e(~DUKE

~ ENERGY September 27, 2017 MNS-17-040 ATTN: Document Control Desk U.S. Nuclear Regulatory Commission Washington, DC 20555-0001 Duke Energy Carolinas, LLC (Duke Energy)

McGuire Nuclear Station (MNS), Units 1 and 2 Docket No. 50-369, 50-370 Renewed License No. NPF-9 and NPF-17 Steven D. Capps Vice President McGuire Nuclear Station Duke Energy MG01VP J 12700 Hagers Ferry Road Huntersville, NC 28078 o: 980.875.4805 f: 980.875.4809 Steven.Capps@duke-energy.com 10 CFR 50.54(f) 10 CFR 50.4

Subject:

Supplement to the High Frequency Supplement to Seismic Hazard Screening Report, Response NRC Request for Information Pursuant to 10 CFR 50.54(f)

Regarding Recommendation 2.1 of the Near-Term Task Force Review of Insights from the Fukushima Dai-ichi Accident

References:

1. NRC Letter, Request for Information Pursuant to Title 10 of the Code of Federal Regulations 50.54(f) Regarding Recommendations 2.1, 2.3, and 9.3, of the Near-Term Task Force Review of Insights from the Fukushima Dai-ichi Accident, dated March 12, 2012, ADAMS Accession Number ML12053A340
2. Duke Energy Letter, Seismic Hazard and Screening Report (CEUS Sites), Response to NRC 10 CFR 50.54(f) Request for Information Pursuant to Title 10 of the Code of Federal Regulations 50.54(f) regarding Recommendations 2.1, 2.3 and 9.3 of the Near-Term Task Force Review of Insights from the Fukushima Dai-ichi Accident, dated March 20, 2014, ADAMS Accession Number ML14098A421
3. NRC Letter, Screening and Prioritization Results regarding information pursuant to Title 10 of the Code of Federal Regulations 50.54(f) regarding seismic Hazard Reevaluations for Recommendation 2.1 of the Near-Term Task Force Reviews of Insights from the Fukushima Dai-ichi accident, dated May 9, 2014, ADAMS Accession Number ML14111A147
4. Duke Energy Letter, High Frequency Supplement to Seismic Hazard Screening Report, Response NRC Request for Information Pursuant to 10 CFR 50.54(f) Regarding Recommendation 2.1 of the Near-Term Task Force Review of Insights from the Fukushima Dai-ichi Accident, dated August 10, 2017, ADAMS Accession Number ML17230A088

U. S. Nuclear Regulatory Commission MNS-17-040 Page 2 On March 12, 2012, the Nuclear Regulatory Commission (NRC) issued a Request for Information per 10 CFR 50.54(f) (Reference 1) to all power reactor licensees. The required response section of Enclosure 1 indicated that licensees should provide a Seismic Hazard Evaluation and Screening Report within 1.5 years from the date of the letter for Central and Eastern United States (CEUS) nuclear power plants.

In response to the 50.54(f) letter, McGuire Nuclear Station (MNS) submitted the reevaluated seismic hazards on March 20, 2014 (Reference 2). By letter dated May 9, 2014 (Reference 3),

the NRC transmitted the initial results of the screening and prioritization review of the seismic hazards reevaluation submittal for MNS. As noted in the May 9, 2014 letter, MNS is to conduct limited-scope evaluations (i.e., spent fuel pool, and high frequency).

By letter dated August 10, 2017 (Reference 4), Duke Energy submitted the Seismic High Frequency Confirmation Report for McGuire. Within the report, a summary of the high-frequency evaluation conclusion was provided in Table B-1 in Appendix B. As summarized in Table B-1 in Appendix B, 289 of the devices have adequate seismic capacity, and 28 components required resolution following the criteria in Section 4.6 of Electric Power Research Institute (EPRI) report entitled, "High Frequency Program, Application Guidance for Functional Confirmation and Fragility Evaluation" (EPRI 3002004396). In response to a recent inquiry by NRC, Duke Energy has reevaluated the 28 components that required resolution using Section 4.6 of the EPRI report. The reevaluation results shows that all 28 component outliers have been resolved by operator action within existing plant procedures in accordance with Section 4.6.3, Operator Actions, of the EPRI report.

The attachment to this letter provides an update to Table B-1, Components Identified for High Frequency Confirmation in Appendix B of the Seismic High Frequency Confirmation Report for McGuire showing the results from the reevaluation.

This letter contains no new Regulatory Commitments and no revision to existing Regulatory Commitments Please address any comments or questions regarding this matter to Joseph Hussey at 980-875-5045.

I declare under penalty of perjury that the foregoing is true and correct. Executed on September 27, 2017.

Sincerely, Steven D Capps

Attachment:

Table B-1, Components Identified for High Frequency Confirmation

U. S. Nuclear Regulatory Commission MNS-17-040 Page 3 xc:

C. Haney Region II Administrator U.S. Nuclear Regulatory Commission Marquis One Tower 245 Peachtree Center Avenue NE, Suite 1200 Atlanta, GA 30303-1257 J.P. Saska, Project Manager U.S. Nuclear Regulatory Commission One White Flint North 11555 Rockville Pike Rockville, MD 20852-2738 M. Mahoney Project Manager (MNS)

U.S. Nuclear Regulatory Commission 11555 Rockville Pike Mail Stop 8 G9A Rockville, MD 20852-2738 G.A. Hutto NRC Senior Resident Inspector McGuire Nuclear Station Justin Folkwein American Nuclear Insurers 95 Glastonbury, CT. 06033-4453

Table B-1: Components Identified for High Frequency Confirmation Component Enclosure Floor Component Evaluation No.

System Building Elev.

Basis for

J Device ID Type Manufacturer Model ID Type Evaluation Result Function (ft)

Capacity I

l NV24L(BB)

Control Seal-In Auxiliary Relay Cutler-Hammer D26MRD30AI IATC4A Control Auxiliary 733 McGuire Cap> Dem Relay Cabinet Building Report 2

I NV25L(BA)

Control Seal-In Auxiliary Relay Cutler-Hanuner D26MRD30AI IATC4A Control Auxiliary 733 McGuire Cap> Dem Relay Cabinet Building Report 3

I DJ(2TRC)

Control Diesel Start Relay Cutler-Hammer D26MRD70AI IDGCPA Control Diesel 736+06 McGuire Cap> Dem Relay Cabinet Building Report 4

I DK(2TRA)

Control Diesel Start Relay Cutler-Hammer D26MRD704AI IDGCPA Control Diesel 736+06 McGuire Cap> Dem Relay Cabinet Building Report 5

l DL(RVG3)

Control Diesel Stop Relay Cutler-Hammer D26MRD70Al IDGCPA Control Diesel 736+06 McGuire Cap> Dem Relay Cabinet Building Report 6

l EK Control Speed Switch Auxiliary Cutler-Hammer D26MRD70AI IDGCPA Control Diesel 736+06 McGuire Cap> Dem Relay Relay Cabinet Building Report 7

l EL Control Speed Switch Auxiliary Cutler-Hanuner D26MRD70Al IDGCPA Control Diesel 736+06 McGuire Cap> Dem Relay Relay Cabinet Building Report 8

l EM Control Speed Switch Auxiliary Cutler-Hammer D26MRD70Al IDGCPA Control Diesel 736+06 McGuire Cap> Dem Relay Relay Cabinet Building Report 9

I FJ(2TRB)

Control Diesel Start Relay Cutler-Hammer D26MRD704AI IDGCPA Control Diesel 736+06 McGuire Cap> Dem Relay Cabinet Building Report IO I

FL( ARR)

Control Alann Restraint Relay Cutler-Hanuner D26MRD70AI IDGCPA Control Diesel 736+06 McGuire Cap> Dem Relay Cabinet Building Report 11 I

GL(DASR)

Control Diesel Automatic Start Cutler-Hammer D26MRD704AI IDGCPA Control Diesel 736+06 McGuire Cap> Dem Relay Relay Cabinet Building Report 12 l

GM(RVG2)

Control Diesel Stop Relay Cutler-Hanuner D26MRD70AI IDGCPA Control Diesel 736+06 McGuire Cap> Dem Relay Cabinet Building Report 13 l

JJ(SlA2X)

Control Speed Switch Auxiliary Struthers-Dunn 219DXBP IDGCPA Control Diesel 736+06 GERS Cap> Dem Relay Relay Cabinet Building 14 l

JK(SRXl)

Control Lube Oil Low Relay Cutler-Hammer D26MRD70Al IDGCPA Control Diesel 736+o6 McGuire Cap> Dem Relay Cabinet Building Report 15 I

JL(SlAIX)

Control 40% Speed Relay Struthers-Dunn 219BBXP IDGCPA Control Diesel 736+o6 GERS Cap> Dem Relay Cabinet Building 16 I

LN(ESX)

Control Emergency Stop Relay Cutler-Hammer D26MRD70AI IDGCPA Control Diesel 736+06 McGuire Cap> Dem Relay Cabinet Building Report 17 I

LO(SRX2)

Control Lube Oil Low Relay Cutler-Hammer D26MRD70AI IDGCPA Control Diesel 736+06 McGuire Cap> Dem Relay Cabinet Building Report 18 l

MA(lEQCSW7720)

Process Overspeed Switch Dynalco SST-2400A IDGCPA Control Diesel 736+06 McGuire Cap> Dem Switch Cabinet Building Report MNS-17-040

Table B-1: Components Identified for High Frequency Confirmation Component Enclosure Floor Component Evaluation No.

  • =

System Building Elev.

