Monthly Operating Rept for Dec 1996 for Re Ginna Nuclear Power Plant
ML17264A778
Person / Time
Site: Ginna 
Issue date: 12/31/1996
From: Walden J, Widay J
ROCHESTER GAS & ELECTRIC CORP.
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
NUDOCS 9701140299
Download: ML17264A778 (42)


Text

E CATEGORY 1 REGULAT INFORMATION DISTRIBUTION+'STEM (RIDE)

L4 ACCESBION NBR:9701140299 DOC.DATE: 96/12/31 NOTARIZED: NO FACIL:50-244 Robert Emmet Ginna Nuclear Plant, Unit 1, Rochester G

AUTH.NAME AUTHOR AFFILIATION WALDEN,J.V.

Rochester Gas 6 Electric Corp.

WIDAY,J.A.

Rochester Gas 6 Electric Corp.

RECIP.NAME RECIPIENT AFFILIATION DOCKET 05000244

SUBJECT:

Monthly operating rept for Dec 1996 for R.E. Ginna Nuclear Power Plant.W/970108 ltr.

DISTRIBUTION CODE:

IE24D COPIES RECEIVED:LTR ENCL SIZE:

TITLE: Monthly Operating Report (per Tech Specs)

NOTES:License Exp date in accordance with 10CFR2,2.109(9/19/72).

05000244 E

RECIPIENT

'D CODE/NAME PD1-1 PD INTERNAL: AEOD/SPD/RRAB NRR/DRPM/PECB RGNl COPIES LTTR ENCL 1

1 1

1 1

1 1

1 RECIPIENT ID CODE/NAME VISSING,G.

TFD~ Ol OC/DBA/PAD COPIES LTTR ENCL 1

1 1

1 1

1 EXTERNAL: LITCO BRYCE,J H

NRC PDR 1

1 1

1 NOAC 1

1 D

0 E

NOTE TO ALL "RIDS" RECIPIENTS:

PLEASE HELP US TO REDUCE WASTE!

CONTACT THE DOCUMENT CONTROL DESK, ROOM OWFN SD-5(EXT. 415-2083)

TO ELIMINATE YOUR NAME FROM DISTRIBUTION LISTS FOR DOCUMENTS YOU DON'T NEED!

TOTAL NUMBER OF COPIES REQUIRED:

LTTR 10 ENCL

. '.10

I

//////////////

/i/i!i/i/

L1l ~ 01 ~ ~

,(

AHD Zl/E@/g)l/ IIIIIIIIII

////////////// i i'//////////

~<~/

ST At C ROCHESTER GAS AND ELECTRIC CORPORATION o 89 EAST AVENUE, ROCHESTER, N.Y. 14649-0001 TCLKPHONC ARCA CODE 715 546.2700 January 8,

1997 US Nuclear Regulatory Commission Document Control Desk Attn:

Guy S. Vissing Project Directorate I-1 Washington, DC 20555

Subject:

Monthly Report for December, 1996 Operating Status Information R.E.

Ginna Nuclear Power Plant Docket No. 50-244

Dear Mr. Vissing:

Pursuant to Ginna Improved Technical Specifications Section 5.6.4, attached is the monthly operating status report for Ginna Station for the month of December, 1996.

Very truly yours,

a. d.

J se h A. Widay P ant Manager xc:

U. S. Nuclear Regulatory Commission Mr. Guy S. Vissing (Mail Stop 14C7)

Project Directorate I-1 Washington, D.C.

20555 U.S. -Nuclear Regulatory Commission Region I 475 Allendale Road King of Prussia, PA 19406 U.S.

NRC Ginna Senior Resident Inspector Attachments 970ii40299 9hi231 PDR ADOCK 05000244 R

PDR

OPERATING DATAREPORT COMPLETED BY:

50-244 nua 8 1997 John V. Walden TELEPH E

(716) 771-3588

1. Unit Name:

R.E. GINNANUCLEAR POWER PLANT

2. Reporting Period:

December 1996 3.

Licensed Thermal Power (MWt):

1520 4.

Nameplate Rating (Gross MWe):

517 5.

Design Electric Rating (Net MWe):

4?0 6.

Maximum Dependable Capacity (Gross MWe):

490 7.

Maximum Dependable Capacity (Net MWe):

470 8.

IfChanges Occur in Capacity Rating (Items Number 3 Through 7) Since Last Report, Give Reason:

9.

Power Level to Which Restricted, IIAny(NetMWe:

10. Reason For Restrictions, IfAn:

This Month Yr.-to-Date Cumulative"

11. Hours In Reported Period
12. Number of hours Reactor Was Critical
13. Reactor Reserve Shutdown Hours
14. Hours Generator On.line
15. Unit Reserve Shutdown Hours
16. Gross Thermal Energy Generated (MWH)
17. Gross Electrical Energy Generated (MWH)
18. Net Etectrical Energy Generated (MWH)
19. Unit Service Factor (%)
20. UnitAvailabilityFactor (%)
21. Unit Ca pacity Factor (using MDC Net) (%)
22. Unit Capacity Factor (using DER Net) (%)
23. Unit Forced Outage Rate (%)

744.0 744.0 0.0 744.0 0.0 1129271.0 386399.0 368215.0 100.0 100.0 105.3 105.3 0.0 8784.0 6247.2 0.0 6177.8 0.0 9012962.0 3047809.0 2898054.8 70.3 70.3 70.2 70.2 13.0 237552.0 189914.3 1687.6

'86926.5 8.5

'65876270.0 88110309.0 83645866.8 78.7 78.7 75.9 75.9 5.8

24. Shutdowns Scheduled Over Next 6 Months (Type, Date and Duration of Each):
25. IfShutdovm At End of Report Period, Estimate Date of Startup:
26. Units in Test Status (Prior to Commercial Operation):

Forcast Achieved INITIALCRITICALITY INITIALELECTRICITY COMMERCIALOPERATION

'UMULATIVETOTALCOMMENCINGJANUARY1, 1975

"'UMULATIVETOTALCOMMENCINGNOVEMBER8, 1969

I l

AVERAGE DAILY UNIT POWER LEVEL DOCKET NO: 50-244 UNIT: R.E.

Ginna Nuclear Power Plant DATE:

Januar 8

1997 COMPLETED BY:

TELEPHONE:

John Walden 16 771-3588 MONTH December 1996 DAY AVERAGE DAILY POWER LEVEL (MWe-Net)

DAY AVERAGE DAILY POWER LEVEL (MWe-Net) 495 17.

495 2.

494 18.

495 3.

495 19.

495 495 20.

495 5.

495 21.

495 6.

495 22.

495 7.

495 23.

496 8.

495 24.

496 25.

496 10.

26.

496 494 27.

496 12

~

495 28.

496 13.

495 29.

496 14.

496 30.

496 15.

496 31.

496 16.

495 INSTRUCTIONS On this format, list the average daily unit power level in MWe-Net for each day in reporting month.

Compute to the nearest whole megawatt.

DOCKET NO: 60-244 UNIT: R.E. GINNA NUCLEAR POWER PLANT DATE:

Januar 8

997 COMPLETED BY:

M John Walden UNIT SHUTDOWN AND POWER REDUCTIONS REPORT MONTH December 1996 No.

Date Type Duration (hours)

Reason'ethod of shuting down reactors'icensee Event Report 0 System Code4 Component Code'ause

& Corrective Action to Prevent Recurrence 1

F: Forced S:

Scheduled 2

Reason:

A-Equipment (Explain)

B-Maintenance or Test C-Refueling D-Regulatory E-Operator Training &

Lecensee Examination F-Administrative G-Operational Error (Explain) 8-Other (Explain) 3 Method:

1-Manual 2-Manual Scram.

3-Automatic Scram.

