ML17296B298

From kanterella
Jump to navigation Jump to search
Responds to IE Bulletin 80-16, Potential Misapplication of Rosemont Inc Models 1151 & 1152 Pressure Transmitters W/ Either a or D Output Codes. Transmitters Supplied by Atomics Intl,Anchor/Darling & Cooper
ML17296B298
Person / Time
Site: Palo Verde  Arizona Public Service icon.png
Issue date: 02/09/1981
From: Van Brunt E
ARIZONA PUBLIC SERVICE CO. (FORMERLY ARIZONA NUCLEAR
To: Engelken R
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION V)
References
ANPP-17257, IEB-80-16, NUDOCS 8103230870
Download: ML17296B298 (4)


Text

WWWE IIV IÃ CIDKQIW5W'P P. O. BOX 2I666 ~

PHOENIX ARIZONA BSO36 February 9, 1981 ANPP-17257 - JMA/KEJ Docket Nos. 50-528, 50-529, 50-530 Mr. R. H. Engelken, Director Nuclear Regulatory Commission Region V 1900 N. California Boulevard Suite 202 Walnut Creek Plaza Walnut Creek, California 94596

Subject:

NRC I8E Bulletin No. 80-16 Potential Misapplication of Rosemount Inc. Models 1151 and 1152 Pressure Transmitters with Either "A" or "D" Output Codes File: 81-055-026

Reference:

ANPP-16140 JMA/WFQ dated August ll, 1980

Dear Mr. Engelken:

In the above referenced letter, ANPP reported that no Rosemount, Inc.

Model 1151 and 1152 Pressure Transmitters were used in any safety-related applications on PVNGS. This response was based on a review of the Bechtel purchase orders, but a survey of the subtier suppliers was not conducted prior to providing these responses. However, during a subsequent review of the subject Bulletin done by Bechtel, Anchor Darling Valve Company was contacted and they verified usage of the Rosemount transmitters in safety-related equipment. As a result of this information, another detailed -reivew was initiated to recheck all safety-related purchase orders for the possible application of Rosemount transmitters by the prime suppliers to Bechtel. The detailed review indicated th'at the subject transmitters are being used by three (3) suppliers of safety-related equipment. Those three suppliers are Atomics International, Anchor Darling, Inc., and Cooper Bessmer. Atomics International and Anchor Darling use the subject transmitters in Class IE applications. The application by Cooper Bessmer is not Class IE.

Atomics International is using the subject transmitters on the thermal hydrogen recombiners . An evaluation was made by Atomics International in response to the referenced NRC Bulletin. A Rosemount differential pressure transmitter is used on the recombiner in the flowmeter instrument loop. The anomalous operation reported in the referenced NRC Bulletin>

+

[-t->~~~ iQ ~sqI

"~II:Ik V I'>8emIOM e OIFORCOgIP p Cr

S l'l

, II h

i h J

1 i

s 'h ~'

r I t

I ll Q1 1

8

Mr. R. H. Engelken, Director February 9, 1981 ANPP-17257 - JMA/KEJ Page 2 cannot occur for the transmitter application on the recombiners due to the range settings used in this case. The Rosemount Model 1152DP4A22 (Output Code "A") being used has range limits of 0 to 150 in. of water.

The range setting for the transmitters used on the recombiners is 0 to 40 in. of water (maximum). According to Rosemount's evaluation, the ambiguous output does not occur until the over-pressure condition is 140/ of the upper range limit of the transmitter, regardless of the span setting.

Ambiguous transmitter output was also reported to occur if a reverse pressure condition should occur. A reverse pressure is not possible in the recombiner application'. When the blower is not operating (i .e.,

providing a positive pressure differential), the differential pressure across the flow element is zero. Also, the recombiner has a low flow alarm which precludes the possibility of the operator not knowing when the flow (differential pressure) has decreased to a below-normal condition.

Anchor Darling Valve Company uses the subject transmitters in the hydraulic actuator package to provide a means to remotely monitor the accumulator (N2) pressure. The nitrogen pressure can normally range from 2,500 psig to 5,000 psig. The pressure transmitters have all been calibrated for the range of 2,500 psig to 6,000 psig. For an ambiguous signal to occur, the high pressure would have to exceed 8,400 psig (6,000 x 140K) or the low pressure would have to be less than zero. Neither condition will occur on the A/DV hydraulic actuator if the actuator and transmitter calibrations are properly maintained.

We believe that with the information presented, the potential defect as described by the Rosemount 10 CFR Part 21 report would not impact or impair the intended function of the equipment being supplied since the intended applications are within the calibrated range of the transmitter. This report supplements and clarifies the original project disposition to the NRC IE Bulletin 80-16.

If any further information is needed, please feel free to contact us.

Very truly ours, C C E. E. Van Brunt, Jr.

APS Vice President, Nuclear Projects ANPP Project Director EEVBJr/KEJ/av cc: G. C. Andognini W. H. Wilson J. M. Allen C. Ferguson J. A. Roedel NRC Office of Inspection and Enforcement F. W. Hartley Division of Reactor Inspection Programs D. B. Fasnacht Washington, D.C. 20555

f