Basis for

i Device ID Type Manufacturer Model ID Type Evaluation Result
  • Function (ft)

Capacity 19 1

MB( 1 EQCSW7730)

Process Overspeed Switch Dynalco SST-2400A lDGCPA Control Diesel 736+06 McGuire Cap> Dem Switch Cabinet Building Report 20 I

MU(SSTA)

Control 95% Speed Relay Struthers-Dunn 219BBXP IDGCPA Control Diesel 736+06 GERS Cap> Dem Relay Cabinet Building 21 1

MV(SSTB)

Control 95% Speed Relay Struthers-Dunn 219BBXP IDGCPA Control Diesel 736+06 GERS Cap> Dem Relay Cabinet Building 22 1

MW(SSTC)

Control 97% Speed Relay Struthers-Dunn 219BBXP IDGCPA Control Diesel 736+06 GERS Cap> Dem Relay Cabinet Building 23 1

DJ(2TRC)

Control Diesel Start Relay Cutler-Hanuner D26MRD70Al IDGCPB Control Diesel 736+06 McGuire Cap> Dem Relay Cabinet Building Report 24 l

DK(2TRA)

Control Diesel Start Relay Cutler-Hammer D26MRD704Al IDGCPB Control Diesel 736+06 McGuire Cap> Dem Relay Cabinet Building Report 25 1

DL(RVG3)

Control Diesel Stop Relay Cutler-Hammer D26MRD70Al IDGCPB Control Diesel 736+06 McGuire Cap> Dem Relay Cabinet Building Report 26 1

EK Control Speed Switch Auxiliary Cutler-Hammer D26MRD70Al IDGCPB Control Diesel 736+06 McGuire Cap> Dem Relay Relay Cabinet Building Report 27 1

EL Control Speed Switch Auxiliary Cutler-Hanuner D26MRD70Al IDGCPB Control Diesel 736+06 McGuire Cap> Dem Relay Relay Cabinet Building Report 28 1

EM Control Speed Switch Auxiliary Cutler-Hammer D26MRD70AI IDGCPB Control Diesel 736+06 McGuire Cap> Dem Relay Relay Cabinet Building Report 29 1

FJ(2TRB)

Control Diesel Start Relay Cutler-Hammer D26MRD704Al lDGCPB Control Diesel 736+06 McGuire Cap> Dem Relay Cabinet Building Report 30 1

FL( ARR)

Control Alann Restraint Relay Cutler-Hammer D26MRD70Al lDGCPB Control Diesel 736+06 McGuire Cap> Dem Relay Cabinet Building Report 31 1

GL(DASR)

Control Diesel Automatic Start Cutler-Hammer D26MRD70AI lDGCPB Control Diesel 736+06 McGuire Cap> Dem Relay Relay Cabinet Building Report 32 1

GM(RVG2)

Control Diesel Stop Relay Cutler-Hammer D26MRD70Al IDGCPB Control Diesel 736+06 McGuire Cap> Dem Relay Cabinet Building Report 33 1

JJ(SlA2X)

Control Speed Switch Auxiliary Strutl1ers-Dunn 219BBXP IDGCPB Control Diesel 736+06 GERS Cap> Dem Relay Relay Cabinet Building 34 I

JK(SRXl)

Control Lube Oil Low Relay Cutler-Hammer D26MRD70AI IDGCPB Control Diesel 736+06 McGuire Cap> Dem Relay Cabinet Building Report 35 1

JL(SlAlX)

Control 40% Speed Relay Struthers-Dunn 219BBXP IDGCPB Control Diesel 736+06 GERS Cap> Dem Relay Cabinet Building 36 1

LN(ESX)

Control Emergency Stop Relay Cutler-Hammer D26MRD70Al IDGCPB Control Diesel 736+06 McGuire Cap> Dem Relay Cabinet Building Report MNS-17-040

Table B-1: Components Identified for High Frequency Confirmation Component Enclosure Floor Component Evaluation No.

  • =

System Bit ii ding Elev.

Basis for

~

Device ID Type Manufacturer Model ID Type Evaluation Result Function (ft)

Capacity 37 1

LO(SRX2)

Control Lube Oil Low Relay Cutler-Hammer D26MRD70AI lDGCPB Control Diesel 736+06 McGuire Cap> Dem Relay Cabinet Building Report 38 1

MA( 1 EQCSW7750)

Process Overspeed Switch Dynalco SST-2400A lDGCPB Control Diesel 736+06 McGuire Cap> Dem Switch Cabinet Building Report 39 1

MB(lEQCSW7760)

Process Overspeed Switch Dynalco SST-2400A

!DGCPB Control Diesel 736+06 McGuire Cap> Dem Switch Cabinet Building Report 40 1

MU(SSTA)

Control 95% Speed Relay Struthers-Dunn 219BBXP lDGCPB Control Diesel 736+06 GERS Cap> Dem Relay Cabinet Building 41 1

MV(SSTB)

Control 95% Speed Relay Struthers-Dunn 219BBXP

!DGCPB Control Diesel 736+06 GERS Cap> Dem Relay Cabinet Building 42 1

MW(SSTC)

Control 97% Speed Relay Struthers-Dunn 219BBXP

!DGCPB Control Diesel 736+o6 GERS Cap> Dem Relay Cabinet Building 43 I

2AB(LRA4)

Control Blackout and/or LOCA Cutler-Hanuner D26MRD704Al

!DGLSA Control Auxiliary 750 McGuire Cap> Dem Relay Relay Cabinet Building Report 44 1

2CA(RA1)

Control Load Actuate Relay Cutler-Hammer D26MRD704Al

!DGLSA Control Auxiliary 750 McGuire Cap> Dem Relay Cabinet Building Report 45 1

2CB(AA1)

Control Auto-Advance Relay Cutler-Hammer D26MRD704Al IDGLSA Control Auxiliary 750 McGuire Cap> Dem Relay Cabinet Building Report 46 1

2DA(RA2)

Control Load Actuate Relay Cutler-Hanuner D26MRD704Al lDGLSA Control Auxiliary 750 McGuire Cap> Dem Relay Cabinet Building Report 47 1

2EA(RA3)

Control Load Actuate Relay Cutler-Hammer D26MRD704Al lDGLSA Control Auxiliary 750 McGuire Cap> Dem Relay Cabinet Building Report 48 I

2FA(RA4)

Control Load Actuate Relay Cutler-Hammer D26MRD704Al lDGLSA Control Auxiliary 750 McGuire Cap> Dem Relay Cabinet Building Report 49 I

2HA(RA6)

Control Load Actuate Relay Cutler-Hammer D26MRD704Al

!DGLSA Control Auxiliary 750 McGuire Cap> Dem Relay Cabinet Building Report 50 1

2HB(RA9)

Control Load Actuate Relay Cutler-Hanuner D26MRD704Al

!DGLSA Control Auxiliary 750 McGuire Cap> Dem Relay Cabinet Building Report 51 I

21A(RA7)

Control Load Actuate Relay Cutler-Hammer D26MRD704AI lDGLSA Control Auxiliary 750 McGuire Cap> Dem Relay Cabinet Building Report 52 1

2IB(RAIO)

Control Load Actuate Relay Cutler-Hammer D26MRD704Al IDGLSA Control Auxiliary 750 McGuire Cap> Dem Relay Cabinet Building Report 53 1

2JA(RA8)

Control Load Actuate Relay Cutler-Hammer D26MRD704Al IDGLSA Control Auxiliary 750 McGuire Cap> Dem Relay Cabinet Building Report 54 I

2JB(RA1 I)

Control Load Actuate Relay Cutler-Hammer D26MRD704Al lDGLSA Control Auxiliary 750 McGuire Cap> Dem Relay Cabinet Building Report MNS-17-040

Table B-1: Components Identified for High Frequency Confirmation Component

  • Enclosure Component Evaluation,

~

Floor No.

System, Building Elev.

.Basis for Evalnatiori Res~lt

~

Device ID Type Manufacturer Model ID Type Function

(ft)

Capacity 55 1

4AA(lEQBR127AX)

Protective Undervoltage Relay

!TE ITE-27H

!DGLSA Control Auxiliary 750 GERS Cap> Dem Relay (211801710)

Cabinet Building 56 1

AA(LSA2)

Control Load Shed Relay Cutler-Hammer D26MRD704Al

!DGLSA Control Auxiliary 750 McGuire Cap> Dem Relay Cabinet Building Report 57 1

AB(LSAl)

Control Load Shed Relay Cutler-Hammer D26MRD704Al lDGLSA Control Auxiliary 750 McGuire Cap> Dem Relay Cabinet Building Report 58 1

BD(lESGAXI)

Control LOCARelay Cutler-Hanuner D26MRD704Al IDGLSA Control Auxiliaiy 750 McGuire Cap> Dem Relay Cabinet Building Report 59 I

CB(l27AX)

Control Undervoltage Auxiliary Cutler-Hammer D26MRD70Al lDGLSA Control Auxiliary 750 McGuire Cap> Dem Relay Relay Cabinet Building Report 60 1

CG(LSATX)

Control DG Breaker Closure Cutler-Hammer D26MRD30AI

!DGLSA Control Auxiliary 750 McGuire Cap> Dem Relay Control Cabinet Building Report 61 1

DC(BOA)

Control Blackout Relay Cutler-Hammer D26MRD704Al

!DGLSA Control Auxiliary 750 McGuire Cap> Dem Relay Cabinet Building Report 62 1

EC(LT2A)

Control Generator Restart Relay Cutler-Hammer D26MRD704Al

!DGLSA Control Auxiliary 750 McGuire Cap> Dem Relay Cabinet Building Report 63 1

FA(RGA)

