Proposed Tech Specs Re Surveillance Requirements 4.8.1.1.2.b,c & D to Allow Implementation of More Comprehensive & Effective Fuel Oil Surveillance Program
ML17285B141
Person / Time
Site: Columbia 
Issue date: 03/30/1990
From:
WASHINGTON PUBLIC POWER SUPPLY SYSTEM
To:
Shared Package
ML17285B140 List:
References
NUDOCS 9004100283
Download: ML17285B141 (4)


Text

CONTRQLLEG It."OPY E'LECTPICAL POW=R SYSTEMS SURVEILLANCE REOUIREMENTS (Continued At least once per 31 days and after each operation of the diesel where the period of operation was greater than or equal to 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> y

hecking for and rem>oving accumulated water from the dav fuel nks.

c.

At

~ast once per 92 days by removing accumulated water th fuel stora e tanks.

4 @PI QCK

<+a~I ed At least nce per 92 days and from new fuel oil prio to addition to the storag

tanks, by obtaining a sample obtained accordance with ASTM-D270-1 5,

and by verifying thai the sample eets the following minimum requi ments and is tested within the ecified time limits:

As soon as mple is taken or from ne fuel prior to addition to the s+orag

tank, as applicable, erify in accordance with the iests speci ed in ASTM-D975-that the sample has:

a)

A water and s

iment con ni of less than or equal to 0.05 volume pre nt.

b)

A kinematic viscose 8 40'C of greater than or equal> to 1.9 centistokes, t

ss than or equal to 4. 1 centistokes.

c)

A specific gr

.y as sp i>ied by the manufacturer I 60/60'."" of eater than or qual to 0.8299 but less than or equal 0.8762 or an API ravity 9 60~F of greater than or qual to 30 deorees.

2.

Within 1 eek afier obtaining the sampl verify an impurity level less than 2

mg of insolubles per 00 ml when tested in a ordance'with ASTM-D2274-70."

3.

>thin 2 weeks after obtaining the sample, verif that the other properties specified in Table 1 of ASTM-D975-and Regulatory Guide 1. 137, Position 2.a, are met when tes d in accordance with ASTM-D975-77.

e.

At least once per 18 months, during shutdown, by:

1.

Subjec ing the diesel to an inspection in accordance with procedures prepared in conjunction with its manufacturer's recommendations for this class of standby service.

2.

Verifying the diesel generator capability to reject a load of greater than or equal to 1377 kW for DG-1, greater than or equal to 1377 kv'or DG-2, and greater than or equal to "In lieu of this requirement until May 30, 1990, each of the above required diesel generators shall be demonstrated OPERABLE at least once every 31 days by obtaining a sample of fuel oil from the discharge line of the storage tank ransfer pumps in accordance with ASTM D2276-78, and verifying that total particulate contamina ion is less than 10 mg/liter when checked in accordance with ASTM 02276-78, Method A.

WASHINGTON NUCLEAR - UNIT 2 3/4 8-4 9004i002S3 900330 PDR ADOCK 05000397 PDC

/

Amendm n. No. 76 I

PROPOSED CHANGE TO SURVEILLANCE 4.8.1.1.2 By checking for and removing accumulated free water in the diesel fuel tanks as follows:

1.

Check for and drain any accumulated water from the day tanks at least once per 31 days and after each occasion when the diesel is operated for greater than 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br />.

2.

Check for accumulated water at the bottom of the storage tank below the transfer pump every 31 days.

Initiate the procedure for pumping off accumulated water within 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> of detection.

By sampling new diesel fuel in accordance with ASTH D4057-81 prior to addition to the storage tanks and 1.

By verifying in accordance with the tests specified in ASTH D975-81 prior to addition to the storage tanks that the sample has:

a

~

b.

An API gravity of within 0.3 degrees at 60'F or a specific gravity of within 0.0016 at 60/60'F, when compared to the supplier's certificate or an absolute specific gravity at 60/60'F of greater than or equal to 0.83 but less than or equal to 0.89 or an API gravity at 60'F of greater than or equal to 27 degrees but less than or equal to 39 degrees.

A kinematic viscosity at 40'C of greater than or equal to 1.9 centistokes, but less than or equal to 4. 1 centistokes, if gravity was not determined by comparison with the supplier's certification.

c.

A flash point equal to or greater than 125'F, and d.

A water and sediment content of less than or equal 0.05 volume percent per ASTM D1796-83 or a Clear and Bright appearance with proper color when tested in accordance with ASTH D4176-82.

2.

By verifying within 31 days of obtaining the sample that the other properties specified in Table 1 of ASTM D975-81 are met when tested in accordance with ASTH D975-81 except that the analysis for sulfur may be performed in accordance with ASTH D1552-79 or ASTM D2622-82.

By obtaining a sample, at least once every 31 days of fuel oil from the storage tanks in accordance with ASTH D2276-78, and verifying within 1 week after obtaining the sample that the total particulate contamination is less than 10 mg/liter when checked in accordance with ASTH D2276-78, Method A.

STATE OF WASHINGTON)

COUNTY OF BENTON

)

Subject:

REQUEST FOR AMENDMENT TO TS URV

.1.1.2 I,

G.

C.

Sorensen, being duly
sworn, subscribe to and say that I am the
Manager, Regulatory
Programs, for the WASHINGTON PUBLIC POWER SUPPLY
SYSTEM, the applicant herein; that I have full authority to execute this oath; that I

have reviewed the foregoing; and that to the best of my knowledge, information, and belief the statements made in it are true.

DATE 3-t

ggvf, 1990 G.

C.

orensen, Manager Regulatory Programs On this day personally appeared before me G.

C. Sorensen, to me known to be the individual who executed the foregoing instrument, and acknowledged that he signed the same as his free act and deed for the uses and purposes herein mentioned.

4A GIVEN under my hand and seal this,9 day of, r 1990.

Notay ublic in and r the STATE OF WASHINGTON 1

h 'll I

Residing at

>'Cg ~

My commission expires 7

4 91

J p

4 4

g II U 4 ~

.1IIL' lf P