PdCE87 r=r C &K Docket Nos. 50-528, 50-529, and 50-530 JUL 1 1
1891 Mr. William F.
Conway Executive Vice President Arizona Public Service Company P. 0.
Box 53999 Phoenix, Arizona 85072-3999
Dear Mr. Conway:
SUBJECT:
MEETING WITH ARIZONA PUBLIC SERVICE, PALO VERDE NUCLEAR GENERATING STATION, UNITS NOS. 1, 2, AND 3 On May 13, 1991, Gregory C. Cwalina of the Vendor Inspection Branch met with several representatives of the Arizona Public Service Company (APS) at their corporate headquarters in Phoenix.
The purpose of the meeting was to discuss APS involvement with their diesel generator supplier, Cooper-Bessemer Reciprocating (C-B) and NRC's inspection of C-B in August of 1990.
APS was concerned that the NRC's inspection report did not properly characterize the extent of APS's involvement in improving C-B's quality assurance, parts classification, and commercial-grade dedication programs.
APS personnel presented a description of their interactions with C-B over the past several years.
In addition, the APS representatives provided copies of several audit reports and summaries of their experiences with C-B.
The enclosed trip report provides a more detailed description of the meeting.
I have also included the APS experience summaries as enclosures to the trip report.
S incerely, 9i07240336 9f07li I
PDR ADOCK 05000528 P
PDRI
Enclosures:
As stated cc:
See next page ORIGINAL SIGNED BY Catherine M. Thompson, Project Manager Project Directorate V
Division of Reactor Projects III/IV/V Office of Nuclear Reactor Regulation DISTRIBUTION:
NRG I LP R
~ l(Ffli gli NVirgilio PDV r/f P
Jgyer EJordan GC 1
a ADRS (10)
JPartlow BBoger CThompson OGC JCaldwel 1
g CDJC1iirig.
D NAME
- RCesaro DATE:07/g /91 PD
- 0Th~a/vw
- 07/)991
.JDye
- DT/ I)/01 gQOonr ocumen arne:
I N
H kl
=/
W l
II A
II il N
1 IIJ
Mr. William F.
Conway Arizona Public Service Company Palo Verde CC:
Arthur C. Gehr, Esq.
Snell 5 Wi lmer 3100 Valley Center Phoenix, Arizona 85073 James A. Beoletto, Esq.
Southern California Edison Company P. 0.
Box 800
- Rosemead, Gal ifornia 91770 Senior Resident Inspector U.S. Nuclear Regulatory Commission HC-03 Box 293-NR Buckeye, Arizona 85326 Regional Administrator, Region V
U. S. Nuclear Regulatory Commission 1450 Maria Lane Suite 210 Walnut Creek, California 94596 Jack R.
- Newman, Esq.
Newman 5 Holtzinger, P.C.
1615 L Street, N.W., Suite 1000 Washington, D.C.
20036 Ignacio R. Troncoso Senior Vice President El Paso Electric Company Post Office Box 982 El Pasco, Texas 79960 Roy P. Lessey, Jr.,
Esq.
Bradley W. Jones, Esq.
Akin, Gump, Strauss, Hauer and Feld El Paso Electric Company 1333 New Hampshire Ave., Suite 400 Washington, D.C.
20036 Mr. Charles B. Brinkman, Manager Washington Nuclear Operations ABB Combustion Engineering Nuclear Power 12300 Twinbrook Parkway, Suite 330 Rockville, Maryland 20852 Mr. Charles Tedford, Director Arizona Radiation Regulatory Agency 4814 South 40 Street Phoenix, Arizona 85040 Chairman Maricopa County Board of Supervisors 111 South Third Avenue Phoenix, Arizona 85003
ENCLOSURE TRIP REPORT MEETING WITH ARIZONA PUBLIC SERVICE MAY 13, 1991 Prepared by:
Gregory C. Cwalina, Chief Special Projects Section Vendor Inspection Branch 1
BACKGROUND On August 27-30, 1990, the Vendor Inspection Branch (VIB) conducted an inspection of the Cooper-Bessemer Reciprocating (C-B) company.