4-Other (Explain) 4 Exhibit G - Instructions for Preparation of Data Entry Sheets for

~ Licensee Event Report (LER) File (NUREG-0161) 5 Exhibit 1-Same Source

NARRATIVE

SUMMARY

OF OPERATING EXPERIENCE DOCKET NO: 50-244 UNIT: R.E. Ginna Nuclear Power Plant DATE:

Januar 8

1997 COMPLETED BY:

u5 John Walden TELEPHONE:

16 771-3588 MONTH December 1996 The unit operated all full power for the entire month of December.

The average power level was 99.9:.

~

i

Distribution Sheet Priority: Normal From: Stefanie Fountain Distri62.txt Action Recipients:

G Vissing Copies:

1 Paper Copy Internal Recipients:

RidsRgn1MailCenter Rids Res DraaOerab RidsOcfoDpbaPab RidsManager RidsAcrsAcnwMailCenter RGN1.

RES/DRAA/OERAB OCF PB ESKER Q~

ACRS External Recipients:

NOAC INEEL Marshall 0

0 0

OK OK OK OK 0

OK Paper Copy Paper Copy Paper Copy Paper Copy Paper Copy, Paper Copy Paper Copy Total Copies:

8 Item: ADAMS Document Library: ML ADAMS"HQNTAD01 ID: 003694568:1

Subject:

Monthly Report for February, 2000 Operating Status Information R.E. Ginna Nuclear Po wer Plant Body:

ADAMS DISTRIBUTION NOTIFICATION.

Electronic Recipients can RIGHT CLICKand OPEN the firstAttachment to View the Document in ADAMS. The Document may also be viewed by searching for Accession Number ML003694568.

Page 1

Distri62.txt lE24-Monthly Operating Report(per Tech Specs)

Docket: 05000244 Page 2

aeo ROCHESTER GAS ANDELECTRIC CORPORATION.B9 EASTAVENUE, ROCHESTER, N.Y. 14649-0001 AREA CODE 716-546-2700 March 10, 2000 US Nuclear Regulatory Commission Document Control Desk Attn:

Guy S. Vissing Project Directorate I-1 Washington, DC 20555

Subject:

Monthly Report for February, 2000 Operating Status Information R.E. Ginna Nuclear Power Plant Docket No. 50-244

Dear Mr. Vissing:

Pursuant to Ginna Improved Technical Specifications Section 5.6.4, attached is the monthly operating status report for Ginna Station for the month of February, 2000.

Very truly yours/~ ('+oW)

Joseph A. Widay Plant Manager xc:

U.S. Nuclear Regulatory Commission Mr. Guy S. Vissing (Mail Stop 14B2)

Project Directorate l-1 Washington, D.C. 20555 U.S. Nuclear Regulatory Commission Region I

475 Allendale Road King of Prussia, PA 19406 U.S. NRC Ginna Senior Resident Inspector Attachments

j

~

(r t

OPERATING DATAREPORT COMPLETED BY:

50-244 March 10, 2000 John V. Walden TELEPHONE (716) 771-3588 OPERATING STATUS 480

1. Unit Name:

R.E. GINNANUCLEARPOWER PLANT

2. Reporting Period:

Februa, 2000 3.

Design Electric Rating (Net MWe):

470 4.

Maximum Dependable Capacity (Net MWe):

Notes:

This Month Yr.-to-Date Cumulative**

5. Number of hours Reactor Was Critical
6. Hours Generator On-line
7. Unit Reserve Shutdown Hours
8. Net Electrical Energy Generated (MWH) 696.0 696.0 0.0 331765.0 1440.0 1440.0 0.0 700301.0 215654.0 212583.9 8.5 96085436.4
    • CUMULATIVETOTALCOMMENCING NOVEMBER 8, 1969

DOCKET NO: 50-244 UNIT NAME: R.E. GINNA NUCLEAR POWER PLANT

~ATE:~M COMPLETED BY: John V. Walden TELEPHONE~8 UNITSHUTDOWN REPORTING PERIOD:

Februa 2000 (MonthNear)

NO.

DATE TYPE F: FORCED S: SCHEDULED DURATION (HOURS)

REASON(')

METHOD OF SHUTTING DOWN(')

CAUSE/CORRECTIVE ACTIONS COMMENTS

SUMMARY

The unit experienced two power reductions due to frazil ice formation on the intake structure.