Control Generator Restart Relay Cutler-Hammer D26MRD70Al

!DGLSA Control Auxiliary 750 McGuire Cap> Dem Relay Cabinet Building Report 64 1

GA(ST4A)

Control Sequence Timer Relay TEMPO 812-1-6-08-0

!DGLSA Control Auxiliary 750 McGuire Cap> Dem Relay Cabinet Building Report 65 I

GB(ST2A)

Control Sequence Timer Relay TEMPO 812-1-6-08-0

!DGLSA Control Auxiliary 750 McGuire Cap> Dem Relay Cabinet Building Report 66 1

GC(LSAT)

Control Load Shed Timer TEMPO 812-1-6-01-0

!DGLSA Control Auxiliary 750 McGuire Cap> Dem Relay Cabinet Building Report 67 1

HA(ST7A)

Control Sequence Timer Relay TEMPO 812-1-6-05-0

!DGLSA Control Auxiliary 750 McGuire Cap> Dem Relay Cabinet Building Report 68 1

HB(ST6A)

Control Sequence Timer Relay TEMPO 812-1-6-05-0 IDGLSA Control Auxiliary 750 McGuire Cap> Dem Relay Cabinet Building Report 69 1

IA(STIOA)

Control Sequence Timer Relay TEMPO 812-1-6-07-0

!DGLSA Control Auxiliary 750 McGuire Cap> Dem Relay Cabinet Building Report 70 1

IB(ST9A)

Control Sequence Timer Relay TEMPO 812-1 *6-09-0

!DGLSA Control Auxiliary 750 McGuire Cap> Dem Relay Cabinet Building Report 71 I

IC(ST8A)

Control Sequence Timer Relay TEMPO 812-1-6-05-0

!DGLSA Control Auxiliary 750 McGuire Cap> Dem Relay Cabinet Building Report 72 1

JA(STIA)

Control Sequence Timer Relay TEMPO 812-1-6-01-0

!DGLSA Control Auxiliary 750 McGuire Cap> Dem Relay Cabinet Building Report MNS-17-040

Table B-1: Components Identified for High Frequency Confirmation Component Enclosure Floor Component Evalnation No.

a System Building Elev.

Basis for

i Device ID Type Manufacturer Model ID Type (ft).

Evaluation Result Function Capacity 73 I

JB(STI IA)

Control Sequence Timer Relay TEMPO 812-1-6-07-0 lDGLSA Control Auxiliary 750 McGuire Cap> Dem Relay Cabinet Building Report 74 1

2AB(LRB4)

Control Blackout and/or LOCA Cutler-Hammer D26MRD704Al IDGLSB Control Auxiliary 733 McGuire Cap> Dem Relay Relay Cabinet Building Report 75 1

2CA(RB1)

Control Load Actuate Relay Cutler-Hammer D26MRD704Al IDGLSB Control Auxiliary 733 McGuire Cap> Dem Relay Cabinet Building Report 76 1

2CB(AB1)

Control Auto-Advance Relay Cutler-Hammer D26MRD704Al IDGLSB Control Auxiliary 733 McGuire Cap> Dem Relay Cabinet Building Report 77 I

2DA(RB2)

Control Load Actuate Relay Cutler-Hammer D26MRD704Al lDGLSB Control Auxiliary 733 McGuire Cap> Dem Relay Cabinet Building Report 78 1

2EA(RB3)

Control Load Actuate Relay Cutler-Hammer D26MRD704Al lDGLSB Control Auxiliary 733 McGuire Cap> Dem Relay Cabinet Building

  • Report Control Control Auxiliary McGuire 79 1

2FA(RB4)

Relay Load Actuate Relay Cutler-Hammer D26MRD704Al lDGLSB Cabinet Building 733 Report Cap> Dem Control Control Auxiliary McGuire 80 I

2HA(RB6)

Relay Load Actuate Relay Cutler-Hammer D26MRD704Al IDGLSB Cabinet Building 733 Report Cap> Dem Control Control Auxiliary McGuire 81 I

2HB(RB9)

Relay Load Actuate Relay Cutler-Hammer D26MRD704Al IDGLSB Cabinet Building 733 Report Cap> Dem Control Control Auxiliary McGuire 82 1

21A(RB7)

Relay Load Actuate Relay Cutler-Hammer D26MRD704Al lDGLSB Cabinet Building 733 Report Cap> Dem 83 1

2IB(RBIO)

Control Load Actuate Relay Cutler-Hammer D26MRD704Al lDGLSB Control Auxiliary 733 McGuire Cap> Dem Relay Cabinet Building Report 84 1

2JA(RB8)

Control Load Actuate Relay Cutler-Hammer D26MRD704Al lDGLSB Control Auxiliary 733 McGuire Cap> Dem Relay Cabinet Building Report 85 I

2JB(RB11)

Control Load Actuate Relay Cutler-Hanuner D26MRD704Al lDGLSB Control Auxiliary 733 McGuire Cap> Dem Relay Cabinet Building Report 86 1

4AA(lEQBRL27BX)

Protective Undervoltage Relay

!TE ITE-27H lDGLSB Control Auxiliary 733 GERS Cap> Dem Relay (211801710)

Cabinet Building 87 1

AA(LSB2)

Control Load Shed Relay Cutler-Hammer D26MRD704Al lDGLSB Control Auxiliary 733 McGuire Cap> Dem Relay Cabinet Building Repo1t 88 1

AB(LSBl)

Control Load Shed Relay Cutler-Hammer D26MRD704Al IDGLSB Control Auxiliary 733 McGuire Cap> Dem Relay Cabinet Building Report 89 1

BD(lESGBXl)

Control LOCA Relay Cutler-Hammer D26MRD704Al IDGLSB Control Auxiliary 733 McGuire Cap> Dem Relay Cabinet Building Report 90 I

CB(l27BX)

Control Undervoltage Auxiliary Cutler-Hanuner D26MRD70Al IDGLSB Control Auxiliary 733 McGuire Cap> Dem Relay Relay Cabinet Building Report MNS-17-040

Table B-1: Components Identified for High Frequency Confirmation Component Enclosure Floor Component Evaluation No.

~

System Building Elev.

Basis for

i Device ID Type Manufacturer Model ID Type Evaluation Result Function (ft)

Capacity 91 I

CG(LSBTX)

Control DG Breaker Closure Cutler-Hammer D26MRD30Al IDGLSB Control Auxiliary 733 McGuire Cap> Dem Relay Control Cabinet Building Report 92 I

DC(BOB)

Control Blackout Relay Cutler-Hammer D26MRD704Al IDGLSB Control Auxiliary 733 McGuire Cap> Dem Relay Cabinet Building Report 93 I

EC(LT2B)

Control Generator Restart Relay Cutler-Hammer D26MRD704Al IDGLSB Control Auxiliary 733 McGuire Cap> Dem Relay Cabinet Building Report 94 1

FA(RGB)

Control Generator Restart Relay Cutler-Hammer D26MRD70Al IDGLSB Control Auxiliary 733 McGuire Cap> Dem Relay Cabinet Building Report 95 1

GA(ST4B)

Control Sequence Timer Relay TEMPO 812-1-6-08-0 IDGLSB Control Auxiliary 733 McGuire Cap> Dem Relay Cabinet Building Report 96 1

GB(ST2B)

Control Sequence Timer Relay TEMPO 812-1-6-08-0 IDGLSB Control Auxiliary 733 McGuire Cap> Dem Relay Cabinet Building Report 97 1

GC(LSBT)

Control Load Shed Timer TEMPO 812-1-6-01-0 lDGLSB Control Auxiliary 733 McGuire Cap> Dem Relay Cabinet Building Report 98 I

HA(ST7B)

Control Sequence Timer Relay TEMPO 812-1-6-05-0 lDGLSB Control Auxiliary 733 McGuire Cap> Dem Relay Cabinet Building Report 99 I

HB(ST6B)

Control Sequence Timer Relay TEMPO 812-1-6-05-0 IDGLSB Control Auxiliary 733 McGuire Cap> Dem Relay Cabinet Building Report 100 I

IA(STIOB)

Control Sequence Timer Relay TEMPO 812-1-6-07-0 IDGLSB Control Auxiliary 733 McGuire Cap> Dem Relay Cabinet Building Rep01t IOI I

IB(ST9B)

Control Sequence Timer Relay TEMPO 812-1-6-09-0 lDGLSB Control Auxiliary 733 McGuire Cap> Dem Relay Cabinet Building Report 102 1

1C(ST8B)

Control Sequence Timer Relay TEMPO 812-1-6-05-0 lDGLSB Control Auxiliary 733 McGuire Cap> Dem Relay Cabinet Building Report 103 1

JA(STIB)

Control Sequence Timer Relay TEMPO 812-1-6-01-0 lDGLSB Control Auxiliary 733 McGuire Cap> Dem Relay Cabinet Building Report 104 I

JB(STI IB)

Control Sequence Timer Relay TEMPO 812-1-6-07-0 lDGLSB Control Auxiliary 733 McGuire Cap> Dem Relay Cabinet Building Report Control Over Voltage Time Delay Control Auxiliary McGuire Operator action 105 1

K301 Relay Auxiliary Relay

<Unknown>

<Unknown>

IEDGA Cabinet Building 736+06 Report within an existing procedure Control Over Voltage Time Delay Control Auxiliary McGuire Operator action 106 I

K301 Relay Auxiliary Relay

<Unknown>

<Unknown>

lEDGB Cabinet Building 736+06 Report within an existing procedure 107 1

52@1ELXA-04B LY Circuit Load Center Feeder

!TE K-2000S IELXA Switch-Auxiliary 750 McGuire Cap>Dem*

Breaker Breaker gear Building Report 108 1

52@1ELXA-04D LY Circuit MCC Feeder Breaker

!TE K-1600S IELXA Switch-Auxiliary 750 McGuire Cap> Dem Breaker gear Building Report MNS-17-040

Table B-1: Components Identified for High Frequency Confirmation Component Enclosure Floor Component Evaluation No.

  • =

System Building Elev.

Basis for

~

Device ID Type Manufacturer Model ID Type (ft)

Evaluation Result Function Capacity 109 I

52@1 ELXA-050 LY Circuit MCC Feeder Breaker

!TE K-1600S IELXA Switch-Auxiliary 750 McGuire Cap> Dem Breaker gear Building Report 110 I

52@1 ELXB-04B LY Circuit Load Center Feeder

!TE K-2000S IELXB Switch-Auxiliary 733 McGuire Cap> Dem Breaker Breaker gear Building Report 111 I

52@1ELXB-05C LY Circuit MCC Feeder Breaker

!TE K-1600S IELXB Switch-Auxiliary 733 McGuire Cap> Dem Breaker gear Building Report 112 I

52@1ELXB-05D LY Circuit MCC Feeder Breaker

!TE K-1600S IELXB Switch-Auxiliary 733 McGuire Cap> Dem Breaker gear Building Report Auxiliary Operator action 113 I

M/C@l EMXA5-02A Contactor Valve Closing Contactor Joslyn Clark T30U031-76 IEMXA5 MCC Building 750 GERS within an existing procedure Auxiliary Operator action 114 I

M/C@IEMXA5-03D Contactor Valve Closing Contactor Joslyn Clark T30U031-76 IEMXA5 MCC Building 750 GERS within an existing procedure Auxiliary Operator action 115 I

M/C@l EMXB-03D Contactor Valve Closing Contactor Joslyn Clark T30U031-76 IEMXB MCC Building 733 GERS within an existing procedure M/C@IEMXB2-Auxiliary Operator action 116 I

Contactor Valve Closing Contactor Joslyn Clark T30U03 l-76

!EMXB2 MCC 733 GERS within an existing F04B Building procedure 117 I

52@1ETAl2 MY Circuit Pump Circuit Breaker ABB/ITE 5HK-250

!ETA Switch-Auxiliary 750 EPRIHF Cap> Dem Breaker gear Building Test 118 I

52@1ETA14 MY Circuit DG Circuit Breaker ABB/ITE 5HK-250

!ETA Switch-Auxiliary 750 EPRI HF Cap> Dem Breaker gear Building Test 119 I

52@1ETA3 MY Circuit Load Center Transfonner ABB/ITE 5HK-250

!ETA Switch-Auxiliary 750 EPRI HF Cap> Dem Breaker Primary Breaker gear Building Test 120 I

52S@IETAll MY Circuit Circuit Breaker Auxiliary ABB/ITE 5HK-250

!ETA Switch-Auxiliary 750 EPRIHF Cap> Dem Breaker Contact gear Building Test 121 I

AE(52S/F)@IETAI MY Circuit Circuit Breaker Auxiliary ABB/ITE 5HK-250

!ETA Switch-Auxiliary 750 EPRI HF Cap> Dem Breaker Contact gear Building Test 122 I

AE(52S/F)@IETA2 MY Circuit Circuit Breaker Auxiliary ABB/ITE 5HK-250

!ETA Switch-Auxiliary 750 EPRIHF Cap> Dem Breaker Contact gear Building Test 123 I

AF(52S)@IETAI MY Circuit Circuit Breaker Auxiliary ABB/ITE 5HK-250

!ETA Switch-Auxiliary 750 EPRI HF Cap> Dem Breaker Contact gear Building Test 124 l

AF(52S)@IETA2 MY Circuit Circuit Breaker Auxiliary ABB/ITE 5HK-250

!ETA Switch-Auxiliary 750 EPRIHF Cap> Dem Breaker Contact gear Building Test Protective Voltage-Controlled Over Switch-Auxiliary Operator action 125 I

PA(51V)@IETA14 Westinghouse COV-8 (1876244)

!ETA 750 SQ UR TS within an existing Relay Current Protective Relay gear Building procedure Protective Voltage-Controlled Over Switch-Auxiliary Operator action 126 I

PB(5 l V)@l ETA14 Westinghouse COV-8 (1876244)

!ETA 750 SQ UR TS within an existing Relay Current Protective Relay gear Building procedure MNS-17-040

Table B-1: Components Identified for High Frequency Confirmation Component Enclosure Floor Component Evaluation No.

  • =

System Building Elev.

Basis for Device ID Type Manufacturer Model ID Type Evaluation Result Function (ft)

Capacity Protective Voltage-Controlled Over Switch-Auxiliary Operator action 127 I

PC(5IV)@IETAI4 Relay Current Protective Relay Westinghouse COV-8 (1876244)

!ETA Building 750 SQURTS within an existing gear procedure 128 I

52@1ETBI2 MVCircuit Pump Circuit Breaker ABB/ITE 5HK-250 IETB Switch-Auxiliary 733 EPRI HF Cap> Dem Breaker gear Building Test 129 I

52@1ETBI4 MV Circuit DG Circuit Breaker ABB/ITE 5HK-250 IETB Switch-Auxiliary 733 EPRIHF Cap> Dem Breaker gear Building Test 130 I

52@1ETB3 MVCircuit Load Center Transfonner ABB/ITE 5HK-250 IETB Switch-Auxiliary 733 EPRI HF Cap> Dem Breaker Primary Breaker gear Building Test 131 I

52S@lETBII MVCircuit Circuit Breaker Auxiliary ABB/ITE 5HK-250 IETB Switch-Auxiliary 733 EPRI HF Cap> Dem Breaker Contact gear Building Test 132 I

AE(52S/F)@l ETB I MV Circuit Circuit Breaker Auxiliary ABB/ITE 5HK-250 IETB Switch-Auxiliary 733 EPRI HF Cap> Dem Breaker Contact gear Building Test 133 I

AE(52S/F)@IETB2 MVCircuit Circuit Breaker Auxiliary ABB/ITE 5HK-250 IETB Switch-Auxiliary 733 EPRIHF Cap> Dem Breaker Contact gear Building Test 134 I

AF(52S)@IETBI MVCircuit Circuit Breaker Auxiliary ABB/ITE 5HK-250 IETB Switch-Auxiliary 733 EPRIHF Cap> Dem Breaker Contact gear Building Test 135 1

AF(52S)@IETB2 MV Circuit Circuit Breaker Auxiliary ABB/ITE 5HK-250 IETB Switch-Auxiliary 733 EPRIHF Cap> Dem Breaker Contact gear Building Test Protective Voltage-Controlled Over Switch-Auxiliary Operator action 136 I

PA(51V)@IETBI4 Relay Current Protective Relay Westinghouse COV-8 (1876244)

IETB Building 733 SQURTS within an existing gear procedure Protective Voltage-Controlled Over Switch-Auxiliary Operator action 137 I

PB(5IV)@IETBI4 Westinghouse COV-8 (1876244)

IETB 733 SQ UR TS within an existing Relay Current Protective Relay gear Building procedure Protective Voltage-Controlled Over Switch-Auxiliary Operator action 138 I

PC(51V)@IETBl4 Relay Current Protective Relay Westinghouse COV-8 (1876244)

IETB Building 733 SQ UR TS within an existing gear procedure Control High DC Voltage Time Control Auxiliary McGuire Operator action 139 I

K307 Relay Delay Relay

<Unknown>

<Unknown>

EVCA Cabinet Building 733 Report within an existing procedure Control High DC Voltage Time Control Auxiliary McGuire Operator action 140 I

K307 Relay Delay Relay

<Unknown>

<Unknown>

EVCB Cabinet Building 733 Report within an existing procedure 141 l

RD(51VA)

Control Voltage-Controlled Over Cutler-Hammer D26MRD70AI GMPIA Control Auxiliary 750 McGuire Cap> Dem Relay Current Auxiliary Relay Cabinet Building Report 142 I

RE(51VB)

Control Voltage-Controlled Over Cutler-Haimner D26MRD70Al GMPIA Control Auxiliary 750 McGuire Cap> Dem Relay Current Auxiliary Relay Cabinet Building Report 143 1

RF(51VC)

Control Voltage-Controlled Over Cutler-Hammer D26MRD70AI GMPIA Control Auxiliary 750 McGuire Cap> Dem Relay Current Auxiliary Relay Cabinet Building Report 144 I

RD(51VA)

Control Voltage-Controlled Over Cutler-Hammer D26MRD70Al GMPIB Control Auxiliary 733 McGuire Cap> Dem Relay Current Auxiliary Relay Cabinet Building Report MNS-17-040

Table B-1: Components Identified for High Frequency Confirmation Component.

Enclosure Floor Component Evaluation No.

  • a System Building Elev.