In November
- 1990, the staff issued the inspection report which subsequently appeared in the NRC White Book, "Licensee Contractor and Vendor Inspection Status Report" (NUREG-0040, Vol. 14, No. 4).
The Arizona Public Service Company (APS) reviewed the inspection report and had concerns with some of the conclusions of the report.
The general conclusion of the report, as stated in a letter from Uldis Potapovs to Mr. W. H. A. Lambert dated November 13, 1990, was that "C-B has established and is implementing a generally effective dedication program for supplying qualified spare and replacement parts..."
The primary concern of APS regards the report section that deals with their audits of C-B.
The NRC inspectors reviewed two audits of C-B by APS and one by the Commonwealth Edison Company.
Based upon the review of those audit reports, the inspectors concluded that the licensees'udits did not address the adequacy of the classification of parts nor the process for dedicating commercial-grade items for safety-related service.
In April 1991, APS representatives Stephen Guthrie and Pat Purcell contacted Greg Cwalina of the Vendor Inspection Branch to express their concerns and request a meeting to discuss the report and their interactions with C-B.
The meeting was held on May 13, 1991 at the APS offices in Phoenix, Arizona.
2 PURPOSE APS requested the meeting to discuss its concerns regarding the inspection report.
In particular, APS was concerned that the NRC inspectors lacked the historical perspective of APS's interactions with C-B and, therefore, the report's conclusions in some areas may not properly represent C-B's performance.
In addition, the APS representatives felt that the NRC conclusions in the area of licensee audits improperly characterized the degree and depth of APS audits of C-B.
APS stated that the NRC's inspection report did not recognize the extent of APS's involvement in improving C-B's programs for quality assurance, parts
classification and commercial-grade dedication.
In the inspection report, the staff stated "licensees in their audits did not address the adequacy of C-B's classification of parts nor the process for dedication of commercial-grade items for safety-related service."
APS felt this conclusion, which was based upon a limited sample of audit reports, could result in other NRC officials doubting the adequacy of APS's audit program.
However, the report also stated, "the audits were comprehensive in scope and thoroughness..."
APS representatives made a formal presentation summarizing their interactions with C-B over the past several years.
A copy of some of the presentation materials is attached to this report.
The information shows that APS interacted extensively with C-B since
- 1986, when APS took full responsibility for procurement and auditing from their architect engineering firm.
3 RESULTS In June
- 1986, APS performed their first audit of C-B and found six areas of nonconformance.
More importantly, APS felt the deficiencies indicated a larger problem and placed a hold on all shipments from C-B.
As a result, C-B did not ship any safety-related parts to APS during 1986.
- Further, APS decided to require 100 percent source surveillance on all parts procured from C-B.
In November
- 1987, APS performed its second audit of C-B, issuing 12 findings and closing 1 previous finding.
Of particular interest was the finding that C-B failed to pass Part 21 requirements down to subtier vendors.
This finding identified to APS that C-B was not classifying its parts consistent with the engineering parts classification delineated by APS.
The finding resulted in APS sending members of its vendor quality staff to C-B in 1988 to assist C-B in developing a quality assurance program that was consistent with the industry's.
APS worked closely with C-B to facilitate its understanding of the differences between commercial-grade and safety-related procurement requirements and the process for dedicating commercial-grade items for safety-related applications.
It was not until February of 1990 that APS was able to close this finding.
During the same audit, APS found that C-B could not substantiate product quality using its existing methods for qualifying subtier vendors.
APS also found that materials supplied to C-B for APS purchase orders did not comply with C-B's material design requirements.
This finding prompted C-B to initiate a major change in its method for dealing with subtier vendors.
APS closed this finding in October of 1988.
In addition to the audits, APS conducted 80 source surveillances related to 51 purchase orders during 1987 which resulted in a 25%
rejection rate.
APS rejected a part if its review identified any hardware problems or deficiencies in the part's dedication packages.
