ML17264A376
| ML17264A376 | |
| Person / Time | |
|---|---|
| Site: | Ginna |
| Issue date: | 02/21/1996 |
| From: | Mecredy R ROCHESTER GAS & ELECTRIC CORP. |
| To: | Andrea Johnson NRC (Affiliation Not Assigned), NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM) |
| References | |
| NUDOCS 9602260088 | |
| Download: ML17264A376 (5) | |
Text
CATEGORY 1 REGULA Y INFORMATION DISTRIBUTIO SYSTEM (RIDS)
ACCESSION NBR:9602260088 DOC.DATE: 96/02/21 NOTARIZED: NO DOCKET I FACIL:50-244 Robert Emmet Ginna Nuclear Plant, Unit 1, Rochester G
05000244 AUTH.NAMEUTHORAFFILIATION MECREDY,R.C.
.Rochester Gas
& Electric Corp.
RECIP.NAME RECIPIENT AFFILIATION JOHNSONgA.R.
SUBJECT:
Special rept:on 960115,diesel fire pump !'ontroller held,a declared inoperable to allow mod process to begin. Removal 6
installation of diesel fire pump
& controller completed on 960224.
DISTRIBUTION CODE:
IE22D COPIES RECEIVED:LTR I
ENCL Q SIZE-TITLE: 50.73/50.9 Licensee Event Report'(LER), Incident Rpt, etc.
NOTES:License Exp date in accordance with 10CFR2,2.109(9/19/72).
05000244 RECIPIENT ID CODE/NAME PD1-1 PD INTERNAL: AEOD/SPD/RAB
~FXCE CENT~ER NRR/DE/EELB NRR/DRCH/HHFB NRR/DRCH/HOLB NRR/DRPM/PECB NRR/DSSA/SRXB RGNl FILE 01 EXTERNAL: L ST LOBBY WARD NOAC MURPHYiG.A NRC PDR COPIES LTTR ENCL 1
1 1
RECIPIENT ID CODE/NAME JOHNSON,A AEOD/SPD/RRAB NRR/DE/ECGB NRR/DE/EMEB NRR/DRCH/HICB NRR/DRCH/HQMB NRR/DSSA/SPLB RES/DSIR/EIB LITCO BRYCEEJ H
NOAC POOREEW.
NUDOCS FULL TXT COPIES LTTR ENCL e,~rf Pg3$ /6j
/Z,5 NOTE TO ALL "RIDS" RECIPIENTS:
PLEASE HELP US TO REDUCE WASTE!
CONTACT THE DOCUMENT CONTROL DESK, ROOM OWFN 5D-5(EXT. 415"2083)
TO ELIMINATE YOUR NAME FROM DISTRIBUTION LISTS FOR DOCUMENTS YOU DON'T NEED!
TOTAL NUMBER OF COPIES REQUIRED:
LTTR 25 ENCL
AND ROCHESTER GAS ANDElECTR/C CORPORATION
~ 89 EASTAVENUE, ROCHESTE'R N K M6d5'0%1 AREA CODE 7I6 5do-27K ROBERT C. MECREDY Vice President Nvcieor Operotions February 21, 1996 U.S. Nuclear Regulatory Commission Document Control Desk Attn:
Allen R. Johnson Project Directorate I-1 Washington, D.C.
20555
Subject:
Thirty (30)
Day Special Report Inoperable Fire Pump Greater Than Seven (7)
Days R.E.
Ginna Nuclear Power Plant Docket No. 50-244 Ref.(a):
Updated Final Safety Analysis Report (UFSAR),
Table 9.5-2, Item 2
Dear Mr. Johnson,
In accordance with the Ginna Station Updated Final Safety Analysis Report (UFSAR),
Table 9.5-2, Item 2,
Required Action A.1, this thirty day special report on an inoperable fire pump for a duration greater than 7 days is being submitted.
During 1995, RG&E concluded that replacement of the diesel engine driver and controller on the diesel driven fire pump was warranted.
This was due to the continued degradation of the diesel fire pump head gaskets and water
- pump, along with the inability to obtain parts for the King-Knight Controller.
A plant change was developed to install a new Cummins NT855-F6 fire rated diesel driver and a
UL listed Firetrol FTA-1100 micro controller. It was determined that it would take approximately 2
weeks to complete the modification and subsequent testing.
On January 15, 1996, with the plant at power, the diesel fire pump and controller were held and'eclared inoperable to allow the modification process to begin.
The removal and'installation of the diesel fire pump and controller was completed on January 24, 1996.
Ginna Station is equipped with two redundant fire
- pumps, one electric motor driven and one diesel engine driven.
In accordance with compensatory measures identified in UFSAR Table 9.5-2, Item 2., the required action statement A.1 (b) was implemented, which states that with an inoperable redundant component, the component should be restored to operable status within 7
days.
If not restored within that time, the redundant component should be run continuously until.the inoperable component is restored to operable status.
In addition, a 30-day special report shall be prepared.
Accordingly the motor driven fire pump was started on Monday 9602260088 960221 PDR ADDCK 05000244 8
January 22,
- 1996, and was run continuously until the diesel fire pump was declared operable.
Testing began on January 25, 1996, and was completed on February 2,
- 1996, when the diesel fire pump was declared operable.
Throughout the modification process the fire water capabilities were adequately maintained by the running of the motor driven'fire pump.
Based on the known work scope and the appropriate compensatory measures that were taken, all required actions of the UFSAR were completed, and plant safety was never comprised.
Very truly yours, Robert C. Mecred GAH4417 xc: