Forwards Final Response to NRC Bulletin 88-010 & Suppl 1, Nonconforming Molded-Case Circuit Breakers. High Percentage of Acceptable Circuit Breakers Stored at Facility Warehouse Reflects High Confidence Factor in Procurement
ML17305A479
Person / Time
Site: Palo Verde  
Issue date: 12/27/1989
From: Conway W
ARIZONA PUBLIC SERVICE CO. (FORMERLY ARIZONA NUCLEAR
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
161-02724-WFC-J, 161-2724-WFC-J, IEB-88-010, IEB-88-10, NUDOCS 9001190405
Download: ML17305A479 (26)


Text

gCCE~RATED DRKBUTION DEMO4S1%TION SYSTEM REGUIATORY INFORMATION DISTRIBUTION SYSTEM (RIDS)

ACCESSION NBR:9001190405 DOC.DATE: 89/12/27 NOTARIZED: YES DOCKET I FACIL:STN-50-528 Palo Verde Nuclear Station, Unit 1, Arizona Publi 05000528 STN-50-529 Palo Verde Nuclear Station, Unit 2, Arizona Publi 05000529 STN-50-530 Palo Verde Nuclear Station, Unit 3, Arizona Publi 05000530 AUTH.NAME AUTHOR AFFILIATION CONWAYPW.F.

Arizona Public Service Co. (formerly Arizona Nuclear Power RECZP.NAME RECIPIENT AFFILIATION

, Document Control Branch (Document Control Desk)

SUBJECT:

Forwards final response to NRC Bulletin 88-010 a Suppl 1, "Nonconforming Molded-Case Circuit Breakers."

DISTRIBUTION CODE:

IE21D COPIES RECEIVED:LTR g ENCL

/

SIZE:

TITLE: Bulletin Response 88-10 Nonconforming Molded Case Circuit Breakers.

NOTES: Standardized plant.

Standardized plant.

05000528 05000529 g

05000530 RECIPIENT ID CODE/NAME PD5 LA CHANPT PETERSONPS.

INTERNAL: AEOD/DOA NRR DOEA/GCB 11 NRR GUILLENgJ NRR STONE,J.C.

NRR/DOEA/OEAB11 NRR/DREP/PEPB9D ILRB12

- 6 FILE 02 RGN5 LE 01 COPIES LTTR ENCL 1

0 1

1 1

1 1

1 1

1 1

1 1

1 1

1 1

1 1

1 1

1 1

1 RECIPIENT ID CODE/NAME PD5 PD DAVIS,M.

AEOD/DSP/TPAB NRR GILLPA.S.

NRR POTAPOUSPU NRR/DET/EMEB9H3 NRR/DOEA/OGCB11 NRR/DST 8E2

.NUDOCS-ABSTRACT RES/DSIR/EIB COP1ES LTTR ENCL 1

1 1

1 1

1 1

1 1

1 1

1 1

1 1

1 1

1 1

1 EXTERNAL: LPDR NSZC NOTES:

1 1

1 1

1 1

NRC PDR 1

1 NAZE Zl3 ALL 'RIES" RECIPIENTS:

PLEASE HELP US IO KKQCB HASTE!

CORIACT THE DOCUMEÃZ CXKZROL DESK, RGB Pl-37 (EXT. 20079)

KO ELXHXKQR YOOR MME HKH DISTBZBUTZCII LISTS FOR DCCUMEHIS KXJ DGHPT NEEDf D

TOTAL NUMBER OF COPIES REQUIRED:

LTTR 26 ENCL 25

Arizona Public Service Company P.O. 8OX 53999

~

PHOENIX. ARIZONA85072-3999 WILLIAMF. CONWAY EXECUTIVEVICEPRESIDENT NUCLEAR 161-02724-WFC/JMQ December 27, 1989 Docket Nos.

STN 50-528/529/530 Document Control Desk U. S. Nuclear Regulatory Commission Mail Station Pl-37 Washington, D.

C.

20555

References:

(1)

Letter from NRC to all Holders of Operating Licenses or Construction Permits for Nuclear Power Reactors dated November 22, 1988.

Subject:

NRC Bulletin 88-10, "Nonconforming Molded-Case Circuit Breakers (2)

Letter from D. B. Karner,

APS, (161-01808),

to NRC dated March 30, 1989.

Subject:

Response

to NRC Bulletin 88-10, "Nonconforming Molded-Case Circuit Breakers (3)

Letter from NRC to NUMARC dated February 17, 1989.