APS concluded that C-B did have an adequate commercial
l
quality assurance program for parts that it manufactured.
- However, that program would require significant improvement to satisfy the requirements of ANSI-N45.2.
Throughout
- 1988, APS continued to closely interact with C-B.
In December
- 1988, APS performed an audit at the Cooper Industries, Rotating Division (Rotating) to assess the adequacy of Rotating's quality assurance program and determine if it could be placed on the APS approved vendors list (AVL).
APS identified 15 areas of noncompliance with its quality program.
As a result, the Rotating division was not placed on the AVL, and C-B Reciprocating remained accountable for product verification.
In December
- 1988, APS also performed a full scope audit of C-B to evaluate corrective actions and re-assess the C-B quality program.
The audit resulted in issuing another eight findings.
In
- 1988, APS conducted approximately 15 source surveillances relating to 12 purchase orders.
A 40 percent rejection rate resulted with the same concerns as were identified in 1987.
In 1989, APS re-audited both C-B Rotating and C-B Reciprocating.
The Rotating audit showed sufficient progress to allow APS to place it on the AVL with source inspection restrictions.
The audit of Reciprocating showed that it had made some progress, but several corrective actions had not been completed.
In addition, APS conducted 21 source surveillances relating to 17 purchase orders resulting in a rejection rate of 19 percent.
APS expanded their interactions with C-B in 1989 when they audited ESG Cooper En-tronics Controls, the supplier of diesel generator instrumentation and control systems and replacement parts.
APS identified five areas of nonconformance and placed En-tronics on the AVL with source inspection restrictions.
A re-audit was performed at all three facilities in 1990.
The re-audit of Reciprocating showed that adequate corrective actions had not been completed to resolve two deficiencies.
Since this was the third audit that indicated C-B had not resolved the deficiencies, APS requested a meeting with C-B senior management.
The audits at Rotating and En-tronics had yielded similar results.
In both
- cases, APS determined that the vendor had not implemented adequate corrective actions.
APS imposed.100 percent source surveillance at both facilities.
In
- 1990, APS completed approximately 23 source surveillances relating to 21 purchase orders with a rejection rate of 61 percent.
- However, APS noted that the source surveillances reflected significant improvement in procurement, vendor qualification, and dedication activities.
At this time, APS waived 100 percent surveillance requirements on certain items.
During the meeting, the APS representative stated that C-B had reached its peak performance during this time and that it was considering removing all restrictions pending the results of its audits.
- However, as
4'
noted
- above, the audits did not demonstrate the existence of an adequate quality program.
In 1991, APS has performed approximately 9 source surveillances relating to 7 purchase orders.
These surveillances have resulted in a 44 percent rejection rate.
APS also plans to re-audit all three C-B divisions in September 1991.
These audits will be conducted with representatives of the Commonwealth Edison Company.
4 CONCLUSIONS Based upon a review of the audits performed by APS of the three C-B divisions, it can be concluded that APS's oversight of the procurement process with C-B has been comprehensive.
The licensee identified numerous deficiencies in the vendor's quality assurance program and worked closely with the vendor to resolve the issues.
The issues of primary interest include parts classification, the dedication of commercial-grade
- items, and C-B's oversight of its subtier vendors.
All of these issues have been addressed by APS in its interactions with C-B.
In the NRC's inspection report for Cooper-Bessemer, the staff
- stated, "the inspectors concluded that the licensees in their audits did not address the adequacy of C-Bs classification of parts nor the process for dedication of commercial-grade items for safety-related service."
The NRC inspection of C-B included a
sampling of audit reports from licensees.
In the report, the inspectors identified the specific audit reports that the NRC reviewed.
Although APS addressed parts classification and dedication in some of its audits, they were not addressed in those audits sampled by the NRC.
The staff informed APS that the NRC reviews audit reports on a sampling basis and cannot review all audits because of limited time and resources.
Although the APS representatives understood the limitations of the NRC inspection, they stated that all readers would not understand that the statement in the inspection report is intended to only address the audits reviewed during the inspection and does not apply to all of the licensee's audits.