The events occurred on february 8 and;12.

Power was reduced to approximately 40% during each occurrence.

Average power forthe month of February was 96.5%.

(1) Reason A - Equipment Failure (Explain)

B - Maintenance or Test C - Refueling D - Regulatory Restriction E - Operator Training/License Examination F - Administrative G - Operational Error (Explain)

H - Other (Explain)

(2) Method 1 - Manual 2 - Manual TripfScram 3 - Automatic Trip(Scram 4 - Continuation 5 - Other (Explain)

., Distribution Sheet gu-S/q' Priority: Normal From: Patricia Exum Distri49.txt Action Recipients:

G Vissing Internal Recipients:

RidsRgn1MailCenter RidsResDraaOerab Rids Manager RidsAcrsAcnwMailCenter RGN1 RES/DRAA/OERAB OC FILE C ACRS Copies:

1 Paper Copy OK OK OK 0

OK Paper Copy 1

Paper Copy Paper Copy Paper Copy Paper Copy External Recipients:

NOAC INEEL Marshall Paper Copy Paper Copy Total Copies:

Item: ADAMS Document

'ibrary:

ML ADAMS"HQNTAD01 ID: 003685028:1

Subject:

Monthly Report for January, 2000 Operating Status Information R.E. Ginna Nuclear Pow er Plant Body:

ADAMS DISTRIBUTION NOTIFICATION.

Electronic Recipients can RIGHT CLICKand OPEN the first Attachment to View the Document in ADAMS. The Document may also be viewed by searching for Accession Number ML003685028.

Page 1

0 4

'lt

Distri49.txt lE24-Monthly Operating Report(per Tech Specs)

Docket: 05000244 Page 2

AeO N5%

ROCHESTER GAS ANDELECTRIC CORPORATION.89EASTAVENIIE, ROCHESTER, N.Y. 14649-0001 AREA CODE 716-546-2700 February 7, 2000 US Nuclear Regulatory Commission Document Control Desk Attn:

Guy S. Vissing Project Directorate I-1 Washington, DC 20555

Subject:

Monthly Report for January, 2000 Operating Status Information R.E. Ginna Nuclear Power Plant Docket No. 50-244

Dear Mr. Vissing:

Pursuant to Ginna Improved Technical Specifications Section 5.6.4, attachedis the monthly operating status report for Ginna Station for the month of January, 2000.

Very truly yours, a.u-se hA.Widay lant Manager xc:

U.S. Nuclear Regulatory Commission Mr. Guy S. Vissing (Mail Stop 14B2)

Project Directorate I-1 Washington, D.C. 20555 U.S. Nuclear Regulatory Commission Region I

475 Allendale Road King of Prussia, PA 19406 U.S. NRC Ginna Senior Resident Inspector Attachments

IJ

'PERATING DATAREPORT COMPLETED BY:

50-244 ebrua 7, 2000 John V. Walden TELEPHONE (716) 771-3588 OPERATING STATUS 480

1. Unit Name:

R.E. GINNANUCLEAR POWER PLANT

2. Reporting Period:
Janua, 2000 3.

Design Electric Rating (Net MWe):

470 4.

Maximum Dependable Capacity (Net MWe):

Notes:

This Month Yr.-to-Date Cumulative**

5. Number of hours Reactor Was Critical
6. Hours Generator On-line
7. Unit Reserve Shutdown Hours
8. Net Electrical Energy Generated (MWH) 744.0 744.0 0.0 368536.0 744.0 744.0 0.0 368536.0 214958.0 211887.9 8.5 95753671.4
    • CUMULATIVETOTALCOMMENCING NOVEMBER 8, 1969

. ea, P

DOCKET NO: 50-244 UNITNAME: R.E. GINNA NUCLEAR POWER PLANT

~ATE~I COMPLETED BY: John V. Walden TELEPHONE:~

UNITSHUTDOWN REPORTING PERIOD:

Janua 2000 (Month/Year)

NO.

