ENCLOSURE
1
Florida Power and Light Company
St.
Lucie
Docket Nos.
50-335
and 50-389
License
Nos.
The
following violations
were
identified
during
an
inspection
conducted
on
.
March
12 - April 8,
1985.
The Severity Levels were assigned
in accordance
with
the
NRC Enforcement Policy (10 CFR Part 2, Appendix C).
1.
Technical
Specification
Table 4.8-2 requires
that battery specific gravity
be corrected for electrolyte level.
Contrary to the
above,
the licensee's
surveillance
programs
do not correct
battery specific gravity for electrolyte level.
This is
a Severity
Level
IV violation (Supplement
1).
2.
10 CFR 50 Appendix B, Criterion V, as
implemented
by Florida Power
and Light
Company Topical guali ty Assurance
Report
1-76A,
Revision
7, requires that
activities affecting
quality
shall
be
accomplished
in
accordance
with
instructions,
procedures
or drawings.
Contrary to the
above,
the safety-related
batteries
were not installed
in
accordance
with
approved
drawings
8770-9998,
Rev.
1
and
2998-14664,
Rev.
1.
Nonconformances
included
missing tie
rods,
missing bolts,
the
pattern of tie rods
and the
end clearance
between
the battery bank and tray
end.
This is
a Severity Level IV violation (Supplement
1).
I
Pursuant
to
you are required
to submit to this office within 30
days of the date of this Notice,
a written statement
or explanation
in reply,
including:
(1) admission
or denial
of the alleged violations;
(2) the
reasons
for the violations if admitted;
(3) the corrective
steps
which have
been
taken
and
the results
achieved;
(4) corrective
steps
which will be
taken to avoid
further violations;
and $ 5) the date
when full compliance will be achieved.
Security
or
safeguards
information
should
be
submitted
as
an
enclosure
to
facilitate withholding it from public disclosure
as required
or 10 CFR 73.21.
MAY 08
1985
Date:
8506Zi05i4 850508
ADOCK 05000335
Q