The NRC also concluded that C-B has establish'ed and is implementing a generally effective dedication program.
APS also expressed concern that C-B would use the NRC report as evidence of an adequate program and be less responsive to recommendations from APS. It was pointed out to APS that the NRC inspection of C-B was performed at about the same time that APS was considering removing all restrictions regarding C-B procurements.
Generally, the NRC inspection findings seemed to agree with APS'erceptions of C-B at the time of the inspection.
Unfortunately, the NRC does not have the resources to routinely inspect all vendors to ensure that their quality programs do not decline.
The APS representatives recognized the NRC constraints and explained that they were merely describing problems that may arise as
- a. result of NRC vendor inspection activities.
Since the NRC inspection of C-B is really a "snapshot" of C-B's programs in effect at the time of the inspection, there is no reason to question the report's conclusions.
However, it is important to note that APS has spent significant time and resources interfacing with C-B.
These interactions have prompted C-B to significantly improve its procurement programs and are partly responsible for the adequacy of the program reviewed by the NRC.
5 PERSONS CONTACTED The following members of the APS organization attended the meeting:
arne Title Ram N. Prabhakar Rosemary C. Fullmer Bob Gordon Michael Ferguson W.
P. Purcell, Jr.
Stephen Guthrie Ali Fakhar Manager Quality Engineering Manager Quality Audits.and Monitoring Procurement Engineer Sr. Vendor Quality Engineer Supervisor Vendor Quality Engineering Deputy Director Nuclear Safety Supervisor Procurement Engineering
I I,
1986 APS Vendor Quality Assurance Engineering Major Vendor Audits and Significant Events {1966-1991) 1987 1988 1989 1990 6'I8 O
1st APS auNt of RECIPROCATIHG 12%8:
6'old on shipment:
Imposed
-1/87
- e
- DG Unlt38
- articulating
- rod Incident 12/87:
r
~ 2nd APS auNt of RECIPROCATING
~ 51 APS PO.'e (80 Reports)
Inspected during 1987 I
- ~ 3rd APS audit of RECIP.
- ~ 1st audit of MT.VERNON:
8I ROTATING
- ~ VQE spent tyro weeks at:.
- ESGtoaeelstlnQA Program rewrite
- ~ Procurement limited to Outage/Operation needs only
- ~ 12 APS P.O.'e (1 5 Reports) Inspected duAng 1988
- ~ DG Unit 2B fuel line rupture 4/91
- ~ APS reknpoeed100%
Source VerNcNon
- atESG.
- ~ 7 APS P.O.'e (9 Reporh)
Inspected to date I
APS/CECOaudltof ail ESG facIII5ee echeduled for September 1991 1289:
I
- ~ Re-audit of RECIP.
- ~ Re-audit of ROTATING
- ~ 1st APS audit of EHTRONICS
- ~ UNer to Contracte-ESG QA Program State of Affaire
- ~ 17 APS P.O.'e (2f Reports) Inspected during 1989 12/90:
I
- ~ Reaudlta at following:
- ~ RECIPROCATING
- ~ ROTATING
- ~ EHTROHICS
~ 21 APS P.O'a (23 Reports) Inspected during 1990
SECTION IV Overview of APS activities
- 1986 ud ts A.
u e
First APS Audit of Cooper Reciprocating.
This resulted in four corrective action reports and a hold on shipment.
o CAR CP86-0121 was the most significant finding.
This CAR identified that Cooper processed a part (heater element) as commercial grade and not as safety-related per APS purchase order requisite.
CAR CP87-0112.
e kept current with business operation practices.
The QA organization and interface controls between Mt. Vernon and Grove City were not as depicted in the QAM.
This finding was closed
~0 16 87 with Mt. Vernon/gncronics being added to Grove City AVL.
o CAR CP86-0123 identified program implementation weaknesses in the M&TE process.
