ML17252B013

From kanterella
Jump to navigation Jump to search
Letter Confirming a 11/20/1972 Conversation Concerning Reactors Low Pressure Switches Being Out of Calibration - Dresden Unit 3
ML17252B013
Person / Time
Site: Dresden 
(DPR-025)
Issue date: 11/20/1972
From: Worden W
Commonwealth Edison Co
To: Anthony Giambusso
US Atomic Energy Commission (AEC)
References
Download: ML17252B013 (1)


Text

1 M I

So-~'1-9 1

. \\

D+

USAEC-HQS GTWN VU WSH

/

TLXA289 WAE197<2043JC1~032231C325002>PD 11/20/72 2039

  • C
~wt

-~

ICS IPMVEIA MVN

~@.

~

..... J 2CZC 00222 TOVE MORRIS ILL 120 11-20 315P_CST

~i R'1S MR A GIAMBUSSO DEPUTY DIRECTOR OF REACTIV~ PROJECTS ~~

'"~

DIRECTOR APE OF

~ICENSING WUX ~ACHINE.

~

  • S..

()tJf

  • N L6 ATOMICH ENERGY COMMISSION W\\SH I NG TON DC M ~.*

~~} ' -

.9.J. BJEC T :.OP R. -2 5 DRESDEN NUCLEAR POWER' STAT I ON U_ N 1 T 3 n1-.

l1'f.l::'f:(J; *~, IJrc~

lHIS WILL CONF !RM A CONVERSATION wi TH MR ;i DANCE OF YOUR!

~- ~/.., $.

I A~. 1100 HOURS THIS DATE C~N<;:ERNING REACT,ORS LOW PRESSURE _sw1 TC. ~

-~~;~ \\ \\~ '.

~ING OUT.OF ~ALIBERATION~ ON

~l/L9/72 WHlLE UNIT i-WAS SHUT DOWN, I

AtAL)BERATION WAS MADE ON MAIN STEAM LINE LOW PRESSURE-SWITCHES.

CABLE 3.2.1 OF THE TECHNICAL SPE.CIFICATIONS STATE THAT THE TRIP

~VEL SETTING ON THESE SWITCHES SHOULD BE EQUAL TO OR GREATER lHAN 8 50 PS I G ** ALL FOUR PRESSURE SW I TC HES HAD TR IP SETTINGS BELOW 850 PSIG. PRESSURE SWITCHES 3-261-30A AND 308 HAD SETTING

. F 847 AND 848 PSIG *. PRESSURE SWITCHES 3-261-30C *AND 300

~D.SETTINGS OF 849 AND 848 PSIG. IN ORDER TO ELIMINATE.THIS PROBLEM*

I IN THE FUTURE.THE "AS LEFT" CALIBERATION SETTING ON THESE

~ITCHES HAS BEEN CHA~GED F~OM 85~ PLUS OR Ml~US PSIG Pl,.US OR i"11NUS 4PSIG.

W P WORDEN

~UPERINTENDENT COMMONWEALTH EDISON ORESD~N ~UCLEAR POWERSTATIQN RR 1 MORRIS ILLINOIS 430A 11-21-72

+.

l.SAEC HQS GTWN

. I