ML17254A731

From kanterella
Jump to navigation Jump to search
Forwards Safety Insp Rept 50-244/85-26 on 851201-31 & Notice of Violation.On 851203,technician Installed Chlorine Monitor in Discharge Canal & Isolated Sample Flow Line.Caused by Insufficient Mgt Planning & Controls
ML17254A731
Person / Time
Site: Ginna 
Issue date: 01/24/1986
From: Collins S
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
To: Kober R
ROCHESTER GAS & ELECTRIC CORP.
Shared Package
ML17254A732 List:
References
NUDOCS 8601310110
Download: ML17254A731 (3)


See also: IR 05000244/1985026

Text

Docket No. 50-244

Rochester

Gas

and Electric Corporation

ATTN:

Mr. Roger

W. Kober

Vice President

Electric and

Steam Production

49 East Avenue

Rochester,

New York 14649

Gentlemen:

Subject:

Inspection

50-244 85-2

This refers to the routine safety inspection

conducted

by Mr.

W. A. Cook

of this office on December

1,

1985 through

December

31,

1985 at the

R.

E.

Ginna Nuclear

Power Plant of activities authorized

by

NRC license

No.

DPR-18

and to the discussions

of our findings by Mr. Cook with Mr. S.

MD Spector

and

other members of your staff periodically during the inspection.

Areas examined during this inspection

are described

in the

NRC Region I

Inspection

Report which is enclosed with this letter.

Within these

areas,

the inspection

consisted of selective

examinations

of procedures

and

representative

records,

interviews with personnel

and observations

by the

inspector.

Based

on the results of this inspection, it appears

that one of your

activities was not conducted

in full compliance with NRC requirements,

as set

forth in the Notice of Violation, enclosed

herewith

as Appendix A.

Specifically,

on December

3,

1985,

a station technician installed

a

new

chlorine monitor in the discharge

canal

sample line and unknowingly isolated

sample line flow to the radiological effluent composite

sampler.

The

inspector determined that this maintenance activity was performed without

appropriate

maintenance

controls or proper preplanning,

review and approval.

A similar event indicating insufficient planning

and managerial

controls

was

brought to your attention in Inspection

Report

No. 50-244/85-10.

This

violation indicates

an apparent

weakness

in the control of non-scheduled

maintenance

related activities.

This violation has

been catagorized

by severity level in accordance

with the

revised

NRC Enforcement Policy ( 10 CFR 2, Appendix C) 1985.

You are required

to respond to this letter and in preparing your response,

you should follow

the instructions

in Appendix A.

e~a~slo~~o

8~Oiae

PDR

ADOCR 00000244

8

PDR

1

OFFICIAL RECORD

COPY

IR GINNA 85-26 - 0001.0.0

01/21/86

Rochester

Gas'and

Electric Company

The response

directed

by this letter and the accompanying

Notice are not

subject to the clearance -procedures

of the Office of Management

and Budget as

required

by the Paperwork

Reduction Act of 1980,

PL 96-511.

Your cooperation

is appreciated.

Sincerely,

E<~eL sr~,

Samuel J. Collins, Chief

Projects

Branch

No.

2

Division of Reactor Projects

Enclosures:

1.

Appendix A, Notice of Violation

2.

NRC Region I Inspection

Report

Number 50-244/85-26

cc w/encl:

Harry H. Voigt, Esquire

Central

Records

(4 copies)

Director,

Power Division

Public Document

Room (PDR)

Local Public Document

Room (LPDR)

Nuclear Safety Information Center

(NSIC)

NRC Resident

Inspector

State of New York

R:RI

ook

1/i~ /86

P:RI

tair

1//8/86

RI

inville

1//3/86

bcc w/encl:

Region I Docket

Room (with concurrences)

,Senior Operations Officer (w/o encls)

Section Chief,

DRP

ORSON, Peak

~C.

DR: RI

~55': ~~

Co

1

s

OPSIA'<<

zP~jas

OFFICIAL RECORD

COPY

IR GINNA 85-26 - 0002.0.0

01/10/86

l Col

~

~

~ .

7

'I

~ gC ~

~ +l

'n

~ II

H

'l

i