This finding was closed
~02 19 88 based on issuance of CAR CP87-0116.
o CAR CP86-0124 was considered significant in that Cooper was not peiforming shipping inspections prior to hardware shipment.
Cooper was procuring parts from sub-tier vendors and not inspecting them prior to shipment.
This
ag was closed ~015 87 by corrective action verification.
At this point in time APS Vendor Quality felt the deficiencies identified symptoms of a larger problem.
A hold-on-shipment was issued to prevent Cooper from shipping parts to APS until we could get a better understanding of what was transpiring.
puree Su e
a ces No safety-related material/parts were shipped to APS in 1986.
I I
SECTION V Overview of APS activities
- 1987 gndiccss A.
ovembe 6-9 8
Thi.s was the second audit of Cooper-Reciprocating.
The intent of the audit was twofold:
(1) to obtain a better understanding of what was happening at Cooper, and (2) to assess corrective action implementation and effectiveness of the 1986 findings.
Twelve findings were issued; one 1986 finding was closed.
"e" indicated a severe weakness in the indoctrination/training of Cooper personnel.
This finding oas closed ~004 88.
o CAR CP87-0111 identified weakness in the administrative portions of Cooper's Design Control program.
This finding oas closed
~01 03 89.
o CAR CPS7-0112 identified a recurring deficiency with Cooper failing to pass down 10CFR21 to sub-tiers.
This issue was identified on CAR CP86-0121, VDN 87-046 and VDN 87-050.
The VDNs were a result of source inspection activities at Cooper.
Note: This finding was very critical in that APS told Cooper that the classification of their parts were not consistent with the engineering parts classification delineated by APS. It took Cooper from ll/87 until 10/SS to understand commercial grade vs. safety-related terminology, dedication and effective supplier controls.
VQE spent two weeks at Cooper to assist in developing a
QA program consistent with the procurement initiatives at that time.
This finding was closed
~0
~9 90.
o CAR CP87-0113 identified that implementing procedures either did not exist or were weak to provide quantitative, qualitative criteria to ensure compliance with the commitments delineated in the QA manual.
This finding was closed ~0
~7 88.
I
Page 2 of Section V
identifying, that:
(1) the sub-tier vendors could not verification, and (2) that orders did not comply with requirements.
complimented CAR CP87-0112 by methods implemented to qualify substantiate product quality materials supplied for hPS purchase Cooper's material design This finding was very critical because it caused Cooper to:
o Re-orient their philosophy on supplier qualification.
o Revamp their quality program.
o Undertake a major effort to adequately and effectively assess their vendors.
This finding perpetuated the issuance of QCP-10-16 which is their dedication program.
This finding was closed
~0
~7 88.
CAR CP87-0115 identified concerns with Cooper's inspection and test status program.
This finding oes closed
~0 04 88.
CAR CP87-0116 identified numerous deficiencies in Cooper's control of M&TE.
This finding was closed
~0 0~.
o
-CAR CP87-0117 identified a serious weaknesses with Cooper's Corrective Action program.
This finding oes closed
~05 10 88.
Q
- Records, as demonstrated by APS audit results This finding was closed ~0 0~4 8
CAR CP87-0119 identified an overall ineffectiveness in Cooper's internal assessment system.
This finding was closed out ~0
~7 88.
reporting requirements of 10CFR21 in a timely manner.
This finding wes closed on 10ID04 88.
Page 3 of Section V
u e
Fifty-one APS safety-related purchase orders were subjected to source surveillance at Cooper facilities.
Approximately 80 trips vere taken to support the project in obtaining parts for plant outage/operation.
Rejection statistics are reflected on the performance trend.
Our surveillances pointed our typical problems in the area of:
l.
2.
3.
4, 5.
Design compliance, Procurement process.
Vendor qualification.
Inspection anomalies.
Parts substitution.
It is important to mention that no item could be shipped from Cooper until APS Vendor Quality could substantiate that the part:
l.
2.
3.
Met design characteristics.
Was procured properly.
Inspected upon receipt and prior to shipment.