DATE TYPE F: FORCED S: SCHEDULED DURATION (HOURS)

REASON('l METHOD OF SHUTTING DOWN(')

CAUSE/CORRECTIVE ACTIONS COMMENTS

SUMMARY

The unit operated at fullpower for the entire month of January.

Average power forthe month was 99.8%.

(1) Reason A - Equipment Failure (Explain)

B - Maintenance or Test C - Refueling D - Reguhtory Restriction E - Operator Training/License Examination F - Administrative G - Operational Error (Explain)

H - Other (Explain)

(2) Method 1 - Manual 2 - Manual TripfScram 3 - Automatic Trip/Scram 4 - Continuation 5 - Other (Explain)

~ h

AIVD ROCHESTER GAS ANDELECTRIC CORPORATION'69EASTAVENUE, ROCHESTER, NY 14649-0001 AREA CODE 716-546-2700 January 10, 2000 US Nuclear Regulatory Commission Document Control Desk Attn:

Guy S. Vissing Project Directorate I-1 Washington, DC 20555

Subject:

Monthly Report for December, 1999 Operating Status Information R.E. Ginna Nuclear Power Plant Docket No. 50-244

Dear Mr. Vissing:

Pursuant to Ginna Improved Technical Specifications Section 5.6.4, attached is the monthly operating status report for Ginna Station for the month of December, 1999.

Very truly yours, a.d s phA.Widay Plant Manager xc:

U.S. Nuclear Regulatory Commission Mr. Guy S. Vissing (Mail Stop 14B2)

Project Directorate I-1 Washington, D.C. 20555 U.S. Nuclear Regulatory Commission Region I

475 Allendale Road King of Prussia, PA 19406 U.S. NRC Ginna Senior Resident Ins ector Attachments

OPERATING DATAREPORT COMPLETED BY:

50-244 Janua 10, 2000 John V. Walden TELEPHONE (716) 771-3588 OPERATING STATUS 480

1. Unit Name:

R.E. GINNANUCLEAR POWER PLANT

2. Reporting Period:

December, 1999 3.

Design Electric Rating (Net MWe):

470 4.

Maximum Dependable Capacity (Net MWe):

Notes:

This Month Yr.-to-Date Cumulative**

5. Number of hours Reactor Was Critical
6. Hours Generator On-line
7. Unit Reserve Shutdown Hours
8. Net Electrical Energy Generated (MWH) 744.0 744.0 0.0 368290.0 7494.8 7445.2 0.0 3534055.0 214214.0.

211143.9 8.5 95385135.4

    • CUMULATIVETOTALCOMMENCING NOVEMBER 8, 1969

DOCKET NO: 50-244 UNIT NAME: R.E. GINNA NUCLEAR POWER PLANT DATE: Janua 10 2000 COMPLETED BY: John V. Walden TELEPHDNE:~

UNIT SHUTDOWN REPORTING PERIOD:

December 1999 (Month/Year)

NO.

DATE TYPE F:FORCED S:SCHEDULED DURATION (HOURS)

REASON('>

METHOD OF SHUTTING DOWN(')

CAUSE/CORRECTIVE ACTIONS COMMENTS

SUMMARY

The unit operated at fullpower forthe entire month of December.

Average power forthe month was 99.8%.

(1) Reason A - Equipment Fai!ure (Explain)

B - Maintenance or Test C - Refueling D - Regulatory Restriction E - Operator Training/License Examination F - Administrative G - Operational Enor (Explain)

H - Other (Explain)

(2) Method 1 - Manual 2 - Manual Trip/Scram 3 - Automatic Trip(Scram 4 - Continuation 5 - Other (Explain)

Distribution Sheet Distri49.txt Priority: Normal From: Elaine Walker Action Recipients:

G Vissing Internal Recipients:

RGN1 RES/DRAA/OERAB OCFO/DP BA

~FILE CENTER~01 A'CRS Copies:

1 Not Found Not Found Not Found Not Found Not Found Not Found External Recipients:

NOAC INEEL Marshall Not Found Not Found Total Copies:

Item: ADAMS Document Library: ML ADAMS"HQNTAD01 ID: 003676972

Subject:

Monthly Report for December, 1999 Operating Status Information R.E. Ginna Nuclear Po wer Plant Docket No. 50-244. With January 1'0, 2000 letter.