Basis for

i Device ID Type Manufacturer Model ID Type (ft)

Evaluation Result Function Capacity 145 1

RE(51VB)

Control Voltage-Controlled Over Cutler-Hammer D26MRD70Al GMPlB Control Auxiliary 733 McGuire Cap> Dem Relay Current Auxiliary Relay Cabinet Building Report 146 1

RF(SlVC)

Control Voltage-Controlled Over Cutler-Hammer D26MRD70Al GMPIB Control Auxiliary 733 McGuire Cap> Dem Relay Current Auxiliary Relay Cabinet Building Report 147 1

AB(lEQCSW7740)

Process Overspeed Switch Dynalco SST-2400A TB672 Control Diesel 736+06 McGuire Cap> Dem Switch Cabinet Building Report 148 1

BA(SSTD)

Control Speed Switch Auxiliary Struthers-Dunn 219BBXP TB672 Control Diesel 736+06 GERS Cap> Dem Relay Relay Cabinet Building 149 l

BB(SSTE)

Control Speed Switch Auxiliary Struthers-Dunn 219BBXP TB672 Control Diesel 736+06 GERS Cap> Dem Relay Relay Cabinet Building 150 1

BC(SSTF)

Control Speed Switch Auxiliary Struthers-Dunn 219BBXP TB672 Control Diesel 736+06 GERS Cap> Dem Relay Relay Cabinet Building 151 1

CA(SSTDl)

Control Overspeed Trip Relay Cutler-Hammer D26MRD70Al TB672 Control Diesel 736+06 McGuire Cap> Dem Relay Cabinet Building Report 152 l

CB(SSTEl)

Control Overspeed Trip Relay Cutler-Hammer D26MRD70Al TB672 Control Diesel 736+06 McGuire Cap> Dem Relay Cabinet Building Report 153 1

AB(lEQCSW7770)

Process Overspeed Switch Dynalco SST-2400A TB673 Control Diesel 736+06 McGuire Cap> Dem Switch Cabinet Building Report 154 l

BA(SSTD)

Control Speed Switch Auxiliary Struthers-Dunn 219BBXP TB673 Control Diesel 736+06 GERS Cap> Dem Relay Relay Cabinet Building 155 l

BB(SSTE)

Control Speed Switch Auxiliary Struthers-Dunn 219BBXP TB673 Control Diesel 736+06 GERS Cap> Dem Relay Relay Cabinet Building 156 l

BC(SSTF)

Control Speed Switch Auxiliary Struthers-Dunn 219BBXP TB673 Control Diesel 736+06 GERS Cap> Dem Relay Relay Cabinet Building 157 1

CA(SSTD!)

Control Overspeed Trip Relay Cutler-Hammer D26MRD70Al TB673 Control Diesel 736+06 McGuire Cap> Dem Relay Cabinet Building Report 158 l

CB(SSTEl)

Control Overspeed Trip Relay Cutler-Hammer D26MRD70Al TB673 Control Diesel 736+06 McGuire Cap> Dem Relay Cabinet Building Report 159 2

NV24L(DA)

Control Seal-In Auxiliary Relay Cutler-Hammer D26MRD30Al 2ATC4A Control Auxiliary 733 McGuire Cap> Dem Relay Cabinet Building Report 160 2

NV25L(DA1)

Control Seal-In Auxiliary Relay Cutler-Hammer D26MRD30Al 2ATC4A Control Auxiliary 733 McGuire Cap> Dem Relay Cabinet Building Report 161 2

DJ(2TRC)

Control Diesel Start Relay Cutler-Hammer D26MRD70Al 2DGCPA Control Diesel 736+06 McGuire Cap> Dem Relay Cabinet Building Report 162 2

DK(2TRA)

Control Diesel Start Relay Cutler-Hammer D26MRD704Al 2DGCPA Control Diesel 736+06 McGuire Cap> Dem Relay Cabinet Building Report MNS-17-040

Table B-1: Components Identified for High Frequency Confirmation Component Enclosure Floor Component Evaluation No.

a System Building Elev.

Basis for

i Device ID Type Manufacturer Model ID Type

.{ft)

Evaluation Resul~

Function Capacity**

163 2

DL(RVG3)

Control Diesel Stop Relay Cutler-Hammer D26MRD70Al 2DGCPA Control Diesel 736+06 McGuire Cap> Dem Relay Cabinet Building Report 164 2

EK Control Speed Switch Auxiliaty Cutler-Hammer D26MRD70Al 2DGCPA Control Diesel 736+06 McGuire Cap> Dem Relay Relay Cabinet Building Report 165 2

EL Control Speed Switch Auxiliaty Cutler-Hammer D26MRD70Al 2DGCPA Control Diesel 736+06 McGuire Cap> Dem Relay Relay Cabinet Building Report 166 2

EM Control Speed Switch Auxiliaty Cutler-Hammer D26MRD70Al 2DGCPA Control Diesel 736+06 McGuire Cap> Dem Relay Relay Cabinet Building Report 167 2

FJ(2TRB)

Control Diesel Start Relay Cutler-Hammer D26MRD704Al 2DGCPA Control Diesel 736+06 McGuire Cap> Dem Relay Cabinet Building Report 168 2

FL(ARR)

Control Alarm Restraint Relay Cutler-Hammer D26MRD70Al 2DGCPA Control Diesel 736+06 McGuire Cap> Dem Relay Cabinet Building Report 169 2

GL(DASR)

Control Diesel Automatic Start Cutler-Hammer D26MRD70Al 2DGCPA Control Diesel 736+06 McGuire Cap> Dem Relay Relay Cabinet Building Report 170 2

GM(RVG2)

Control Diesel Stop Relay Cutler-Hammer D26MRD70Al 2DGCPA Control Diesel 736+06 McGuire Cap> Dem Relay Cabinet Building Report 171 2

JJ(SlA2X)

Control Speed Switch Auxiliaty Struthers-Dunn 219DXBP 2DGCPA Control Diesel 736+06 GERS Cap> Dem Relay Relay Cabinet Building 172 2

JK(SRXl)

Control Lube Oil Low Relay Cutler-Hammer D26MRD70Al 2DGCPA Control Diesel 736+06 McGuire Cap> Dem Relay Cabinet Building Report 173 2

JL(SlAlX)

Control 40% Speed Relay Struthers-Dunn 219BBXP 2DGCPA Control Diesel 736+06 GERS Cap> Dem Relay Cabinet Building 174 2

LN(ESX)

Control Emergency Stop Relay Cutler-Hammer D26MRD70Al 2DGCPA Control Diesel 736+06 McGuire Cap> Dem Relay Cabinet Building Report 175 2

LO(SRX2)

Control Lube Oil Low Relay Cutler-Hanuner D26MRD70Al 2DGCPA Control Diesel 736+06 McGuire Cap> Dem Relay Cabinet Building Report 176 2

MA(2EQCSW7720)

Process Overspeed Switch Dynalco SST-2400A 2DGCPA Control Diesel 736+06 McGuire Cap> Dem Switch Cabinet Building Report

-177 2

MB(2EQCSW7730)

Process Overspeed Switch Dynalco SST-2400A 2DGCPA Control Diesel 736+06 McGuire Cap> Dem Switch Cabinet Building Report 178 2

MU(SSTA)

Control 95% Speed Relay Strutl1ers-Dunn 219BBXP 2DGCPA Control Diesel 736+06 GERS Cap> Dem Relay Cabinet Building 179 2

MV(SSTB)

Control 95% Speed Relay Struthers-Dunn 219BBXP 2DGCPA Control Diesel 736+06 GERS Cap> Dem Relay Cabinet Building 180 2

MW(SSTC)

Control 97% Speed Relay Struthers-Dunn 219BBXP 2DGCPA Control Diesel 736+06 GERS Cap> Dem Relay Cabinet Building MNS-17-040

Table B-1: Components Identified for High Frequency Confirmation Component Enclosure Floor Component Evaluation No..

  • =

System Building Elev.

Basis for Device ID Type Manufacturer Model ID Type*

(ft)

Evaluation Result Funetion Capacity 181 2

DJ(2TRC)

Control Diesel Stait Relay Cutler-Hammer D26MRD70AI 2DGCPB Control Diesel 736+06 McGuire Cap> Dem Relay Cabinet Building Report 182 2

DK(2TRA)

Control Diesel Start Relay Cutler-Haimner D26MRD704Al 2DGCPB Control Diesel 736+06 McGuire Cap> Dem Relay Cabinet Building Report 183 2

DL(RVG3)

Control Diesel Stop Relay Cutler-Hammer D26MRD70Al 2DGCPB Control Diesel 736+06 McGuire Cap> Dem Relay Cabinet Building Report 184 2

EK Control Speed Switch Auxiliary Cutler-Hammer D26MRD70Al 2DGCPB Control Diesel 736+06 McGuire Cap> Dem Relay Relay Cabinet Building Report 185 2

EL Control Speed Switch Auxiliary Cutler-Hammer D26MRD70Al 2DGCPB Control Diesel 736+06 McGuire Cap> Dem Relay Relay Cabinet Building Report 186 2

EM Control Speed Switch Auxiliary Cutler-Haimner D26MRD70Al 2DGCPB Control Diesel 736+06 McGuire Cap> Dem Relay Relay Cabinet Building Report 187 2

FJ(2TRB)

Control Diesel Start Relay Cutler-Haimner D26MRD704Al 2DGCPB Control Diesel 736+06 McGuire Cap> Dem Relay Cabinet Building Report 188 2

FL( ARR)

Control Alarm Restraint Relay Cutler-Haimner D26MRD70Al 2DGCPB Control Diesel 736+06 McGuire Cap> Dem Relay Cabinet Building Report 189 2

GL(DASR)

Control Diesel Automatic Start Cutler-Hammer D26MRD704Al 2DGCPB Control Diesel 736+06 McGuire Cap> Dem Relay Relay Cabinet Building Report 190 2

GM(RVG2)

Control Diesel Stop Relay Cutler-Hammer D26MRD70Al 2DGCPB Control Diesel 736+06 McGuire Cap> Dem Relay Cabinet Building Report 191 2