A conclusion one can draw was that Cooper did have an adequate/effective commercial program which required significant improvements to satisfy ANSI-N45.2 requirements.
SECTION VI Overview of APS activities
- 1988 cembe
-9 This was the first audit of Cooper-Rotating.
The purpose was to assess the adequacy, implementation and effectiveness of their quality program for placement on the APS Approved Vendors List.
Fifteen areas were identified which did not comply with the quality program.
o VDN 89-00 identified that Cooper-Rotating was procuring parts/services from unapproved vendors and was ~o m
erne t t
ded cat o
o (QCP 10-16) as required.
This finding was closed
~03 I 89.
o 9~0'9-00 identified that the 00 Inspectors did nor doc,ument, on the QC/IP, the M&TE used during inspection activities.
This finding was closed 03/317 89.
o VDN 89-003 identified that QC Inspectors did not perform all of the dimensional inspections t'equired by the quality program.
This finding was closed 05/523 89.
o VDN 89-004 identified that Cooper-Rotating procurement documents failed to pass down either APS and/or Cooper quality requirements to sub-tier vendors.
This finding was closed
~05 3 89.
o VDN 89-005 identified procedure inadequacies (this deficiency parallels the concerns identified on CAR CP87-113).
This finding was closed 07/706 89.
o VDN 89-006 identified that a required test procedure was not listed on the associated drawing to provide quantitative/qualitative acceptance criteria to QC.
This finding was closed
~03 0'i~.
emote:
As a result of this VDN, Cooper committed to review all of their drawings for technical adequacy.
This resulted in the cclassification of turbochar er arts.
Page 2 of Section VI V~>~9- )~0 identified that heat treatment strip charts received from a sub-tier vendor indicated that the temperature cooling rate exceeded specification requirements.
This finding was closed ~~.
was calibrated by an unapproved source.
No MRR was written to identify this nor to evaluate turbocharger acceptance.
This finding was closed ~~.
VDN 89-009 identified the fact that twenty-one MRRs were either dispositioned incorrectly or provided inadequate engineering justification for the use-as-is disposition, and that Cooper failed to initiate an internal CAR to document this trend.
This finding was closed ~0
~7 V~DN 89-0 0 identified that Cooper vas not documenting training of employees.
This finding was closed ~5 2~.
o VDY 89-011 identified administrative concerns with the control of internal procedures.
This finding vas closed
~05 23 89.
o V~DN 89-01 documents that CooPer had an ineffective CAR program.
This finding vas c1osed 055023 89.
o VDN 89-013 identified that Cooper's audit program was deficient/inadequate.
This finding vas closed
~08 24 90.
As a result, Rotating was not added to the APS AVL and Reciprocating was held accountable for product verification and C
of C signature.
ecembe 4-6 9
Based on the results of the 1987 audit and source surveillances performed during 1988 at the Reciprocating facility, a full scope audit was performed to assess the implementation of corrective actions and re-evaluate the Reciprocating quality program.
As a result of this audit an additional eight findings were issued.
~
4 I
Page 3 of Section VI s"
vere not maintained in accordance vith procedural requirements.
This finding vas closed
~0 o
V 89-0 5 identified that lead auditor certifications did not comply with quality program requirements.
This finding vas closed $44'~)g.
o V
89-0 6 identified that no document control measures vere established for inspection and audit procedures.
This finding was closed ~4~0 V~DN 89-0 7 identified that the corrective action prograa was inadequate to ensure timely resolution and implementation verification of adverse conditions.
This finding was closed 04/420 89.
VDN 89-018 identified that the audit program vas inadequate to ensure the effectiveness and implementation of the quality program.
This finding was closed
~08 24 90."
V~DR 89-0 9 identified that Cooper Engineering had established two different sets of critical characteristics for dedication of the same art.
This finding was closed
~04 20 9.
I VDN 89-020 identified that the vendor qualification files lacked sufficient documented ob)ective evidence to subaeantiate placement of vendors on the Cooper NAVL.
