizona 85004.

Dated at Rockville, Maryland this 22nd day of December, 1992.

FOR THE NUCLEAR REGULATORY COMMISSION Charles H. Trammell, Senior Project Manager Project Directorate V

Division of Reactor Projects III/IV/V Office of Nuclear Reactor Regulation