Body:

Docket: 05000244, Notes: License Exp date in accordance with 10CFR2,2.109(9/19/72).

Page 1

~ I

Distribution Sheet Distri47.txt Priority: Normal From: Stefanie Fountain Action Recipients:

G Vissing Internal Recipients:

RGN 1>>.

RES/DRAA/OERAB OC/D LE CENTE ACRS Copies:

1 Not Found Not Found Not Found Not Found Not Found Not Found External Recipients:

NRC PDR NOAC INEEL Marshall Not Found Not Found Not Found Total Copies:

Item: ADAMS Document Library: ML ADAMS"HQNTAD01 ID: 993480495

Subject:

Monthly operating report for November 1999 for R. E. Ginna Nuclear Power Plant. With I etter dated 12/7/99.

Body:

PDR ADOCK 05000244 R Docket: 05000244, Notes: License Exp date in accordance with 10CFR2,2.109(9/19/72).

Page 1

0 I.

4 1%

l~

0 ANO ROCHESTER GAS AND ELECTRIC CORPORATION.89 EASTAVENIIE, ROCHESTER, N.Y.

14649-0001'REA CODE 716-546-2700 December 7, 1999 US Nuclear Regulatory Commission Document Control Desk Attn:

Guy S. Vissing Project Directorate I-1 Washington, DC 20555

Subject:

Monthly Report for November, 1999 Operating Status Information R.E. Ginna Nuclear Power Plant Docket No. 50-244

Dear Mr. Vissing:

Pursuant to Ginna Improved Technical Specifications Section 5.6.4, attached is the monthly operating status report for Ginna Station for the month of November, 1999.

Very truly yours, CL0 se A. Widay lant Manager xc:

U.S. Nuclear Regulatory Commission Mr. Guy S. Vissing (Mail Stop 14B2)

Project Directorate I-1 Washington, D.C. 20555 U.S. Nuclear Regulatory Commission Region I

475 Allendale Road King of Prussia, PA 19406 U.S. NRC Ginna Senior Resident Inspector Attachments

e 1

OPERATING DATAREPORT 50-244 December 7, 1999 COMPLETED BY:

John V. Walden TELEPHONE (716) 771-3588 OPERATING STATUS 480

1. Unit Name:

R.E. GINNANUCLEARPOWER PLANT

2. Reporting Period:

November, 1999 3.

Design Electric Rating (Net MWe):

470 4.

Maximum Dependable Capacity (Net MWe):

Notes:

This Month Yr.-to-Date Cumulative**

5. Number of hours Reactor Was Critical
6. Hours Generator On-line
7. Unit Reserve Shutdown Hours
8. Net Electrical Energy Generated (MWH) 720.0 720.0 0.0 348064.0 6750.8 6701.2 0.0 3165765.0 213470.0 210399.9 8.5 95016845.4
    • CUMULATIVETOTALCOMMENCING NOVEMBER 8, 1969

DOCKET NO: 50-244 UNIT NAME: R.E. GINNANUCLEAR POWER PLANT DATE: December 7 1999 COMPLETED BY: John V. Walden EELEPNQNE~7777-7 UNITSHUTDOWN REPORTING PERIOD:

November 1999 (Month/Year)

DATE TYPE F: FORCED S:SCHEDULED DURATION (HOURS)

REASON">

METHOD OF SHUTTING DOWNt'>

CAUSE/CORRECTIVE ACTIONS COMMENTS

SUMMARY

Power was reduced to approximately 50% for a planned condenser waterbox inspection on November 13, 1999. The unit operated at-full power prior to and after the inspection. Average power for the month was 97.7%.

