ML17272A242

From kanterella
Jump to navigation Jump to search
Forwards IE Circular 79-02, Failure of 120 Volt Vital AC Power Supplies
ML17272A242
Person / Time
Site: Columbia, 05000000, Washington Public Power Supply System, Satsop
Issue date: 01/16/1979
From: Engelken R
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION V)
To: Strand N
WASHINGTON PUBLIC POWER SUPPLY SYSTEM
References
NUDOCS 7901220216
Download: ML17272A242 (9)


Text

qP,R AylQQ(

0 O

qP

+)t *++

UNITED STATES NUCLEAR REGULATORY COMMISSION REGION V SUITE 202, WALNUTCREEK PLAZA 1990 N. CALIFORNIA BOULEVARD WALNUTCREEK, CALIFORNIA 94596

'anuary 16,.1979 NOTE TO:

ALL THOSE ON IE CIRCULAR DISTRIBUTION LIST FROM:

IE, REGION V

SUBJECT:

IE CIRCULAR NO. 79 FAILURE OF 120 VOLT VITAL AC POWER SUPPLIES The attached IE Circular 79-02 was issued this date to the following licensees:

1.

Arizona Public Service Company (Palo Verde 1, 2 5 3, Docket Nos.

50-528, 50-529, 50-530) 2.

Pacific Gas 8t Electric Company (Humboldt Bay Unit 3, Diablo Canyon Units 1

8 2, Docket Nos.

50-133, 50-275, 50-323) 3.

Portland General Electric Company (Trojan, Docket No. 50-344) 4.

Sacramento Municipal UtilityDistrict (Rancho

Seco, Docket No. 50-312) 5.

Southern California Edison Company (San Onofre Units 1, 2, 3, Docket Nos.

50-206, 50-361, 50-362) 6.

Washington Public Power Supply stem (WNP-l, WNP-2, WNP-3, WNP-4, and WNP-S, Docket Nos.

50-460 50-3J, 50-508, 50-513 and 50-509)

Region V has made distribution to the Accessions Unit for the

PDR, Local
PDRs, NSIC, TIC and Central Files.

Enclosures:

1.

Transmittal Ltr.

2.

IE Circular No. 79-02 790l.8z e w f,

Qb

6'EG(p (4

P

~4 0

Cy A

/+

9 QN

+a**+

UNITED STATES NUCLEAR REGULATORY COMMISSION REGION V SUITE 202, WALNUT CREEK PLAZA 1990 N. CALIFORNIA BOULEVARD WALNUTCREEK, CALIFORNIA 94596 Docket Nos.

50-397 50-460 50-513 50-508 50-509

,19N $ R ~.

Washington Public Power Supply System P. 0.

Box 968 3000 George Washington Way

Richland, Washington 99352 Attention:

Mr. N. 0. Strand Managing Director Gentlemen:

The enclosed IE Circular No. 79-02, is forwarded to you for information.

If there are any questions related to your understanding of the suggested

actions, please contact this office.

Sincerely, R.

H. Engelken Director

Enclosures:

1.

IE Circular No. 79-02 2.

List of IE Circulars Issued in the last 12 months cc w/encl:

M. E. Witherspoon, WPPSS

, A. D. Kohler, HNP-2, HPPSS J.

P.

Thomas, WPPSS W. J. Talbott, WPPSS N. Lewis, HA Engergy Facility

FAILURE OF 120 VOLT VITAL AC POWER SUPPLIES P

Description of Circumstances:

IE Circular Ho. 79-02 January 16, 1979 Page I of 2 On September 16, 1978, Arkansas Nuclear One - Unit 2, while in hot functional testing preceding initial criticality, suffered a degrada-tion of both of the independent off-site power sources.

This produced

.an undervoltage condition on the Engineering Safety Features (ESF)

Buses and caused an inadvertent ESF actuation.

The licensee determined that the ESF actuation occurred on a loss of at least two of the uninter-ruptable 120 volt vital AC power sources.

Immediate investigation revealed that all four of the Solidstate Controls, Inc.,

(SCI) inverter static switches had automatically transferred to the alternate power supply (the 120 volt AC being supplied by transformers directly off the ESF buses rather than from the inverter output.)

Figure 1 (attached) shows the functional interconnection of the 120 volt AC power supply system.

A single conclusive cause of the undesired SCI inverter static switch transfer could not be identified.

However, the following problems were discovered during subsequent investigation.

(a)

The SCI inverters have circuitry to monitor the incoming DC voltage level which, on sensing a low voltage (nominally 104 DC volts for these inverters) will trip both input breakers to the inverter component after an adjustable time delay..

The setting of these time delay relays was not verified during either preoperational testing or subsequent maintenance.

The time delay is necessary in order to accommodate transient loading condi-tions which may be encountered.

(b)

On one SCI inverter, a

DC fuse within the inverter component was found blown.

The vendor indicated that this fuse will blow due to an excessive DC voltage to the inverter component caused by a transient on the 480 AC input.

The licensee has subsequently reset the taps on the 480Y to 120V three-phase AC input transformer to limit the DC voltage to the inverter to less than the nameplate maximum rating in the event of a high AC input voltage transient.

(c)

The SCI inverter static switch is designed to transfer to an alternate source on inverter output overcurrent or undervoltage.

'nitially, these trips were set at 125 percent overcurrent and 80 percent undervoltage.

An explanation for the transfer of two

IE Circular No. 79-02 January 16, 1979 Page 2 of 2 of the inverter static switches is that during one of the transfers of site loads, the instantaneous inductive load caused these trip set points to be exceeded.

