IREE Ml~IIICOKQRMW P. O. BOX 2I666

'HOENIXiARIZONA 85036 March 18, 1980 ANPP-15055 - JMA/WFQ Docket Nos. 50-528,

529, 530 Mr.

R.

H. Engelken, Director U.S. Nuclear Regulatory Commission Region V

202 Walnut Creek Plaza 1990 N. California Boulevard Walnut Creek, California 94591

Subject:

NRC I8E Bulletin No. 80-03 Loss of Charcoal from Standard Type II, 2 Inch Tray Adsorber Cells File:

D.4.01.1

'lO (Fcoilf[J MAR 84 1980

Dear Mr. Engelken:

We have reviewed the design of PVNGS in accordance with the concerns of NRC ISE Bulletin No. 80-03.

The subject Type II tray adsorber cells are not used on PVNGS.

The filtration units for PVNGS use rechargeable, permanent, single-unit adsorbers (PSU).

Perforated plates tach welded on 3/4" centers to the cell'housing are used on the PSU type adsorbers instead of a screen riveted to the housing.

Therefore, there should not be any separation or filter housing deformation to cause loss of charcoal and/or channeling.

Very truly yours, CC V~

E.

E.

Van Brunt, Jr.

APS Vice President, Nuclear Projects ANPP Project Director EEVBJr/WFQ/av cc:

J.

M. Allen J.

A. Roedel F.

W. Hartley L.

W. Price W.

H. Wilson C.

Ferguson NRC Office of Inspection 5 Enforcement Division of Reactor Inspection Programs Washington, D.C.

20555 800V250M

'$0- I&