(1) Reason A - Equipment Failure (Explain)

B - Maintenance or Test C - Refueling D - Regulatory Restriction E - Operator Training/License Examination F - Administrative G - Operational Error (Explain)

H - Other (Explain)

(2) Method 1 - Manual 2 - Manual Trip/Scram 3 - Automatic Trip/Scram 4 - Continuation 5 - Other (Explain)

'Ve~ 'I 3 8$

4jl f k,

V E

I

ANO L8%

ROCHESTER GAS ANDELECTRICCORPORATION 89EASTAVENUE, ROCHESTER, N.Y. 14649-000$

AREA CODE 716-546-2700 November 10, 1999 US Nuclear Regulatory Commission Document Control Desk Attn:

Guy S. Vissing Project Directorate l-1 Washington, DC 20555

Subject:

Monthly Report for October, 1999 Operating Status Information R.E. Ginna Nuclear Power Plant Docket No. 50-244

Dear Mr. Vissing:

Pursuant to Ginna Improved Technical Specifications Section 5.6.4, attached is the monthly operating status report for Ginna Station for the month of October, 1999.

Very truly yours,

'.iJ se A. Widay Plant Manager xc:

U.S. Nuclear Regulatory Commission Mr. Guy S. Vissing (Mail Stop 14B2)

Project Directorate l-1 Washington, D.C. 20555 U.S. Nuclear Regulatory Commission Region I

475 Allendale Road King of Prussia, PA 19406 U.S. NRC Ginna Senior Resident Inspector Attachments

~~QLQl.(

IOisil99

I

OPERA ING DATAREPORT 50-244 November 10, 1999 COMPLETED BY:

pp) / Q John V. Walden TELEPHONE (716) 771-3588 OPERATING STATUS 480

1. Unit Name:

R.E. GINNANUCLEARPOWER PLANT

2. Reporting Period:

October, 1999 3.

Design Electric Rating (Net MWe):

470 4.

Maximum Dependable Capacity (Net MWe):

Notes:

This Month Yr.-to-Date Cumulative**

5. Number of hours Reactor Was Critical
6. Hours Generator On-line
7. Unit Reserve Shutdown Hours
8. Net Electrical Energy Generated (MWH) 745.0 745.0 0.0 366752.0 6030.8 5981.2 0.0 2817701.0 212750.0 209679.9 94668781.4
    • CUMULATIVETOTALCOMMENCING NOVEMBER 8, 1969

P t

J t

g Cl,

' 'i V

4 P

DOCKET NO: 50344 UNIT NAME: R.E. GINNANUCLEAR POWER PLANT DATE: November 10 1999 COMPLETED BY: John V. Walden TELEPHONE:~

~ >>

--3~ 8I8 UNITSHUTDOWN REPORTING PERIOD:

October 1999 (Month/Year)

NO.

DATE TYPE F:FORCED S:SCHEDULED DURATION (HOURS)

REASON<'>

METHOD OF SHUTTING DOWN('>

CAUSE/CORRECTIVE ACTIONS COMMENTS

SUMMARY

The unit operated at full power for the entire month of October. Average power for the month was 99.7%.

(1) Reason A-Equipment Failure (Explain)

B - Maintenance or Test C - Refueling D - Regulatory Restriction E - Operator Training/License Examination F - Administrative G - Operational Error (Explain)

H - Other (Explain)

(2) Method 1-Manual 2-Manual Trip/Scram 3 - Automatic Trip/Scram 4 - Continuation 5 - Other (Explain)

0

~

LQg 1 gay a

Distribution Sheet Distri96.txt Priority: Normal From: Stefanie Fountain Action Recipients:

G Vissing Internal Recipients:

RGN 1.

RES/DRAA/OERAB OC/DJ34/PAD FILECENT R 0 ACRS Copies:

1 Not Found Not Found Not Found Not Found Not Found Not Found External Recipients:

NRC PDR NOAC

'INEEL Marshall Not Found Not Found Not Found Total Copies:

Item: ADAMS Document Library: ML ADAMS"HQNTAD01 ID'93240386

Subject:

Monthly Report for October,1999 Operating Status for RE Ginna Nuclear Power Plant Body:

PDR ADOCK 05000244 R Docket: 05000244, Notes: License Exp date in accordance with 10CFR2,2.109(9/19/72).

Page 1