Subject:

NRC Comments on NUMARC's Draft Clarification of NRC Bulletin 88-10 (4)

Letter from NRC to all Holders of Operating Licenses or Construction Permits for Nuclear Power Reactors dated August 3, 1989.

Subject:

NRC Bulletin 88-10, "Supplement 1

Nonconforming Molded-Case Circuit Breakers"

Dear Sirs:

Subject:

Palo Verde Nuclear Generating Station (PVNGS)

Units 1, 2, and 3

Response

to NRC Bulletin 88-10 and Supplement 1, Nonconforming Molded Case Circuit Breakers File:

89-056-026 Attached is the PVNGS final response to NRC Bulletin 88-10.

If you have any questions on this matter, please call Mr. A.

C.

Rogers of my staff at (602) 340-4041.

Sincerely, 9001190405 S91227 PDR ADOCK 05000528 8

PNU

t II

Document Control Desk U. S. Nuclear Regulatory Commission Page 2

161-02724-WFC/JMQ December 27, 1989 WFC/JMQ/jle Attachment CC'.

B.

M. J.

T. L.

T ~ J 0 G.

W.

A. C.

A. H.

Martin Davis Chan Polich Knighton Gehr Gutterman (all w/attachment)

It H

I/

161-02724-WFC/JMg December 27, 1989 STATE OF ARIZONA

)

)

SS

~

COUNTY OF HARICOPA

)

I, Vi.

F.

Conway, represent that I am Executive Vice President
Nuclear, that the foregoing document has been signed by me on behalf of Arizona Public Service Company with full authority to do so, that I have read such document and know its contents, and that to the best of my knowledge and belief, the statements made therein are true and correct.

W.

F Conwa Sworn to before me this day of IQ~

~,<~ iaaf, 1989.

Notary Public Hy Commission Expires:

MfCQwMgg QPjgg Jggg 5 1ggy

I I

l

Res onse to NRC Bulletin 88-10 and Su lement 1:

Nonconformin Molded-Case Circuit Breakers The following summarizes the actions taken by APS for each of the Bulletin's "Actions Requested,"

Item Nos. (AI) 1 thru 8 of Bulletin 88-10.

1-Per this requested action item, the Molded Case Circuit Breakers (MCCBs) stored in the PVNGS warehouse, classified for use or potential use in safety related applications, were identified.

The total number of CBs identified was 1309, thus exceeding the required minimum sample of 50 CBs.

As a result, no installed CBs were required to be removed from the plant safety related systems to form the 50 CB minimum required sample.

The traceability and/or acceptance

status, as defined within the context of the Bulletin, was verified for 1240 CBs of the 1309 CBs identified. Of the 1240 CBs, 159 were received prior to August, 1983.

This effort resulted in the traceability/acceptance of 94.73% of the CB (i.e., 1240) and the rejection of 5.27% of the CBs (i.e., 69).

Attachment 1 includes a complete listing of the non-traceable CBs with all the associated information (i.e., manufacturer, model number and the procurement chain when available).

2-This requested action item is considered not applicable to PVNGS since no installed CBs were recovered per AI 1. In addition, a justification for continued operation willnot be required for the case of the non-traceable CB described in the response to AI 5 below.

'This CB was discovered during the current Unit 1 outage and will be removed prior to the start-up of the Unit 1.

3-Based on the 80% or more CB traceability to the Circuit Breaker Manufacturer (CBM),

this action item requires testing of the non-traceable CBs per the test criteria as set forth in the Bulletin. Per Reference 3 (paragraphs 4 and 5), the NRC intent for the testing of non-traceable CBs is to demonstrate the proper operability of these CBs in the case where proper replacements are not readily available.

It is stated, however, that "The Staff willnot require utilities to test stored non-traceable MCCBs but willrequire, in lieu of testing, all non-traceable breakers be considered failed within the context of the Bulletin." As a result, APS has opted not to perform any testing on the non-traceable CBs identified in the response to AI 1, but rather to remove the identified non-traceable CBs from PVNGS warehouse stock.

In addition, per the stated NUMARC recommendation, APS willalso quarantine the non-traceable CBs for the requested one year period.

4-This requested action item requires that ifmore than 10% of the non-traceable CBs fail the proposed Bulletin's tests, all molded-case CBs purchased between August 1, 1983 and August 1, 1988, be identified, traceability verified and all associated information identified (i.e., model number, manufacturer, installation application and procurement chain).

In lieu of testing, PVNGS has considered that all non-traceable CBs failed the Bulletin's required tests.