JJ(S1A2X)

Control Speed Switch Auxiliary Struthers-Dunn 219DXBP 2DGCPB Control Diesel 736+06 GERS Cap> Dem Relay Relay Cabinet Building 192 2

JK(SRXl)

Control Lube Oil Low Relay Cutler-Hanuner D26MRD70Al 2DGCPB Control Diesel 736+06 McGuire Cap> Dem Relay Cabinet Building Report 193 2

JL(SIAIX)

Control 40% Speed Relay Struthers-Dunn 219BBXP 2DGCPB Control Diesel 736+06 GERS Cap> Dem Relay Cabinet Building 194 2

LN(ESX)

Control Emergency Stop Relay Cutler-Hanuner D26MRD70Al 2DGCPB Control Diesel 736+06 McGuire Cap> Dem Relay Cabinet Building Report 195 2

LO(SRX2)

Control Lube Oil Low Relay Cutler-Hammer D26MRD70Al 2DGCPB Control Diesel 736+06 McGuire Cap> Dem Relay Cabinet Building Report 196 2

MA(2EQCSW7750)

Process Overspeed Switch Dynalco SST-2400A 2DGCPB Control Diesel 736+06 McGuire Cap> Dem Switch Cabinet Building Report 197 2

MB(2EQCSW7760)

Process Overspeed Switch Dynalco SST-2400A 2DGCPB Control Diesel 736+06 McGuire Cap> Dem Switch Cabinet Building Report 198 2

MU(SSTA)

Control 95% Speed Relay Struthers-Dunn 219BBXP 2DGCPB Control Diesel 736+06 GERS Cap> Dem Relay Cabinet Building MNS-17-040

Table B-1: Components Identified for High Frequency Confirmation Component Enclosure Floor Component Evaluation No.

~

System Building Elev.

Basis for

~

Device ID Type Manufacturer Model ID Type (ft)

Evaluation Res~lt Function Capacity 199 2

MV(SSTB)

Control 95% Speed Relay Struthers-Dunn 219BBXP 2DGCPB Control Diesel 736+06 GERS Cap> Dem Relay Cabinet Building 200 2

MW(SSTC)

Control 97% Speed Relay Struthers-Dunn 219BBXP 2DGCPB Control Diesel 736+06 GERS Cap> Dem Relay Cabinet Building 201 2

2AB(LRA4)

Control Blackout and/or LOCA Cutler-Hammer D26MRD704Al 2DGLSA Control Auxiliary 750 McGuire Cap> Dem Relay Relay Cabinet Building Report 202 2

2CA(RA1)

Control Load Actuate Relay Cutler-Hammer D26MRD704Al 2DGLSA Control Auxiliary 750 McGuire Cap> Dem Relay Cabinet Building Report 203 2

2CB(AA1)

Control Auto-Advance Relay Cutler-Hammer D26MRD704Al 2DGLSA Control Auxiliary 750 McGuire Cap> Dem Relay Cabinet Building Report 204 2

2DA(RA2)

Control Load Actuate Relay Cutler-Hanuner D26MRD704Al 2DGLSA Control Auxiliary 750 McGuire Cap> Dem Relay Cabinet Building Report 205 2

2EA(RA3)

Control Load Actuate Relay Cutler-Hammer D26MRD704Al 2DGLSA Control Auxiliary 750 McGuire Cap> Dem Relay Cabinet Building Report 206 2

2FA(RA4)

Control Load Actuate Relay Cutler-Hammer D26MRD704Al 2DGLSA Control Auxiliary 750 McGuire Cap> Dem Relay Cabinet Building Report 207 2

2HA(RA6)

Control Load Actuate Relay Cutler-Hanuner D26MRD704Al 2DGLSA Control Auxiliary 750 McGuire Cap> Dem Relay Cabinet Building Report 208 2

2HB(RA9)

Control Load Actuate Relay Cutler-Hammer D26MRD704Al 2DGLSA Control Auxiliary 750 McGuire Cap> Dem Relay Cabinet Building Report 209 2

2IA(RA7)

Control Load Actuate Relay Cutler-Hanuner D26MRD704Al 2DGLSA Control Auxiliary 750 McGuire Cap> Dem Relay Cabinet Building Report 210 2

2IB(RA10)

Control Load Actuate Relay Cutler-Hammer D26MRD704Al 2DGLSA Control Auxiliary 750 McGuire Cap> Dem Relay Cabinet Building Report 211 2

2JA(RA8)

Control Load Actuate Relay Cutler-Hanuner D26MRD704Al 2DGLSA Control Auxiliary 750 McGuire Cap> Dem Relay Cabinet Building Report 212 2

2JB(RA1 I)

Control Load Actuate Relay Cutler-Hammer D26MRD704Al 2DGLSA Control Auxiliary 750 McGuire Cap> Dem Relay Cabinet Building Report 213 2

4AA(2EQBRL27 AX)

Protective Undervoltage Relay

!TE ITE-27H 2DGLSA Control Auxiliary 750 GERS Cap> Dem Relay (211B017ID)

Cabinet Building 214 2

AA(LSA2)

Control Load Shed Relay Cutler-Hanuner D26MRD704Al 2DGLSA Control Auxiliary 750 McGuire Cap> Dem Relay Cabinet Building Report 215 2

AB(LSAl)

Control Load Shed Relay Cutler-Hammer D26MRD704Al 2DGLSA Control Auxiliary 750 McGuire Cap> Dem Relay Cabinet Building Report 216 2

BD(2ESGAX1)

Control LOCA Relay Cutler-Hammer D26MRD704Al 2DGLSA Control Auxiliary 750 McGuire Cap> Dem Relay Cabinet Building Report MNS-17-040

Table B-1: Components Identified for High Frequency Confirmation Component Enclosnre Floor Component Evalnation No.

a System Bnilding Elev.
  • Basis for
i Device ID Type Manufacturer Model ID Type (ft)

Evaluation Result Function Capacity 217 2

CB(227AX)

Control Undervoltage Auxiliary Cutler-Hammer D26MRD70AI 2DGLSA Control Auxiliary 750 McGuire Cap> Dem Relay Relay Cabinet Building Report 218.

2 CG(LSATX)

Control DG Breaker Closure Cutler-Hammer D26MRD30Al

-2DGLSA Control Auxiliary 750 McGuire Cap> Dem Relay Control Cabinet Building Report 219 2

DC(BOA)

Control Blackout Relay Cutler-Hammer D26MRD704Al 2DGLSA Control Auxiliary 750 McGuire Cap> Dem Relay Cabinet Building Report 220 2

EC(LT2A)

Control Generator Restart Relay Cutler-Hammer D26MRD704Al 2DGLSA Control Auxiliary 750 McGuire Cap> Dem Relay Cabinet Building Report 221 2

FA(RGA)

Control Generator Restart Relay Cutler-Hammer D26MRD70Al 2DGLSA Control Auxiliary 750 McGuire Cap> Dem Relay Cabinet Building Report 22_2 2

GA(ST4A)

Control Sequence Timer Relay TEMPO 812-1-6-08-0 2DGLSA Control Auxiliary 750 McGuire Cap> Dem Relay Cabinet Building Report 223 2

GB(ST2A)

Control Sequence Timer Relay TEMPO 812-1-6-08-0 2DGLSA Control Auxiliary 750 McGuire Cap> Dem Relay Cabinet Building Report 224 2

GC(LSAT)

Control Load Shed Timer TEMPO 812-1-6-01-0 2DGLSA Control Auxiliary 750 McGuire Cap> Dem Relay Cabinet Building Report 225 2

HA(ST7A)

Control Sequence Timer Relay TEMPO 812-1-6-05-0 2DGLSA Control Auxiliary 750 McGuire Cap> Dem Relay Cabinet Building Report 226 2

HB(ST6A)

Control Sequence Timer Relay TEMPO 812-1-6-05-0 2DGLSA Control Auxiliary 750 McGuire Cap> Dem Relay Cabinet Building Repott 227 2

IA(STlOA)

Control Sequence Timer Relay TEMPO 812-1-6-07-0 2DGLSA Control Auxiliary 750 McGuire Cap> Dem Relay Cabinet Building Report 228 2

IB(ST9A)

Control Sequence Timer Relay TEMPO 812-1-6-09-0 2DGLSA Control Auxiliary 750 McGuire Cap> Dem Relay Cabinet Building Report 229 2

IC(ST8A)

Control Sequence Timer Relay TEMPO 812-1-6-05-0 2DGLSA Control Auxiliary 750 McGuire Cap> Dem Relay Cabinet Building Report 230 2

JA(STIA)

Control Sequence Timer Relay TEMPO 812-1-6-01-0 2DGLSA Control Auxiliary 750 McGuire Cap> Dem Relay Cabinet Building Report 231 2

JB(STI IA)

Control Sequence Timer Relay TEMPO 812-1-6-07-0 2DGLSA Control Auxiliary 750 McGuire Cap> Dem Relay Cabinet Building Report 232 2

2AB(LR84)

Control Blackout and/or LOCA Cutler-Hammer D26MRD704AI 2DGLSB Control Auxiliary 733 McGuire Cap> Dem Relay Relay Cabinet Building Report 233 2

2CA(RB1)

Control Load Actuate Relay Cutler-Hammer D26MRD704Al 2DGLSB Control Auxiliary 733 McGuire Cap> Dem Relay Cabinet Building Report 234 2

2CB(AB1)

Control Auto-Advance Relay Cutler-Hammer D26MRD704Al 2DGLSB Control Auxiliary 733 McGuire Cap> Dem Relay Cabinet Building Report MNS-17-040

Table B-1: Components Identified for High Frequency Confirmation Component Enclosure Floor Component Evaluation No.

