Attachment 51 Uoltage Simulation for Case EOF LOC4 LOCA Simulation for 50/50 mode Circuit 767 Details 12B Transformer Feeding Bus 12B Prepared by:

~P-2 -$0 Reviewed by:~~

'I Approved by:

~SO 90 90ltI050244 900920 PDR ADOCK 05000244 P

PDC

This attachment is associated with Design Analysis 4525-2 "Adequacv of Electric Svstem Voltages" Rev 1.

The results of an additional LOCA voltage simulation is presented in this attachment.

Xn particular, case EOF LOCA was repeated with breaker 12BY opened.

This new case (EOF LOC4) quantifies the performance of circuit 767 during a

I.OCA condition when the offsite power system is configured in the normal 50/50 configuration and the grid voltage is at its minimum value of 116Kv.

Xt was not necessary to quantify the performance of circuit 751 for this condition since a

more limiting case (DOF LOCA) gives acceptable results.

2.0 Results For the EOF LOC4 case, 480 volt bus voltages, including the 1E buses, remain above 414 volts.

The lowest 480 bus voltage is 431.5 on Bus 16.

The voltages at motor terminals 16S and 16C are 429 and 430.5 respectively.

The lowest I'ICC voltage is 421.9 on ICC 1D.

The lowest 4160 bus voltage for the EOF LOC4 case was 3964 on Bus 12B which is well above the 3600 volt limit.

3.0 Conclusion The EOF LOC4 case demonstrates that circuit 767 will be able

'o maintain adequate voltages during LOCA conditions for the normal 50/'50 configuration even during worst case grid voltage conditions.

,POWER TECHNOLOGIES INC.

EOF LOC4, OFF'LINE P6cQ g

LOCA LOAD 116KV NIMUM VOLTAGES BELOW POWER SYSTEM SIMULATOR,P U

BUSZ 50/50 MODE 200.0 PERCENT VERSION 4 '

AUG 28 1990

TUE, 16:00 MINIMUM VOLTAGE NODE S13AE S13A 767 12BTP 12BT 12BY 12BY2 12BTS 12BX 12B22 12B SST16 16 16C 16S 1D SST17 IS l1B 11BC 11BS SST15 l5 15C lr5S PHAS ABC ABC ABC ABC ABC ABC ABC ABC ABC ABC ABC ABC ABC ABC

'BC ABC ABC ABC ABC ABC ABC ABC ABC ABC ABC ABC ABC

/PU 1.009 1.009 0.969 0.968 0.966 0.966 0.966 0.966 0.955 0.955 0.953 0.951 0 '99 0.897 0.894 0.879 0.952 0.934 0.933 0.934 0.953 0.950 0.948 0.953 0.918 0

~ 918 0.911

/KV 67.0 67.0 19.3 19.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 0.4 0.4 0.4 0.4 2.3 0.5 0.5 0

5 2.3 2.3 2.3 2.3 0.4 0.4 0.4

/ 100.

100.9 100.9 96.9 96.8 96.6 96 '

96.6 96.6 95.5 95.5

95. 3 95.1 89.9 L

89.7 L

89.4 L

87.9 L

95.2 93.4 L

93.3 L

93.4 L

95.3 95.0 94.8 95.3 91.8 L

91.8 L

91.1

POWER TECHNOLOGIES INC.

POWER SYSTEN Sii~jULRTOR, P'OF

LOC4, OFFLINE,
PRQ, BUSZ 50/50 iiODE LOCA LOAD 116KV VERSION 4.0 AUG 28 1990
TUE, 16:01 AL TREE DES NODES LOOPS TNSF 55 27 0

7 ASYNC SWCH GENS 4

0 SYNC ASYNC SYNC GENS i~1OTS RIOTS 0

0 0

KW KVAR PF SOURCE

9. 88iM 5.14M 0 '87 LOSSES 127.82 923.19 GENERATION 0.00 0.00 MOTOR LOAD 0.00 0.00 9.37 0.00 CHARGING CAPACITANCE BY CATEGORY KW KVAR 1

0.00 0.00 ACTUAL STATIC LOAD 2

3 0.00 0.00 0.00 0.00 4

9748. 97 4226.23 ilAX V-LN 1.009 PU, 66.97 MIN V-LiN 0.948 PU, 2.28 i~lAX V-LL 0.934 PU, 0.45

.1IN V-LL 0.879 PU, 0.43 KV, KV, KV, KV, 100.9/ 100.0 V AT NODE S13AE PHASE 94.8/ 100.0 V AT NODE 11BS PHASE 93.4/ 100.0 V AT NODE 17 PHASE 87.9/ 100.0 V AT NODE 1D PHASE A

B CA AB BY CATEGORY KW R

1 0.00 0.00 NOMINAL STATIC LOAD 2

3 0.00 0.00 9872.27 0.00 0.00 4341.66 FSC DEFPF 0.00 1.00 0.00 1.00 0.00 1.00 0.00 1.00 BY CATEGORY KW KVAR 1

0.00 0.00 ACTUAL STATIC LOAD 2

3 0.00 0.00 9748.97 0.00 0.00 4226.23 KW KVAR GENERATORS MOTORS ASYNCHRONOUS SYNCHRONOUS ASYNCHRONOUS SYNCHRONOUS 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00