The licensee has subsequently adjusted the transfer sensing circuitry to higher overcurrent and lower undervoltage trip settings to assure that the inverter will maintain load over the widest possible range of voltage and current.

(Note that in this case, once the SCI inverter transfers to the alternate source, it will not automatically transfer back to normal sour ce. )

All holders of operating licenses should be aware of the potential problems of the types noted above.

It is recommended that the

'ollowing items be considered in your review of this matter:

1.

Determine whether or not time delay circuitry is used in your inverter units.

If so, have they been adjusted to the appropriate set point as required by equipment and the integrated system designs?

2.

Determine if the AC input voltage and transformer tap settings are optimized to prevent exceeding the inverter component name-plate maximum rated DC input voltage in the event of a high AC input voltage transient.

3.

If an alternate 120 volt source is used in your design, determine'f the protection transfer'ircuitry of the inverter has been optimized within design limits to ensure maximum possible avail-ability of the inverter system during transient loading conditions.

An operatinq history of inexplicable transfers may be indicative of the above.

4.

Determine if the administrative controls employed by your facility ensures operability of safety systems after its subcomponents (e.g.,

time delay relays, switches, etc.)

have been subjected to maintenance or testing.

This Circular is also being forwarded to all holders of construction permits for their information with regard to preoperational and startup testing.

No written response to this Circular is required.

If you require additional information regarding this matter, contact the Director of the appropriate NRC Regional Office.

Attachment:

Figure 1

~25 VDC BATTERV BAN r

INC f

ter vDC BATTERY CHARGER QNC

'25 YDC BU5

~

0

~ 41 0

~'

NC 3HC

'Ip r

r

.s~~

OPEN OjgkB Z.

VOLTA..

~j l~

~

.l IA'7"RNP TE-,

pc eE.A Iso URCE

~ )

.INVERT R...

C,OMPONEAT.

~

~

NO;R,MAL Et'E:R~ '~" STAT)C Tv~VS'.F=-n

.s'il TC H

'3 I

t2O vAC PA.NEL F AUGUR

~~OGLE Lit'iE.Dlc.GRAM-lP.O:V>C

IE Circular No. 79-C2 January 16, 1979 LISTING OF IE CIRCULARS ISSUED IN LAST TWELVE MONTHS Circular Subject No.

'ate of Issue Issued To 78-01 78-02 78-03 78-04 Loss of Well Logging Source Proper Lubricating Oil for Terry Tur bines Packaging Greater Than Type A Ouantities of Low Specific Activity Radioactive Haterial for Transport Installation Error That Could Prevent Closing of Fire Doors 4/5/78 4/20/78 5/12/78 5/15/78 All Holders 'of Well Logging Source Licenses All Holders of Reactor OLs or CPs All Holders of Reactor

OLs, CPs, Fuel Cycle, Priority I f1aterial and Waste Disposal Licenses.

'All Holders of Reactor(Ls or CPs 78-05 Inadvertent Safety Injection 5/23/78 During Cool down All Holders of Reactor OLs or CPs 78-06 78-07 78-08 78-09 Potential Common ~lode Flooding of ECCS Equipment Rooms at BWR Facilities Damaged Components of a Bergen-Paterson Series 25000 Hydraulic Test Stand Environmental gualification of Safety Related Equipment at Nuclear Power Plants Arcing of General Electric Company Size 2 Contactors 5/23/78 5/31/78 5/31/78 6/5/78 All Holders of Reactor OLs or CPs All'Holders of Reactor OLs or CPs All Holders of Reactor OLs or CPs All Holders of CPs Enclosure Page 1 of 3

0 IE Circular No. 79-02 i)anuary 16, 1979 LISTING OF IE CIRCULARS ISSUED IN

. LAST TWELVE MONTHS

. Circular Subject No.

Date of Issue Issued to 78-10 78-11

'78-12 78-13 78-14 78-15 78-16 78-17 Control of Sealed Sources Used in Radiation Therapy Recirculation M-G Set Overspeed Stops HPCI Turbine Control Valve Lift Rod Bendin'g

~Inoperability of Multiple Service Water Pumps

'PCI Turbine Reversing Chamber Hold Down Bolting Checkvalves Fail to Close In Vertical Position Limitorque Valve Actuators Inadequate Guard Training/

qualification and Falsified Training Records

, 6/14/78 6/15/78 6/30/78 7/10/78 7/12/78 7/20/78 7/26/78 10/13/78 All Medical Licensees in Categories G

and Gl All Holders of BWR OLs or CPs All Holders of BWR OLs or CPs for plants with HPCI Terry Turbine All Holders of Reactor OLs and CPs except for plants located in: AL, AK, CA, FL, GA, LA, l1S, SC All Holders of BWR OLs or CPs for plants with a HPCI Terry Turbine excepting Duane Arnold and Monticello All Holders of Reactor OLs or CPs All Holders of Reactor OLs or CPs All Holders of and applicants for Reactor OLs.

Enclosure Page 2 of 3

IE Circular No. 79-02 January 16, 1979 LISTING'F IE CIRCULARS ISSUED IN LAST T'HELVE MONTHS 78-18 UL Fire Test Circular Subject No.

Date of Issue 11/6/78 "

Issued To All Holders of Reactor OLs or CPs 78-19 79-01 Manual Override (Bypass) of Safety Actuation Signals Administration of Unauthorized Byproduct Material to Humans 12/28/78 1/12/79 All Holders of CPs All Medical Licensees except Teletherapy Medical Licensees and each Radiopharmaceutical Suppliers Enclosure Page 3 of 3