  • =

System Building Elev.

Basis for

i Device ID Type Manufacturer Model ID Type Evaluation Result Function (ft)

Capacity 235 2

2DA(RB2)

Control Load Actuate Relay Cutler-Hammer D26MRD704Al 2DGLSB Control Auxiliary 733 McGuire Cap> Dem Relay Cabinet Building Report 236 2

2EA(RB3)

Control Load Actuate Relay Cutler-Hammer D26MRD704Al 2DGLSB Control Auxiliary 733 McGuire Cap> Dem Relay Cabinet Building Report 237 2

2FA(RB4)

Control Load Actuate Relay Cutler-Hammer D26MRD704Al 2DGLSB Control Auxiliary 733 McGuire Cap> Dem Relay Cabinet Building Report 238 2

2HA(RB6)

Control Load Actuate Relay Cutler-Hammer D26MRD704Al 2DGLSB Control Auxiliary 733 McGuire Cap> Dem Relay Cabinet Building Report 239 2

2HB(RB9)

Control Load Actuate Relay Cutler-Haimner D26MRD704Al 2DGLSB Control Auxiliary 733 McGuire Cap> Dem Relay Cabinet Building Report 240 2

2IA(RB7)

Control Load Actuate Relay Cutler-Hammer D26MRD704Al 2DGLSB Control Auxiliary 733 McGuire Cap> Dem Relay Cabinet Building Report 241 2

2IB(RB10)

Control Load Actuate Relay Cutler-Hammer D26MRD704Al 2DGLSB Control Auxiliary 733 McGuire Cap> Dem Relay Cabinet Building Report 242 2

2JA(RB8)

Control Load Actuate Relay Cutler-Hanuner D26MRD704Al 2DGLSB Control Auxiliary 733 McGuire Cap> Dem Relay Cabinet Building Report 243 2

2JB(RB11)

Control Load Actuate Relay Cutler-Hammer D26MRD704Al 2DGLSB Control Auxiliary 733 McGuire Cap> Dem Relay Cabinet Building Report 244 2

4AA(2EQBRL27BX)

Protective Undervoltage Relay

!TE ITE-27H 2DGLSB Control Auxiliary 733 GERS Cap> Dem Relay (211B0171D)

Cabinet Building 245 2

AA(LSB2)

Control Load Shed Relay Cutler-Hanuner D26MRD704Al 2DGLSB Control Auxiliary 733 McGuire Cap> Dem Relay Cabinet Building Report 246 2

AB(LSBl)

Control Load Shed Relay Cutler-Hammer D26MRD704Al 2DGLSB Control Auxiliary 733 McGuire Cap> Dem Relay Cabinet Building Report 247 2

BD(2ESGBX1)

Control LOCARelay Cutler-Hammer D26MRD704Al 2DGLSB Control Auxiliary 733 McGuire Cap> Dem Relay Cabinet Building Report 248 2

CB(227BX)

Control Undervoltage Auxiliary Cutler-Hammer D26MRD70Al 2DGLSB Control Auxiliary 733 McGuire Cap> Dem Relay Relay Cabinet Building Report 249 2

CG(LSBTX)

Control DG Breaker Closure Cutler-Hammer D26MRD30Al 2DGLSB Control Auxiliary 733 McGuire Cap> Dem Relay Control Cabinet Building Report 250 2

DC(BOB)

Control Blackout Relay Cutler-Hammer D26MRD704Al 2DGLSB Control Auxiliary 733 McGuire Cap> Dem Relay Cabinet Building Report 251 2

EC(LT2B)

Control Generator Restart Relay Cutler-Hammer D26MRD704Al 2DGLSB Control Auxiliary 733 McGuire Cap> Dem Relay Cabinet Building Report 252 2

FA(RGB)

Control Generator Restart Relay Cutler-Hammer D26MRD70Al 2DGLSB Control Auxiliary 733 McGuire Cap> Dem Relay Cabinet Building Report MNS-17-040

Table B-1: Components Identified for High Frequency Confirmation Component Enclosure Floor Component Evaluation No.

  • =

System Building Elev.

Basis for

~

Device ID Type Manufacturer Model ID Type (ft)

Evaluation Result Function Capacity 253 2

GA(ST4B)

Control Sequence Timer Relay TEMPO 812-1-6-08-0 2DGLSB Control Auxiliary 733 McGuire Cap> Dem Relay Cabinet Building Report 254 2

GB(ST2B)

Control Sequence Timer Relay TEMPO 812-1-6-08-0 2DGLSB Control Auxiliary 733 McGuire Cap> Dem Relay Cabinet Building Report 255 2

GC(LSBT)

Control Load Shed Timer TEMPO 812-1-6-01-0 2DGLSB Control Auxiliary 733 McGuire Cap> Dem Relay Cabinet Building Report 256 2

HA(ST7B)

Control Sequence Timer Relay TEMPO 812-1-6-05-0 2DGLSB Control Auxiliary 733 McGuire Cap> Dem Relay Cabinet Building Report 257 2

HB(ST6B)

Control Sequence Timer Relay TEMPO 812-1-6-05-0 2DGLSB Control Auxiliary 733 McGuire Cap> Dem Relay Cabinet Building Report 258 2

lA(STlOB)

Control Sequence Timer Relay TEMPO 812-1-6-07-0 2DGLSB Control Auxiliary 733 McGuire Cap> Dem Relay Cabinet Building Report 259 2

IB(ST9B)

Control Sequence Timer Relay TEMPO 812-1-6-09-0 2DGLSB Control Auxiliary 733 McGuire Cap> Dem Relay Cabinet Building Report 260 2

IC(ST8B)

Control Sequence Timer Relay TEMPO 812-1-6-05-0 2DGLSB Control Auxiliary 733 McGuire Cap> Dem Relay Cabinet Building Report 261 2

JA(STlB)

Control Sequence Timer Relay TEMPO 812-1-6-01-0 2DGLSB Control Auxiliary 733 McGuire Cap> Dem Relay Cabinet Building Report 262 2

JB(STl lB)

Control Sequence Timer Relay TEMPO 812-1-6-07-0 2DGLSB Control Auxiliary 733 McGuire Cap> Dem Relay Cabinet Building Report Control Over Voltage Time Delay Control Auxiliary McGuire Operator action 263 2

K301 Relay Auxiliary Relay

<Unknown>

<Unknown>

2EDGA Cabinet Building 736+06 Report within an existing procedure Control Over Voltage Time Delay Control Auxiliary McGuire Operator action 264 2

K301 Relay Auxiliary Relay

<Unknown>

<Unknown>

2EDGB Cabinet Building 736+06 Report within an existing procedure 265 2

52@2ELXA-04B LV Circuit Load Center Feeder ITE K-2000S 2ELXA Switch-Auxiliary 750 McGuire Cap> Dem Breaker Breaker gear Building Report 266 2

52@2ELXA-04D LV Circuit MCC Feeder Breaker ITE K-1600S 2ELXA Switch-Auxiliary 750 McGuire Cap> Dem Breaker gear Building Report 267 2

52@2ELXA-05D LV Circuit MCC Feeder Breaker ITE K-1600S 2ELXA Switch-Auxiliary 750 McGuire Cap> Dem Breaker gear Building Report 268 2

52@2ELXB-04B LV Circuit Load Center Feeder ITE K-2000S 2ELXB Switch-Auxiliary 733 McGuire Cap> Dem Breaker Breaker gear Building Report 269 2

52@2ELXB-04C LV Circuit MCC Feeder Breaker ITE K-1600S 2ELXB Switch-Auxiliary 733 McGuire Cap> Dem Breaker gear Building Report 270 2

52@2ELXB-05C LV Circuit MCC Feeder Breaker ITE K-1600S 2ELXB Switch-Auxiliary 733 McGuire Cap> Dem Breaker gear Building Report MNS-17-040

Table B-1: Components Identified for High Frequency Confirmation Component Enclosure Floor Component Evaluation No.

  • =

System Building Elev.