PAGE 1'

I

In response to this item, reference is again being made to the Staff's clarifications of Bulletin 88-10 (Reference 3). Per paragraph 4, "...Given the existing language of Bulletin 88-10, this requires utilities with even a small percentage of non-traceable breakers to proceed with AIs 4 and 5.

The Staff will, on a case by case basis only, consider the circumstances of individual utilities with a very small number of non-traceable MCCBs.

Provided all non-traceable MCCBs can be accounted for and the circumstances contributing to the non-traceable stock do not suggest repeatable programmatic breakdowns of the utilityprocurement practices, the staff may relieve utilities from AI's 4 and 5 and instead requires only the removal from stock of the non-traceable MCCBs...."

Based on the above provision, APS has met the intent of this action item, based on the following justification and other actions taken in support of Bulletin 88-10 and Supplement 1:

a)

The high percentage of traceable/acceptable CBs (i.e., 95%) stored in PVNGS'arehouse, for safety related (SR) service totaling 1240 CBs, reflects a very high confidence factor in the procurement, storage and application programs of safety related (SR) CBs at PVNGS.

b)

APS assessed and accounted for the installed CBs, that were procured under non-traceable purchase orders, identified as a result of the PVNGS warehouse inspections (see AI 5).

c)

The 5% (69) non-traceable CBs are divided into two categories; MRS (Material Returned to Stores) rejects (21 CBs) and supplier rejects (48 CBs).

The MRS CBs were returned to the warehouse stock, after being tested for acceptability per PVNGS test procedures, either from PVNGS original plant equipment or after being released from the warehouse for the plant's use.

Documentation relating the MRS CBs to a particular purchase order does not exist, thus deeming these CBs as non-traceable per the guidelines of Bulletin 88-10.

Forty two of the non-traceable CBs from the supplier rejects category were procured from three of PVNGS'ajor equipment suppliers of safety related equipment:

Combustion Engineering (CE, the NSSS supplier), Cooper (Safety Related Diesel Generator supplier) and Elgar (Inverter supplier).

All of the non-traceable CBs were procured as class IE SR from an approved PVNGS vendor and with a certificate of compliance.

The other six CBs that belong to the supplier rejects category were procured from a local distributor (J. E. Redmond) thru a regional distributor (MAG-TROL).

Although both vendors produced traceability and procurement records for only selling new and factory originated CBs, their records were not kept for more than Gve years.

Due to the procurement date of the six CBs (August, 1983) these CBs were deemed non-traceable, since no traceability documentation was found.

PAGE 2

The described circumstances and non-traceability cases definitely do not suggest repeatable programmatic breakdowns of PVNGS procurement practices.

As stated earlier and during the performance of AI 1, it was clearly identified that a great majority of the CBs were traceable to the CBM.

d)

As indicated in Reference 2, during the five years covering August 1, 1983, through August 1, 1988, there were only four Engineering Change Evaluations (ECEs) for commercial grade dedication of molded-case circuit breakers.

In all of the four identified cases the molded-case CBs were traced back to the CBM.

There was another commercial grade dedication

case, however, that identified non-automatic type CBs, classified as molded-case switches which did not contain any overcurrent trip mechanisms.

These switches were determined to be non-traceable and, although were not considered to be within the scope of the Bulletin, were addressed immediately upon discovery and replaced in all PVNGS'nits per PNVGS internal procedures, regulatory and reportability requirements.

5-This requested action requires the replacement of all non-traceable molded-case CBs installed in safety related systems with CBs that meet the traceability criteria of Bulletin 88-10.

As a result of this action item, PVNGS has identified only two cases of non-traceable molded-case CBs, resultant from the warehouse inspections.

In one case, two CBs, although classified for safety related applications, were issued for use in a non-safety related application as part of a PVNGS temporary modification.

In the second case, two CBs were issued for use in a safety related application in Unit 1. As a result, a PVNGS work order has been issued to replace the installed CB during the current PVNGS Unit 1 outage.

All the other non-traceable molded-case CBs, part of the purchase orders listed in Attachment 1, are accounted for and currently quarantined in the PVNGS warehouse, as previously indicated in the response to AI 1 above.

This response also meets the NRC position "4" requirements of Bulletin 88-10, Supple-ment 1.

6-This requested action requires the documentation and maintenance of the generated information while performing the required actions for Bulletin 88-10 for a period of five

years, As requested, PVNGS willbe maintaining all the generated documentation in an auditable form.

7-This requested action requires that molded-case CBs installed after August 1, 1988, be procured and dedicated per the Bulletin's stated criteria.