This finding was closed ~1
~9 V~DR 89-0 identified several HRRs which were iwproperly dispositioned and/or did not contain sufficient )ustifications for use-as-is or repair dispositions.
This finding was closed ~~90.
s
Page 4 of Section VI puree Su e
a c
s Twelve APS safety-related purchase orders were sub)ected to source surveillance at Cooper facilities.
Approximately~ trips were taken to support the pro)ect.
Refection statistics are reflected on the performance trend.
Our surveillances pointed out the same concerns identified in 1987.
SECTION VII Overview of Activities - 1989 A reaudit was performed at the Rotating facility to evaluate the corrective actions implemented to resolve the findings issued during the 1988 qualification survey.
The audit team determined that the corrective actions for VDNs 89-01 thru 05 and 07 thru 12 had been effectively implemented and were adequate to resolve the deficiencies.
The corrective actions for VDNs 89-06 and 13 had not been implemented and remained open.
Based on the efforts to resolve these deficiencies, Rotating was placed on the APS AVL with source inspection restrictions.
Initial qualification survey of the En-Tronics facility.
Five areas of non-compliance were identified which resulted in the issuance of three findings.
CAR CE89-0 7
Equipment configuration changes were not evaluated to determine impact on equipment qualifications.
Additionally, parts and components being supplied by En-Tronics for safety/quality related use were not being procured on a quality basis from approved suppliers.
VDN 89-139 The organizational chart depicted in the current quality program did not reflect the reporting relationship of test personnel to the quality organization when performing acceptance tests of quality related equipment.
VDN 89-142 The audit program was found inadequate to ensure that the effectiveness and implementation of the quality program was evaluated (this parallels the findings issued at Reciprocating and Rotating).
The audit team also identified that En-tronics was revising the current quality program to comply with APS requirements;
- however, implementation of the program could not be assessed due to a lack of nuclear orders.
Based on the survey and the revised quality program En-Tronics was placed on the APS AVL with source inspection restrictions.
This restriction was to remain in effect until En-tronics could demonstrate an ability to control the supply of quality related equipment.
Page 2 of Section VII C.
ecembe 9
A reaudit was performed at the Reciprocating facility to evaluate the implementation and effectiveness of the corrective actions for CAR CP87-112 and VDNs89-014,
- 018, 020 and 021.
The audit team concluded that sufficient corrective actions had been implemented to resolve VDN 89-020; however, the proposed corrective actions for CAR CP87-112 and VDNs89-014, 018 and 021 had not been completed.
Revised responses for the CAR and VDNs89-014 and 018 were required and Vendor Quality requested that a reaudit be scheduled for March 1990.
puree urveil a
ce Seventeen safety-related purchase orders were subjected to source surveillance in 1989.
Approximately twenty-one trips were taken to support the project.
Rejection statistics are reflected on the performance trend.
Our surveillances pointed out problems in the following areas:
1.
Lack of design evaluation for critical characteristics.
2.'nconsistency with critical characteristic application.
3.
Vendor qualification in the area of Commercial Grade Surveys.
4.
Parts substitution.
5.
Inspection anomalies.
t f
SECTION VIII Status of Cooper's QA Programs Letter 028-01604 Purcell to Howard, dated July 31, 1989, provided a summary to APS management of the current status of Cooper.
gota~ti Two findings remained open.
o VDN 89-'006 required the performance of an ineerin ev ew turbochar e
ts c assi c t o (i.e.; critical/
noncritical).
V~DN 89-0 3 identified defioienoiee in the implementation of the internal audit program.
==
Conclusion:==
QA Program was considered adequate.
Note 14 (Release for Shipment) still imposed.
2.
Entronics Survey conducted in July revealed several weaknesses in design/procurement areas.
Program was re-written to prevent recurrence.
==
Conclusion:==
QA Program was considered adequate.
Note 14 still imposed.
3.
~otetin o
CAR CP87-0112 remained open.
Cooper to that date failed to adequately resolve issue addressing passing down 10CFR21 to sub-tier vendors.