Basis for

i Device ID Type Manufacturer Model ID Type Evaluation Result Function (ft)

Capacity 271 2

52@2ELXB-05D LV Circuit MCC Feeder Breaker

!TE K-1600S 2ELXB Switch-Auxiliary 733 McGuire Cap> Dem Breaker gear Building Report Auxiliary Operator action 272 2

M/C@2EMXA4-01 C Contactor Valve Closing Contactor Joslyn Clark T30U031-76 2EMXA4 MCC Building 750 GERS within an existing procedure Auxiliary Operator action 273 2

M/C@2EMXA4-01 D Contactor Valve Closing Contactor Joslyn Clark T30U031-76 2EMXA4 MCC Building 750 GERS within an existing procedure Auxiliary Operator action 274 2

M/C@2EMXB-03D Contactor Valve Closing Contactor Joslyn Clark T30U031-76 2EMXB MCC Building 733 GERS within an existing procedure M/C@2EMXB2-Auxiliary Operator action 275 2

F04B Contactor Valve Closing Contactor Joslyn Clark T30U031-76 2EMXB2 MCC Building 733 GERS within an existing procedure 276 2

52@2ETA14 MVCircuit Load Center Transformer ABB/ITE 5HK-250 2ETA Switch-Auxiliary 750 EPRI HF Cap> Dem Breaker Primary Breaker gear Building Test 277 2

52@2ETA2 MVCircuit DG Circuit Breaker ABB/ITE 5HK-250 2ETA Switch-Auxiliary 750 EPRI HF Cap> Dem Breaker gear Building Test 278 2

52@2ETA5 MVCircuit Pump Circuit Breaker ABB/ITE 5HK-250 2ETA Switch-Auxiliary 750 EPRI HF Cap> Dem Breaker gear Building Test 279 2

52S@2ETA6 MVCircuit Circuit Breaker Auxiliary ABB/ITE 5HK-250 2ETA Switch-Auxiliary 750 EPRI HF Cap> Dem Breaker Contact gear Building Test 280 2

AE(52S/F)@2ETA15 MV Circuit Circuit Breaker Auxiliary ABB/lTE 5HK-250 2ETA Switch-Auxiliary 750 EPRIHF Cap> Dem Breaker Contact gear Building Test 281 2

AE(52S/F)@2ETA16 MVCircuit Circuit Breaker Auxiliary ABB/ITE 5HK-250 2ETA Switch-Auxiliary 750 EPRI HF Cap> Dem Breaker Contact gear Building Test 282 2

AF(52S)@2ETA15 MVCircuit Circuit Breaker Auxiliary ABB/lTE 5HK-250 2ETA Switch-Auxiliary 750 EPRlHF Cap> Dem Breaker Contact gear Building Test 283 2

AF(52S)@2ETA16 MV Circuit Circuit Breaker Auxiliary ABB/lTE 5HK-250 2ETA Switch-Auxiliary 750 EPRIHF Cap> Dem Breaker Contact gear Building Test Protective Voltage-Controlled Over Switch-Auxiliary Operator action 284 2

PA(51V)@2ETA2 Westinghouse COV-8 (1876244) 2ETA 750 SQURTS within an existing Relay Current Protective Relay gear Building procedure Protective Voltage-Controlled Over Switch-Auxiliary Operator action 285 2

PB(51V)@2ETA2 Relay Current Protective Relay Westinghouse COV-8 (1876244) 2ETA Building 750 SQURTS within an existing gear procedure Protective Voltage-Controlled Over Switch-Auxiliary Operator action 286 2

PC(5 l V)@2ET A2 Relay Current Protective Relay Westinghouse COV-8 (1876244) 2ETA Building 750 SQURTS within an existing gear procedure 287 2

52@2ETB14 MV Circuit Load Center Transformer ABB/ITE 5HK-250 2ETB Switch-Auxiliary 733 EPRIHF Cap> Dem Breaker Primary Breaker gear Building Test MNS-17-040

Table B-1: Components Identified for High Frequency Confirmation Component -

Enclosure Floor Component Evaluation No.

a System Building Elev.

Basis for

i Device ID Type Manufacturer Model ID Type Evaluation Result Function (ft)

Capacity 288 2

52@2ETB2 MY Circuit DG Circuit Breaker ABB/ITE 5HK-250 2ETB Switch-Auxiliary 733 EPRI HF Cap> Dem Breaker gear Building Test 289 2

52@2ET85 MY Circuit Pump Circuit Breaker ABB/ITE 5HK-250 2ETB Switch-Auxiliary 733 EPRI HF Cap> Dem Breaker gear Building Test 290 2

52S@2ETB6 MY Circuit Circuit Breaker Auxiliary ABB/ITE 5HK-250 2ETB Switch-Auxiliary 733 EPRI HF Cap> Dem Breaker Contact gear Building Test 291 2

AE(52S/F)@2ETB15 MY Circuit Circuit Breaker Auxiliary ABB/ITE 5HK-250 2ETB Switch-Auxiliary 733 EPRI HF Cap> Dem Breaker Contact gear Building Test 292 2

AE(52S/F)@2ETB 16 MY Circuit Circuit Breaker Auxiliary ABB/ITE 5HK-250 2ETB Switch-Auxiliary 733 EPRIHF Cap> Dem Breaker Contact gear Building Test 293 2

AF(52S)@2ETB15 MY Circuit Circuit Breaker Auxiliary ABB/ITE 5HK-250 2ETB Switch-Auxiliary 733 EPRI HF Cap> Dem Breaker Contact gear Building Test 294 2

AF(52S)@2ETB16 MY Circuit Circuit Breaker Auxiliary ABB/ITE 5HK-250 2ETB Switch-Auxiliary 733 EPRIHF Cap> Dem Breaker Contact gear Building Test Protective Voltage-Controlled Over Switch-Auxiliary Operator action 295 2

PA(51V)@2ETB2 Relay Current Protective Relay Westinghouse COV-8 (1876244) 2ETB Building 733 SQ UR TS within an existing gear procedure Protective Voltage-Controlled Over Switch-Auxiliary Operator action 296 2

PB(51V)@2ETB2 Relay Current Protective Relay Westinghouse COV-8 (1876244) 2ETB Building 733 SQ UR TS within an existing gear procedure Protective Voltage-Controlled Over Switch-Auxilia1y Operator action 297 2

PC(51V)@2ETB2 Relay Current Protective Relay Westinghouse COV-8 (1876244) 2ETB Building 733 SQURTS within an existing gear procedure Control High DC Voltage Time Control Auxiliary McGuire Operator action 298 2

K307 Relay Delay Relay

<Unknown>

<Unknown>

EVCC Cabinet Building 733 Report within an existing procedure Control High DC Voltage Time Control Auxiliary McGuire Operator action 299 2

K307 Relay Delay Relay

<Unknown>

<Unknown>

EVCD Cabinet Building 733 Report within an existing procedure 300 2

RD(51VA)

Control Voltage-Controlled Over Cutler-Hammer D26MRD70Al GMP2A Control Auxiliary 750 McGuire Cap> Dem Relay Current Auxiliary Relay Cabinet Building Report 301 2

RE(51VB)

Control Voltage-Controlled Over Cutler-Hanuner D26MRD70Al GMP2A Control Auxiliary 750 McGuire Cap> Dem Relay Current Auxiliary Relay Cabinet Building Report 302 2

RF(51VC)

Control Voltage-Controlled Over Cutler-Hammer D26MRD70Al GMP2A Control Auxiliary 750 McGuire Cap> Dem Relay Current Auxiliary Relay Cabinet Building Report 303 2

RD(51VA)

Control Voltage-Controlled Over Cutler-Hammer D26MRD70Al GMP2B Control Auxiliary 733 McGuire Cap> Dem Relay Current Auxiliary Relay Cabinet Building Report 304 2

RE(51VB)

Control Voltage-Controlled Over Cutler-Hammer D26MRD70Al GMP2B Control Auxiliary 733 McGuire Cap> Dem Relay Current Auxiliary Relay Cabinet Building Report 305 2

RF(51VC)

Control Voltage-Controlled Over Cutler-Hammer D26MRD70Al GMP2B Control Auxiliary 733 McGuire Cap> Dem Relay Current Auxiliary Relay Cabinet Building Report MNS-17-040

Table B-1: Components Identified for High Frequency Confirmation

.Component Enclosure Floor*

Component Evaluation No.

  • =

System Building Elev.

Basis for

i Device ID Type Manufacturer Model ID Type Evaluation Result Function

.(ft)

Capacity 306 2

AB(2EQCSW7740)

Process Overspeed Switch Dynalco SST-2400A TB1672 Control Diesel 736+06 McGuire Cap> Dem Switch Cabinet Building Report 307 2

BA(SSTD)

Control Speed Switch Auxiliary Struthers-Dunn 219BBXP TB1672 Control Diesel 736+06 GERS Cap> Dem Relay Relay Cabinet Building 308 2

BB(SSTE)

Control Speed Switch Auxiliary Struthers-Dunn 219BBXP TB1672 Control Diesel 736+06 GERS Cap> Dem Relay Relay Cabinet Building 309 2

BC(SSTF)

Control Speed Switch Auxiliary Struthers-Dunn 219BBXP TB1672 Control Diesel 736+06 GERS Cap> Dem Relay Relay Cabinet Building 310 2

CA(SSTDl)

Control Overspeed Trip Relay Cutler-Hammer D26MRD70Al TB1672 Control Diesel 736+06 McGuire Cap> Dem Relay Cabinet Building Report 311 2

CB(SSTEl)

Control Overspeed Trip Relay Cutler-Hammer D26MRD70Al TB1672 Control Diesel 736+06 McGuire Cap> Dem Relay Cabinet Building Report 312 2

AB(2EQCSW7770)

Process Overspeed Switch Dynalco SST-2400A TB1673 Control Diesel 736+06 McGuire Cap> Dem Switch Cabinet Building Report 313 2

BA(SSTD)

Control Speed Switch Auxiliary Struthers-Dunn 219BBXP TB1673 Control Diesel 736+06 GERS Cap> Dem Relay Relay Cabinet Building 314 2

BB(SSTE)

Control Speed Switch Auxiliary Struthers-Dunn 219BBXP TB1673 Control Diesel 736+06 GERS Cap> Dem Relay Relay Cabinet Building 315 2

BC(SSTF)

Control Speed Switch Auxiliary Struthers-Dunn 219BBXP TB1673 Control Diesel 736+06 GERS Cap> Dem Relay Relay Cabinet Building 316 2

CA(SSTDI)

Control Overspeed Trip Relay Cutler-Hammer D26MRD70AI TB1673 Control Diesel 736+o6 McGuire Cap> Dem Relay Cabinet Building Report 317 2

CB(SSTEl)

Control Overspeed Trip Relay Cutler-Hammer D26MRD70Al TB1673 Control Diesel 736+06 McGuire Cap> Dem Relay Cabinet Building Report MNS-17-040