As a result of this requested action, PNVGS procurement and dedication practices for molded-case CBs are being revised to meet or exceed the criteria delineated in Bulletin 88-10 (delineated in Section 4 of the attached report).

In addition, per the response to AI 5 above, non-traceable molded-case CBs were identified and replaced.

PAGE 3

I l

8-This requested action item is for addressees who cannot meet the schedule for responding to the Bulletin by April 1, 1989, to provide and justify to the NRC their proposed alternative schedule.

As a result, per Reference 2, APS requested an extension for submitting the final Bulletin's response by December 31, 1989.

Based on the above actions taken, the intent and requirements of NRC Bulletin 88-10 and Supplement 1

have been met.

Per Bulletin 88-10 and Supplement 1

reporting requirements, APS confirms that only molded-case CBs that meet the requirements of AI 7 above, are being maintained as stored spares for future use in safety related applications.

In addition, the information pertaining to the non-traceable CBs is being provided as part of the Attachment 1.

APS also confirms that items 1 thru 7 of the Bulletin's requested actions have been satisfactorily addressed and/or completed.

PAGE 4

1'

ATTACHMENT 1 NRC BULLETIN 88-10 SAFETY RELATED MOLDED CASE CIRCUIT BREAKERS NON-TRACEABLE REJECTION

SUMMARY

ANPP PKG¹ Glass/

Item 4441-STY Purchase Order/

Material Receiving gausst DESCRIPTION REJECTION BASIS 086 9

5 60117307/

861006895 AM2-A3A-10-2 HEINEMANN No S/N*

C-E could not provide traceability to the CBM (Reference C-E Letter Ext 89-144, dated 09/01/89) 004C 11 1

MRS23709 THED126015 GE 15A, 2POLE S/N N3709000046 Material returned from unit and returned to stock.

Traceability to purchase order could not be esta-blished.

004C 11 050 11 1

MRS24548 THED126015 GE 15A, 2POLE S/N N3709000005 1

MRS18347 THED126015 GE 15A, 2POLE S/N N4609100004 Unable to locate MRS copy.

Material returned from unit and returned to stock.

Traceablity to purchase order could not be esta-blished.

021 14 008 14 077 14 1

F174639/

AM2-A3A-15-2 206948 HEINEMANN (For QSPD System)

No S/N 1

13NM001A/

AM2-A3A-15-2 177470 HEINEMANN (for QSPD System)

No S/N 4

60110023/

AM2-A3A-15-2 860814432

,HEINEMANN (for QSPD System)

No S/N C-E could not provide traceability to the CBM (reference C-E Letter Ext-89-144, dated 09/01/89)

C-E could not provide traceability to the CBM (reference C-E letter Ext-89-144, dated 09/Ol/89)

C-E could not provide traceability to the CBM (reference C-E letter Ext-89-144, dated (09/01/89)

  • S/N - Serial Number

1

Class/

ANPP Item PKG¹ '441-QTY Purchase Order/

Materia1 Requiring Receuest DESCRIPTION REJECTION BASIS 050 34 2

MRS18347 THED126090 GE 90A, 2POLE S/N's N6762390048 N6762390052 Material returned from unit and returned to stock.

Traceability to purchase order could not be esta-blished.

069 71 4

33700299/

THJK426FOOO 860776212 GE No S/N Elgar's supplier GESCO cannot supply traceability to GE (Reference Elgar letter dated 10/18/89) 067 71 6

33700255/

THJK426FOOO 85047745 GE No S/N Elgar's supplier GESCO cannot supply traceability to GE (Reference Elgar letter dated 10/18/89) 053 123 2

NO PO CD2-A3-DU HEINEMANN

15A, 240VAC No S/N Breaker stored without traceability to a PO or MRS.

101 123 3

60140015/

CD2-A3-DU 871201038 HEINEMANN No S/N C-E could not provide traceability to the CBM (reference C-E letter Ext-89-144, Dated 09/Ol/89) 013 123 1

F169196/

CD2-A3-DU 205405 HEINEMANN No S/N 041 140 027 141 1

F180818/

2-01E-028-038 218328 HEINEMANN S/N 8612-2 028 141 1

F176577/

2-01E-028-030 204135 GE 70A, 2POLE S/N 128771

  • S/N - Serial Number 1

F176575/

TED124070 204135 GE 70A, 2POLE S/N 128770 C-E could not provide traceability to the CBM (Reference C-E letter Ext-89-144, dated 09/Ol/89)

Cooper could not provide traceability to the CBM Source Surveillance (Cooper)

- unable to establish traceability to the CBM.