==
Conclusion:==
QA Program considered adequate.
Note 14 still imposed.
SECTION I<
Overview of Activities - 1990 1.
~uk~
A.
0-A reaudit was performed at Reciprocating to re-evaluate the corrective actions for VDNs89-018 and 021.
The auditor concluded that adequate corrective actions had not been implemented to resolve VDN 89-021 and that the proposed corrective actions for VDN 89-018 had not been completed.
This was the third verification attempt for these VDNs.
Cooper management was f
ed that APS considered their actions to be ineffective and untimely to resolve the deficiencies.
At the conclusio reaudit Vendor Quality requested that a meeting with senior Cooper management be scheduled in an attempt to expedite closure of the deficiencies.
B.
June 6-2 990:
A reaudit was conducted at the En-Tronics facility to evaluate the corrective actions implemented to resolve the findings issued during the qualification survey.
During the reaudit the audit team was unsuccessful in obtaining sufficient documented evidence to support closure of the findings.
The audit team determined t at nsu c
h i ufficient corrective actions had been implemented, and identified the need for Cooper management to intensify required to resolve the deficiencies.
Based on this reaudit 100%
source inspection requirements were imposed at the En-tronics facility.
June 28-29 1990:
dit was performed at the Rotating facility to re-assess the i
1 t tion of corrective actions for VDNs 8
A reau t was p
mp emen a
he third attempt to close these findings and again a n Vendor was t e t r
a Quality determined that Cooper had not implemente a eq d ade uate actions to correct the deficiencies.
Based on the results of this
- reaudit, the amount of time the deficiencies had remained
- open, d
t urce inspections performed, 100% source inspection lit.
requirements were also imposed at the Rotating faci ty.
2.
ou ce urve a
e Twenty-one sa ety-re a
e f
lated purchase orders were subject to source o su ort the surveillance n
p 1
1990.
A proximately 23 trips were taken to supp ce.trend.
project.
Reject on s a
i t tistics are reflected on the performan Surveillances in this year reflected a significant improvement in Coopers procurement, ven or qua d
ualification, dedication and inspection controls.
APS waived surveillance on selective items such as nuts, bolts o-rings, couplings gaskets, strainers.
SECTION X Overview of Activities - 1991
~udge ts A joint audit of Cooper Divisions is scheduled for September 1991.
o Entronics o
Reciprocating o
Rotating APS Vendor Quality Engineering will be leading the audit and Commonwealth Edison will participate.
ou ce urveil ance As of April 30, 1991 seven safety-related purchase orders were subjected to source surveillance by APS.
Approximately nine trips were taken to support the project.
Rejection statistics are reflected on the performance trend.
Our surveillances to date have indicated a downward trend in parts acceptability.
APS has re-imposed 1001 surveillance.
I r
% Rejection Rate ESG Supplier Performance Trend
{1987 - 1991)
Number of Source Surveillances/Inspections 80 Number of Survelllances/inspections identifying deficiencies Number of Surveillances/inspections 80
?0
~
% Rejection Rete
?0 60 61%
60 40 40 30 30 20 10 0
h lt I"
o A
etio 15 1988 1989 ga+Q hV 1990 1991 (1 st 4 Mos.)
20 10 0
0 I
f 1
p
SECTION XI By overview of audits/reaudits and 100% surveillance activities that APS has been involved at the Cooper facilities to ensure items received comply with requirements.
Commercial dedication was a concern and was identified to Cooper in June 1986:
o Audits conducted in 1986,
- 1987, and 1988.
o Surveillance activities since 1987.
o VQE assistance in development of Coopers current program.
Parts classification was addressed to Cooper:
o December 1987 audit of Reciprocating.
o December 1988 audit of Rotating.
o Surveillance activities since 1987.
APS has had positive controls in place to ensure product quality.
That the proactiveness exhibited here is our philosophy of how we interact with all of our vendors.
This was confirmed by the 1990 NRC diagnostic report which stated that Vendor Quality was a strength of the quality organization.