(Reference letter 028-01814 WPP/MDF)

Source Surveillance (Cooper) unable to establish traceability to t:he CBM.

(Reference letter 028-01814 WPP/MDF)

fl I

ANPP PKG¹ Class/

Item 4441-QTY Purchase Order Material/

Requiring Roue et DESCRIPTION REJECTION BASIS 049 141 1

MRS18315 TED124070 GE 70A, 2POLE No S/N Material returned from unit and returned to stock.

Traceability to purchase order could not be esta-blished.

027 142 028 142 1

F176575/

2-01E-028-026 208809 HEINEMANN 5A, 1POLE No S/N 1

F176577/

2-01E-028-026 205422 HEINEMANN 5A, 1POLE No S/N Source surveillance (Cooper) unable to establish traceability to the CBM.

(Reference letter 028-01814 WPP/MDF)

Source surveillance (Cooper) unable to establish traceability to the CBM.

(Reference letter 028-01814 WPP/MDF) 028 143 1

F176577/

2-01E-028-017 204134 HEINEMANN 1163A No S/N Source surveillance (Cooper) unable to establish traceability to the CBM.

(Reference letter 028-01814

- WPP/MDF) 097 143 027 143 050 240 6

60133325/

2-01E-028-017 861018400 HEINEMANN 1163A

'o S/N 1

F176575/

2-01E-028-017 204135 HEINEMANN 1163A No S/N 1

MRS18347 THED113CB020 GE 20A, 1POLE S/N N4651300010 Source surveillance (Cooper) unable to establish traceability to the CBM.

(Reference letter 028-01814

- WPP/MDF)

Source surveillance (Cooper) unable to establish traceability to the CBM.

(Reference letter 028-01814 WPP/MDF)

Material returned from unit and returned to stock.

Traceability to purchase order could not be esta-blished.

046 260

  • S/N - Serial Number 1

MRS18303 THED136015N GE 15A, 1POLE S/N N780T280003 Material returned from unit and returned to stock.

Traceability to purchase order could not be esta-blished.

II I

J Il

ANPP PKG¹ Class/

Item 4441-QTY Purchase Order/

Material Requiring

~Re eeet DESCRIPTION REJECTION BASIS 100 484 3

60139040/

871162288 N852-103-08 GE No S/N Elgar's supplier GESCO cannot supply traceability to GE (Reference Elgar letter dated 10/18/89) 054 564 3

33400041/

TEC36015S 830229361 GE 15A, 3POLE No S/N J.

E. Redmond's

supplier, Magtrol unable to provide traceability to the CBM.

Both suppliers maintain their PO records for a period of 5 years; PO was issued in 1983.=

054 568 3

33400041/

TEC36050S 830229361 GE 50A, 3POLE No S/N J.

E. Redmond's

supplier, Magtrol unable to provide traceability to the CBM.

Both suppliers maintain their PO records for a period of 5 years; PO was issued in 1983.

051 576 1

MRS23745 THED136050 GE 50A, 3POLE No S/N Material returned from unit and returned to stock.

Traceabili.ty to purchase order could not be esta-blished.

052 576 1

MRS24625 THED136050 GE 50A, 3POLE S/N N890T410007 Material returned from unit and returned to stock.

Traceability to purchase order could not be esta-blished.

046 576 1

MRS18303 THED136050 GE 50A, 3POLE No S/N Material returned from unit and returned to stock.

Traceability to purchase order could not be esta-blished.

048 577 2

MRS18314 THED136070 GE 70AI 3POLE QTY 1 No S/N S/N N1095970010 Material returned from unit and returned to stock.

Traceabili.ty to purchase order could not be esta-blished.

  • S/N - Serial Number

t

Class/

ANPP Item PKG¹ 4441-QTY Purchase Order/

Material Requiring

~Re eeet DESCRIPTION REJECTION BASIS 006 600 1

13MM018/

191962 55519 ITEM 9 WESTINGHOUSE EB1015 No S/N Source surveillance (Cooper) unable to establish traceability to the CBM.

(Reference letter 028-01814 WPP/MDF) 002A 604 006 615 2

MRS18311 THFK236070 GE 70A, 3POLE No S/N 1

MRS18303 THED136070N GE 70A, 3POLE S/N N890T410016 Unable to locate MRS copy Material returned from unit and returned to stock.

Traceability to purchase order could not be esta-blished.

047 616 3

MRS18310 THFK236125 GE 125A, 3POLE Qty 1 No S/N Material returned from unit and returned to stock.

Traceability to purchase order could not be esta-blished.

  • S/N - Serial Number